InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
ANODES & DIP TUBES on WATER HEATERS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPE NOISES
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  CAD CELL RELAY SWITCH
  Check Valves Flow Control Valves Flo Control
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  DIAGNOSE & FIX BOILER
  DRAFT REGULATORS, BAROMETRIC DAMPERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
  Types of Boiler Defects
  Air-bound radiators, baseboards, boilers
  COMBUSTION AIR DEFECTS
  Diagnose Loss of Heat
  Diagnose Oil Heat Noises
  GAS BURNER Flame & Noise Defects
  OIL BURNER NOISE SMOKE ODORS
  OIL BURNER SOOT & PUFFBACKS
  Heat Won't Turn Off - Stop Unwanted Heat
  Heating Malfunctions & Implications
  Heating Defects & Implications
  Leaks at Heating Boilers
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch

COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE

DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR

ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings

EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR

FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEAING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
  BACKDRAFTING HEATING EQUIPMENT
  CAD CELL RELAY SWITCH
  DIAGNOSE & FIX FURNACE
  DRAFT HOODS
  DRAFT REGULATORS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  FAN AUTO ON CONTROLS
  FAN LIMIT SWITCH
  FAN LIMIT SWITCH TROUBLESHOOTING
  FAN MOTOR START CAPACITORS
  FIRE SAFETY CONTROLS
  HEAT EXCHANGER CLEANING
  HEAT EXCHANGER LEAKS
  Reset Switch - Primary Control
  Reset Switch - electric motors
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  ZONE DAMPER CONTROLS

FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION

GAS BURNER Flame & Noise Defects
GAS DETECTION & MEASUREMENT
GAS EXPOSURE EFFECTS, TOXIC
GAS FIRED WATER HEATERS

GAS PIPING, VALVES, CONTROLS
  Gas BTUH & Cubic Feet
  Gas Conversion LP Natural Gas
  Gas Flame & Noise Defects
  Gas Igniter Defects, Repairs
  Gas Leak Detection
  Gas Lighting Pipes & Fixtures
  Gas Meters
  Gas Piping Defects
  Gas Regulators for Appliances
  Gas Regulators for LP Tanks
  Gas Regulators, Two Stage
  Gas Shutoff Valves
  LP Gas Tanks
  LP & Natural Gas Safety Hazards
  LP & Natural Gas Pressures
  METHANE GAS SOURCES
  Natural Gas Combustion Products
  Types of Fuel Gas Source

GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS

HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION

HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL TANKS
HEATING SMALL LOADS
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES

HOT WATER HEATERS
HOT WATER IMPROVEMENT

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
METHANE GAS SOURCES

MIXING / ANTI-SCALD VALVES
MIX VALVE SCALD PROTECTION, Best Practices

MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion Products

NO HEAT - BOILER / FURNACE DIAGNOSIS

NOISE / SOUND DIAGNOSIS & CURE
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for PLUMBING
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS

OIL & GAS PIPING
  GAS PIPING, VALVES, CONTROLS
  OIL TANK PIPING & PIPING DEFECTS

OIL LINE CLOGGING FIX
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION

OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

Reset Switch - Heater Primary Control
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL

SOLAR ENERGY SYSTEMS
SOLAR HEATING SYSTEM DESIGNS

SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BANGING HEATING PIPE NOISES
  CAD CELL RELAY SWITCH
  Check Valves Flow Control Valves Flo Control
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  Pressure & Temperature Settings, Controls
  Pressure Switch, Steam Boiler
  RELIEF VALVES - STEAM TP VALVES
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  Steam Vents
  THERMOSTATS, HEATING / COOLING
  LOW WATER CUTOFF CONTROLS
  Water Feeder Valves, Steam

TANKLESS COILS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

THERMOSTATS, HEATING / COOLING

Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION

WATER SOFTENERS & CONDITIONERS

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves
Woodstove Safety

More Information

Photograph of abandoned gas piping Gas Piping Defects: How to Identify & Report LP Gas or Natural Gas Fuel Piping Problems
InspectAPedia®  -    

  • How to Identify & Report LP Gas or Natural Gas Fuel Piping Defects
  • LP Gas Regulator Installation Requirements
  • LP Gas Regulator Inspection Procedure
  • LP Gas Piping Defect List & sample home inspection report language
  • Natural gas piping defects, leaks, leak detection, troubleshooting & reporting
  • How to inspect, report, & correct abandoned gas equipment and old gas lighting piping & fixtures
  • Gas Piping Maintenance Tips for LP gas (bottled gas or propane gas) & for piped-in natural gas
  • Home inspection report language examples for gas piping defects and safety hazards
  • Questions & answers about gas piping in buildings: defects, inspection, trougleshooting, leaks, repairs

Gas piping in buildings: defects, inspection, trougleshooting, leaks, repairs: in this article series on gas piping we provide descriptions and photographs of unsafe gas piping, indications of unsafe or improperly operating gas appliances, gas meters, and other gas installation defects are provided.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article series on gas piping, lighting, fixtures, and related topics provides free sample draft home inspection report language for reporting defects in oil and gas piping at residential properties.

General safety warning: improper installation and even improper inspection and testing methods involving natural or "LP" gas can involve dangerous conditions and risk fire or explosion. If you smell gas you should leave the building immediately and should do so without doing anything that could create a spark such as operating a light switch or telephone. From a safe location, call your gas company's emergency line and/or your fire department. The text provided here is a working draft and may be incomplete or inaccurate.

Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution. Also see How to Report Defects in Oil Piping. NOTICE: while example report language is provided here, reproduction of this or any of our web pages or their contents at other websites or in printed documents for sale is prohibited.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How to Identify & Report LP Gas or Natural Gas Fuel Piping Defects

Safety Warnings for Gas Leaks

Immediate LP or natural gas safety hazards: if there is evidence of an LP or natural gas leak at a building, gas odors, for example, you should:

  • Do not do anything that is likely to cause a gas explosion, such as lighting a match, operating an electrical switch, or even using a telephone in the building
  • Leave the building immediately and keep a safe distance away - 100 feet or more.
  • Notify other building occupants of the safety concern
  • Contact the local gas company and/or fire department

Heating equipment which the inspector (or building occupant or manager) judges to be an immediate life safety hazard should be shut down and appropriate emergency services called. See Gas Leak Detection for leak detection procedures and alternatives.

LP Gas Regulator Installation Requirements

  • Gas regulator ground clearance: LP gas regulators should be installed at least eighteen inches above the surface of the ground. In areas of deep snow the regulator should really be above the snow level (or protected from weather)
  • Protect gas regulator from weather: the LP gas regulator(s) should not be located where they are exposed to large amounts of water (or ice) such as below a roof eave with no gutter, or close to a downspout opening.
  • Gas regulator hoods: The LP Gas regulator installed outdoors should [in best practice] have a protective hood to avoid damage from rain or (in freezing climates) ice. If an LP gas regulator is being installed horizontally, that is without pointing it's vent opening down, it must be protected by a cover, and even under the cover the vent should slope down to avoid risk of accumulating condensate and frost blockage, an condition which would be unsafe as frost or ice can prevent safe operation of the gas pressure regulator.
  • Point vents down: Where a regulator is installed outside without such protection, it is very important that the regulator is placed with its vent pointed straight down so that rain and ice do not enter and possibly block the vent - a dangerous condition
  • Distance between LP gas regulator and building openings: LP gas regulators should be installed at least five feet from any building window or vent or air intake (ten feet if a buried LP tank is in use).

LP Gas Regulator Inspection Procedure

The LP Gas regulator(s) should be inspected each time that the building receives an LP gas delivery.

  • Turn off the LP gas service valve at the tank and check for gas odors anywhere. If gas odors are present we suspect the main shutoff valve is defective and it may need replacement.
  • Check that the LP gas regulator is properly installed, sloped so that its vent will drain, and that it is protected from the weather
  • Check that the LP gas regulator vent has not become blocked. We sometimes find that insects will nest in openings on these devices, blocking the vent screen with mud or insect nest materials. Make sure the regulator vent has not become blocked with anything whatsoever.
  • Check the LP gas regulator for evidence that water has leaked into it by looking into the regulator's cover-cap (a removable cap). A service technician may also shut down the gas system and remove the regulator's adjusting screw to check the regulator interior for corrosion. It is particularly important to look for evidenceof corrosion in the pressure relief valve area inside the regulatorr, since if this component is corroded the relief valve may not function safely.
  • Gas service experts recommend replacing an LP gas regulator if it is more than fifteen years old.

LP Gas Piping Defect List & sample home inspection report language

Safety warnings about gas piping: Check condition of flexible gas line connections: Caution: home inspectors and other private building inspectors do not pull out appliances to look at gas line connections, but you should do so, or have your service technician do so, in order to check condition of flexible connections for leaks and assuring that a shutoff valve is installed. Watch for leaks in those flex-connector lines between gas line and the appliance as they are thin wall and often corrode and leak. Gas leaks are dangerous.

Safety warning. Flexible soft copper piping defect example: if flexible soft copper tubing has been used to supply municipal (natural) gas to a electric clothes dryer, hot water heater, or heating system, this is not a recommended installation and it may be prohibited by local codes - "black iron" steel piping is required in many jurisdictions.

Safety warning: Flexible ridged thin wall copper tubing defects: if flexible "corrugated" or flexible thin-wall copper tubing been used to supply gas to a hot water heater, or heating system, this is not a recommended installation and it may be prohibited by local codes.

Technical Violation: Flexible copper LP gas line may not be routed through walls or similar locations where it may be damaged or punctured. For these sections of routing threaded iron pipe is required. This is an usually inexpensive item to correct. You can discuss this point further with your gas supplier and your plumber.

All gas or oil piping must comply with local codes and ordinances or with the national fuel gas codes. Copper and brass tubing (except tin lined copper) shall not be used if the gas contains more than an average of .3 grains of hydrogen sulfide per 100 standard cubic feet of gas.

Photograph of gas lighting in a pre-1900 home"Abandoned" live gas piping: Watch out: don't assume that all "old or antique gas pipes" in a building have been actually disconneted from the gas supply.

We have found "live" gas supplied in fireplaces in older homes where a gas log or heater had previously been installed and "live gas" supplied at antique gas lighting fixtures that occupants thought had been disconnected. An example of a surprising "live" gas light is shown in our home inspection photo (left) from a New York home constructed in the 1920's. See Gas Lighting Pipes & Fixtures

*** Safety: gas line loose: At [record location of observed piping defect] you will need to provide better for the gas piping. Loose piping risks dangerous gas leaks. Even if you did not observe/smell a leak at this location when we inspected. This item should be handled as soon as possible.

*** Safety: We recommend that unused gas equipment be removed and that you have the unused section of gas line properly sealed by a qualified plumber or by your gas supplier. Leaky old appliances or gas lines are dangerous.

Gas Piping Maintenance Tips

MAINTENANCE TIP: Openings where the gas supply pipe enters the building should be caulked to reduce possible water or insect/rodent pest entry.

Safety Recommendation: the gas supply line at
... is not installed according to the manufacturer's recommendations. Proper iron pipe plumbing with sediment trap, also called a "drip leg" (typically at least 3" long off of a "tee" at same height as the gas control) should be installed. This is an inexpensive plumbing correction and it should corrected soon to avoid moisture damage to the gas controls. (Note that depending on the quality of the gas being delivered in some municipalities, the installation of a drip leg or dirt leg may not be required by local officials.

*** Safety: gas line loose: At
...
better support is needed for the gas piping. Loose piping risks dangerous gas leaks.
... We did not observe/smell a leak at this location when we inspected. This item should be handled as soon as possible.

*** Safety:We recommend that unused gas equipment be removed and that you have the unused section of gas line properly sealed by a qualified plumber or by your gas supplier. Leaky old appliances or gas lines are dangerous.

Questions & Answers regarding this article

  • Questions & answers about gas piping in buildings: defects, inspection, trougleshooting, leaks, repairs

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

GAS PIPING, VALVES, CONTROLS
  Gas BTUH & Cubic Feet
  Gas Conversion LP Natural Gas
  Gas Flame & Noise Defects
  Gas Igniter Defects, Repairs
  Gas Leak Detection
  Gas Lighting Pipes & Fixtures
  Gas Meters
  Gas Piping Defects
  Gas Regulators for Appliances
  Gas Regulators for LP Tanks
  Gas Regulators, Two Stage
  Gas Shutoff Valves
  LP Gas Tanks
  LP & Natural Gas Safety Hazards
  Natural Gas Combustion Products
  Types of Fuel Gas Source

  • U.S. Energy Information Administration - eia.doe.gov/
  • U.S. Environmental Protection Agency - epa.gov/solar/energy-and-you/affect/natural-gas.html
  • At Natural Gas.Org www.naturalgas.org/environment/naturalgas.asp#emission you’ll find a table of combustion products
  • At geocities.com/rainforest/6847/report1.html is an interesting and detailed though not “neutral” report on the components and contaminants in the combustion of natural gas. You’ll see a long long list of emissions products, but look again – most of the contaminant levels listed are in the picograms.
  • apvgn.pt/documentacao/iangv_rep_part1.pdf lists the components in natural gas exhaust from vehicles
  • The Need Project, Manassas, VA: need.org/needpdf/infobook_activities/SecInfo/NGasS.pdf
  • Kroschwitz, Jacqueline I., and Mary Howe-Grant (eds.). "Gas, Natural." In Encyclopedia of Chemical Technology. 4th ed., vol. 12. New York: John Wiley and Sons, Inc., 1993.
  • Tussing, Arlon R., & Bob Tippee. The Natural Gas Industry: Evolution, Structure, and Economics. 2nd ed. Tulsa, OK: PennWell Publishing, 1995.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Cheating on water tests: Testing Water for Real Estate Transactions - make sure your water test is valid
  • Don't Flush these things into a septic system
  • Drain Noises: may indicate defective or clogged plumbing: how to diagnose and cure drain sounds
  • Drinking Water Testing Advice for home buyers home owners home inspectors
  • Interpreting Drinking Water Test Results and Correcting Unsatisfactory Water
  • Drinking Water Contaminant Levels - Maximum Allowed
  • HOT WATER HEATERS - a detailed guide to all types of hot water sources, problems, inspection, repair
  • Lead Contamination in Drinking Water: Testing & Correction - Advice (This Article)
  • Lead Testing & Correcting Contamination from Lead Water Supply Lines/Entry Mains - Lead Pipe Problems/Advice
  • SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR The Septic Systems Information Website
  • Sewage Odors in Wet or Cold Weather - Septic Odors or Sewage Odor Diagnosis & Repair Guide for diagnosing and eliminating cold weather sewer gas odors
  • Sewage Levels in Septic Tanks - what are normal and abnormal sewage levels in septic tanks and what do they mean about tank condition, leaks, etc.
  • Sewer Line Replacement diagnosing a clogged drain leads to drain line replacement - step by step photo-illustrated guide to drain replacement
  • Water Pressure Loss - Diagnosis how to determine why water pressure has been lost or why there is no water at all in a building
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water testing for Pesticides: comprehensive and pesticides-example parameters
  • Water Testing: background comments on classes of water contaminants, & links to home buyer advice about water testing, drinking water, water supply
  • When and How to Shock or Chlorinate a Well - Procedure for Shocking a Well to (temporarily or maybe longer) "Correct" Bacterial Contamination
  • Water Requirements, Home & Outdoor Living
  • Typical Water Tests & Fees this water test fee schedule applies when testing is combined with other onsite building inspection services
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water pressure tank failures & water pump short cycling diagnosis and repair
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com