InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
ANODES & DIP TUBES on WATER HEATERS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPE NOISES
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  CAD CELL RELAY SWITCH
  Check Valves Flow Control Valves Flo Control
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  DIAGNOSE & FIX BOILER
  DRAFT REGULATORS, BAROMETRIC DAMPERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
  Types of Boiler Defects
  Air-bound radiators, baseboards, boilers
  COMBUSTION AIR DEFECTS
  Diagnose Loss of Heat
  Diagnose Oil Heat Noises
  GAS BURNER Flame & Noise Defects
  OIL BURNER NOISE SMOKE ODORS
  OIL BURNER SOOT & PUFFBACKS
  Heat Won't Turn Off - Stop Unwanted Heat
  Heating Malfunctions & Implications
  Heating Defects & Implications
  Leaks at Heating Boilers
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch

COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE

DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR

ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings

EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR

FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
  BACKDRAFTING HEATING EQUIPMENT
  CAD CELL RELAY SWITCH
  DIAGNOSE & FIX FURNACE
  DRAFT HOODS
  DRAFT REGULATORS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  FAN AUTO ON CONTROLS
  FAN LIMIT SWITCH
  FAN LIMIT SWITCH TROUBLESHOOTING
  FAN MOTOR START CAPACITORS
  FIRE SAFETY CONTROLS
  HEAT EXCHANGER CLEANING
  HEAT EXCHANGER LEAKS
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  ZONE DAMPER CONTROLS

FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION

GAS BURNER Flame & Noise Defects
GAS DETECTION & MEASUREMENT
GAS EXPOSURE EFFECTS, TOXIC
GAS FIRED WATER HEATERS

GAS PIPING, VALVES, CONTROLS
  Gas BTUH & Cubic Feet
  Gas Conversion LP Natural Gas
  Gas Flame & Noise Defects
  Gas Igniter Defects, Repairs
  Gas Leak Detection
  Gas Lighting Pipes & Fixtures
  Gas Meters
  Gas Piping Defects
  Gas Regulators for Appliances
  Gas Regulators for LP Tanks
  Gas Regulators, Two Stage
  Gas Shutoff Valves
  LP Gas Tanks
  LP & Natural Gas Safety Hazards
  LP & Natural Gas Pressures
  METHANE GAS SOURCES
  Natural Gas Combustion Products
  Types of Fuel Gas Source

GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL TANKS
HEATING SMALL LOADS
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES

HOT WATER HEATERS
HOT WATER IMPROVEMENT

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
METHANE GAS SOURCES

MIXING / ANTI-SCALD VALVES
MIX VALVE SCALD PROTECTION, Best Practices

MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion Products

NO HEAT - BOILER / FURNACE DIAGNOSIS

NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for PLUMBING
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL & GAS PIPING
  GAS PIPING, VALVES, CONTROLS
  OIL TANK PIPING & PIPING DEFECTS

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION

OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL

SOLAR ENERGY SYSTEMS
SOLAR HEATING SYSTEM DESIGNS

SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BANGING HEATING PIPE NOISES
  CAD CELL RELAY SWITCH
  Check Valves Flow Control Valves Flo Control
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  Pressure & Temperature Settings, Controls
  Pressure Switch, Steam Boiler
  RELIEF VALVES - STEAM TP VALVES
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  Steam Vents
  THERMOSTATS, HEATING / COOLING
  LOW WATER CUTOFF CONTROLS
  Water Feeder Valves, Steam

TANKLESS COILS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

THERMOSTATS, HEATING / COOLING

Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION

WATER SOFTENERS & CONDITIONERS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

More Information

Photograph of an LP gas leak at a flare fitting (C)DJ Friedman 2007 Find leaks in gas piping: How to Identify & Correct LP Gas or Natural Gas Leaks
InspectAPedia®  -    

  • How to Identify & Correct LP Gas or Natural Gas Leaks in gas piping, at controls, valves, regulators, connections, and appliances
  • How to report defects found in oil or gas piping inspections
  • Home inspection report language examples for oil or gas piping defects and leaks
  • Questions & answers about troubleshooting LP gas or natural gas leaks in gas piping or appliances

Detect or find gas leaks in natural gas or LP gas / propane piping, fittings, & appliances: This article describes how to find gas leaks on LP or natural gas piping, regulators, or appliances, and it provides free sample draft home inspection report language for reporting defects in oil and gas piping at residential properties.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article series provides descriptions and photographs of unsafe gas piping, indications of unsafe or improperly operating gas appliances, gas meters, and other gas installation defects are provided.

Watch out: improper installation and even improper inspection and testing methods involving natural or "LP" gas can involve dangerous conditions and risk fire or explosion. If you smell gas you should leave the building immediately and should do so without doing anything that could create a spark such as operating a light switch or telephone. From a safe location, call your gas company's emergency line and/or your fire department. The text provided here is a working draft and may be incomplete or inaccurate.

Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution. Also see How to Report Defects in Oil Piping.

NOTICE: while example report language is provided here, reproduction of this or any of our web pages or their contents at other websites or in printed documents for sale is prohibited.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How to Test or Look for LP Gas System Leaks

Here we outline some common procedures used to test gas piping and fittings for leaks. These procedures should work equally well for both LP gas (propane or bottled gas) systems and for natural gas (piped-in gas from a gas utility company) systems.

NOTE: Except that LP gas and natural gas operate at different pressures and thus will have different test pressure specifications. Readers who are interested in gas leak detection equipment should review our article and gas testing warnings at Recommendations for gas measurement instruments & gas detector tubes for indoor gas level tests which includes our description of use of the TIF8800 and similar gas detectors.

General Safety Warnings for LP or "bottled" or "propane" Gas Installations & Inspections

Immediate LP or natural gas safety hazards: if there is evidence of an LP or natural gas leak at a building, gas odors, for example, you should:

  • Do not do anything that is likely to cause a gas explosion, such as lighting a match, operating an electrical switch, or even using a telephone in the building
  • Leave the building immediately and keep a safe distance away - 100 feet or more.
  • Notify other building occupants of the safety concern
  • Contact the local gas company and/or fire department

Heating equipment which the inspector (or building occupant or manager) judges to be an immediate life safety hazard should be shut down and appropriate emergency services called.

Pressure testing a gas piping system for evidence of gas leaks

These two methods are generally used to test a gas piping distribution system to see if leaks are present.

  • Low Pressure Method Gas leak tests by gas service technicians generally include the following steps:
    • All gas piping connections, valves, and appliance connections and valves are inspected visually for tightness and good condition
    • A gas pressure gauge [such as the Fisher™ Type 50P-2 gas pressure gauge] is connected to a burner orfice
    • The gas service valve is opened to permit gas to flow into the gas piping distribution system, and then the valve is closed again, securely
    • The gas pressure gauge should read eight inches of water column in pressure (previously 9 inches, earlier eleven inches of water column) and should hold steady.
    • The gas pressure at the point of testing, say a gas-fired heating appliance, is bled off slowly until the gas pressure test instrument gauge indicates nine inches of water column.
    • The system is monitored for any pressure drop for at least three minutes. If no pressure drop is detected the system is considered not leaking.
  • High pressure gas leak method is also used by gas service technicians and includes steps similar to those above, using a special fitting [such as the Fisher(TM) Type J600 test block] installed between the service valve outlet port at the LP gas tank. The service valve is opened,as above, to pressurize the gas piping, and the system is bled down to a test pressure of 10 psig, then monitored for at least three minutes to check for a pressure drop.

Thanks to reader Tony Martinez for updating our data on the proper pressure for LP or Natural Gas leak testing. Thanks to another reader JR, an industry manager familiar with gas pressures, who adds that these two fuel gases operate at different pressures. In residential appliances

  • Natural Gas system pressure: Natural gas operates at a nominal pressure of 7” WC (about 0.253 psi)
  • LPG or Liquid Propage Gas system pressure: LP gas or propane operates at a nominal pressure of 11” WC (about 0.397 psi)
  • Actual NG or LPG gas pressures vary: [Note: the exact pressure you see in the building at an appliance may vary from these numbers depending on the gas distribution piping system size, diameter, number of appliances served, number of appliances operating, regulator adjustment, and other factors. See Gas Regulators for Appliances and Gas Regulators for LP Tanks. See LP or Natural Gas Pressures for a table showing the range of variation in LP gas pressure in the tank at various temperatures. - Ed.]

and adds:

Watch out: Extinguish gas pilot lights - in order to perform pressure-testing methods for LP or natural gas leak detection as discussed above, you will need to extinguish the pilot lights on all gas-fired appliances in the building, and the pilot lights will need to be re-lit again after testing is complete.

Methods used to find and identify points of gas leaks in a gas piping distribution system or at a gas appliance

Photograph of an LP gas leak at a flare fitting (C)DJ Friedman 2007

Visual Inspection for Evidence of Gas Leaks in fuel gas lines and appliances: Our photograph shows black stains on copper tubing at the flare fitting connecting an LP gas line to a shutoff valve.

Some service technicians point to stains on piping as an evidence of a possible chronic leak in the gas line at this point.

  • Gas odors observed during gas piping inspection: The mercaptan put into LP gas and natural gas is inserted there by the gas company as a safety feature so that people may notice that they have a dangerous (explosive) gas leak in their home. Some people may confuse this odor with a septic tank gas odor. See Diagnosing and Curing Sewer Gas Smells and Septic Tank Odors for a discussion of sewer gas odors.
  • "Soap solution" bubble tests for gas leaks: a solution of soapy water (some technicians use dish soap and a brush or rag) is the most common method used to test for gas leaks. As we noted earlier, Readers who are interested in gas leak detection equipment should review our article and gas testing warnings at Recommendations for gas measurement instruments & gas detector tubes for indoor gas level tests which includes our description of use of the TIF8800 and similar gas detectors.
  • Soap solution is applied at every piping joint or connection (or the test instrument may be used carefully at and around every connection or other suspect point) and the technician watches the soaped connection to see if soap bubbles are formed. Experts warn that this method requires some experience and care. For example, a large gas leak may blow away the solution without forming a soap bubble, or bubbles may be forming in a location which is physically hard to see.(Sometimes we can "see" around a corner or to the back side of a pipe using our TIF 8800 combustible gas detector in these cases.)
  • Soap solution is applied along gas piping to lengths of piping to test for pinholes or mechanical damage if no leaks are found at threaded or flared connectors but when gas leaks are evident in the system.
  • Gas leaks at gas valves: we very often find very small gas leaks at the seamed sides of some gas valves, such as those commonly found on gas-fired domestic water heaters, especially when using the TIF 8800. These leaks can be so miniscule that they do not show up during a bubble test, and they are often present even on new valves. This may be a source of some disagreement between a home inspector, building owner, and the gas service technician, and need to be handled with some judgment, experience, and reason.

Identifying Sources of Leaks at Brass Flare Fittings on LP Gas Piping Systems

Photograph of a leaky brass flare fitting Photograph of a brass flare fitting in good condition

Here are two brass flare fittings. One of them had a gouge that gave us a gas leak that was a bit tough to find until we disassembled and inspected the leaky joint.

If tightening flared copper tubing connections does not easily correct a leak at that joint, do not just over-tighten the joint (you may break the flare and cause a still larger leak), and do not rely on pipe sealant inside of flared copper tubing fittings.

Open and inspect the flare fitting joint, and replace the flare fittings or make a new copper tubing flared end if necessary.

Also see Advice for Making Flare Fitting Connections with Copper Tubing or Piping where we describe preparation of the flare joint for flexible copper tubing for refrigeration or gas piping lines.

Questions & Answers regarding this article

Questions & answers about troubleshooting LP gas or natural gas leaks in gas piping or appliances .

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

GAS PIPING, VALVES, CONTROLS
  Gas BTUH & Cubic Feet
  Gas Conversion LP Natural Gas
  Gas Flame & Noise Defects
  Gas Igniter Defects, Repairs
  Gas Leak Detection
  Gas Lighting Pipes & Fixtures
  Gas Meters
  Gas Piping Defects
  Gas Regulators for Appliances
  Gas Regulators for LP Tanks
  Gas Regulators, Two Stage
  Gas Shutoff Valves
  LP Gas Tanks
  LP & Natural Gas Safety Hazards
  Natural Gas Combustion Products
  Types of Fuel Gas Source

  • National Fuel Gas Code, 1988 articles 2.6.2, 2.6.3, & 3.4.2 "Piping in Partitions". Also NFPA 58 Code. See ANSI Z223.1-NFPA 54.
  • Residential Gas Hot Water Heater Pocket Partner - Testing and Trouble Shooting, State Corp., Ashland City, TN 37015
  • U.S. Energy Information Administration - eia.doe.gov/
  • U.S. Environmental Protection Agency - epa.gov/solar/energy-and-you/affect/natural-gas.html
  • At Natural Gas.Org www.naturalgas.org/environment/naturalgas.asp#emission you’ll find a table of combustion products
  • At geocities.com/rainforest/6847/report1.html is an interesting and detailed though not “neutral” report on the components and contaminants in the combustion of natural gas. You’ll see a long long list of emissions products, but look again – most of the contaminant levels listed are in the picograms.
  • apvgn.pt/documentacao/iangv_rep_part1.pdf lists the components in natural gas exhaust from vehicles
  • The Need Project, Manassas, VA: need.org/needpdf/infobook_activities/SecInfo/NGasS.pdf
  • Kroschwitz, Jacqueline I., and Mary Howe-Grant (eds.). "Gas, Natural." In Encyclopedia of Chemical Technology. 4th ed., vol. 12. New York: John Wiley and Sons, Inc., 1993.
  • Tussing, Arlon R., & Bob Tippee. The Natural Gas Industry: Evolution, Structure, and Economics. 2nd ed. Tulsa, OK: PennWell Publishing, 1995.
  • Thanks to reader Tony Martinez for technical editing regarding the test pressures for gas leak evaluation - 3/19/2010.
  • Thanks to reader JR for discussing LP and natural gas operating pressures and leak detection safety, October 2010.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Cheating on water tests: Testing Water for Real Estate Transactions - make sure your water test is valid
  • Don't Flush these things into a septic system
  • Drain Noises: may indicate defective or clogged plumbing: how to diagnose and cure drain sounds
  • Drinking Water Testing Advice for home buyers home owners home inspectors
  • Interpreting Drinking Water Test Results and Correcting Unsatisfactory Water
  • Drinking Water Contaminant Levels - Maximum Allowed
  • HOT WATER HEATERS - a detailed guide to all types of hot water sources, problems, inspection, repair
  • Lead Contamination in Drinking Water: Testing & Correction - Advice (This Article)
  • Lead Testing & Correcting Contamination from Lead Water Supply Lines/Entry Mains - Lead Pipe Problems/Advice
  • SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR The Septic Systems Information Website
  • Sewage Odors in Wet or Cold Weather - Septic Odors or Sewage Odor Diagnosis & Repair Guide for diagnosing and eliminating cold weather sewer gas odors
  • Sewage Levels in Septic Tanks - what are normal and abnormal sewage levels in septic tanks and what do they mean about tank condition, leaks, etc.
  • Sewer Line Replacement diagnosing a clogged drain leads to drain line replacement - step by step photo-illustrated guide to drain replacement
  • Water Pressure Loss - Diagnosis how to determine why water pressure has been lost or why there is no water at all in a building
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water testing for Pesticides: comprehensive and pesticides-example parameters
  • Water Testing: background comments on classes of water contaminants, & links to home buyer advice about water testing, drinking water, water supply
  • When and How to Shock or Chlorinate a Well - Procedure for Shocking a Well to (temporarily or maybe longer) "Correct" Bacterial Contamination
  • Water Requirements, Home & Outdoor Living
  • Typical Water Tests & Fees this water test fee schedule applies when testing is combined with other onsite building inspection services
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water pressure tank failures & water pump short cycling diagnosis and repair
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com