InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
SEPTIC SYSTEM INSPECT DIAGNOSE REPAIR

ADDITIVES / TREATMENTS for SEPTIC SYSTEMS
AEROBIC SEPTIC SYSTEMS
ALTERNATING BED SEPTIC SYSTEMS

BACKUP PREVENTION, SEWER LINE
BIOLOGICAL POLLUTANTS
BIOLOGICAL POLLUTANTS in the HOME - EPA
BOOKS, RECOMMENDED SEPTIC
BOOKSTORE, SEPTIC SYSTEMS

CESSPOOLS
CESSPOOL SAFETY WARNINGS
CHECK VALVES
CHEMICALS & TREATMENTS for SEPTICS
CHLORAMINE / CHLORINE Tests
CHLORINE IN DRINKING WATER
CHLORINE IN SEPTIC WASTEWATER
CISTERNS

D BOX TROUBLESHOOTING
DEFINITIONS OF SEPTIC SYSTEM TERMS
DIFFICULT SEPTIC SITES
DISTRIBUTION-BOX INSPECTION, SEPTIC
DRAINFIELD FAILURE DIAGNOSIS
DRIVING or PARKING OVER SEPTIC
DRYWELL DESIGN & USES

FILTERS SEPTIC & GREYWATER
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODED SEPTIC SYSTEMS, REPAIR

GARBAGE DISPOSAL vs SEPTICS
GRAVELLESS SEPTIC SYSTEMS
GRAVITY/SIPHON DOSING SYSTEMS
GREYWATER SYSTEMS

HOME BUYERS GUIDE to SEPTIC SYSTEMS
HOME SELLERS GUIDE TO SEPTIC INSPECT

LAGOON SEPTIC SYSTEMS
LEACHFIELD FAILURE DIAGNOSIS

MEDIA FILTER SEPTIC SYSTEMS
MOUND SEPTIC SYSTEMS

NOISE / SOUND DIAGNOSIS & CURE

ODORS & SMELLS DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST
ODORLESS CHEMICALS / GASES: CHECK FOR?
ODORS, PLUMBING SYSTEM
ODORS, SEPTIC or SEWER
ODORS, SULPHUR SMELL SOURCES

OUTHOUSES & LATRINES

PLANTS & TREES OVER SEPTIC SYSTEMS
PRESSURE DOSING SEPTIC SYSTEMS

RAISED BED SEPTIC SYSTEMS

SAND BED SEPTIC SYSTEMS
SEEPAGE PITS

SEPTIC & CESSPOOL SAFETY
SEPTIC SYSTEM ARTICLES
SEPTIC AUTHORITIES
  75-A.0 New York State Regulation of Private Septic Systems
  75-A.1 Introduction to Septic Systems, Definitions of Septic System Terms
  75-A.2 Regulation of Sewage Treatment Systems by other agencies
  75-A.3 Sewage flows and design flow estimates
  75-A.4 Soil and site appraisal for Septic Systems
  75-A.5 House or building sewer line specifications
  75-A.6 Septic tank capacity requirements, installation, and placement
  75-A.7 Distribution lines, distribution boxes, gravity flow, pressure distribution, dosing, siphons
  75-A.8 Subsurface treatment of effluent, absorption field requirements, leach field design criteria
  75-A.9 Alternative Septic System Designs
  75-A.10 Other systems
  75-A.11 New product/system design interim approval
SEPTIC BACKUP PREVENTION
SEPTIC BACKUP REPAIR
SEPTIC BOOK, ONLINE
SEPTIC BOOKSTORE
SEPTIC BIOMATS

SEPTIC CARE INSTRUCTIONS
SEPTIC CLEARANCE DISTANCES
SEPTIC CODES & REFERENCES
SEPTIC CONSULTANTS

SEPTIC D-BOX INSPECTION

SEPTIC DRAINFIELD FAILURE DIAGNOSIS
SEPTIC DRAINFIELD INSPECTION & TEST
SEPTIC DRAINFIELD LIFE
SEPTIC DRAINFIELD LOCATION
SEPTIC DRAINFIELD RESTORERS?
SEPTIC DRAWINGS

SEPTIC DYE TEST PROCEDURE

SEPTIC FAILURE LAWSUIT
SEPTIC FAILURE SIGNS
SEPTIC FIELD INSPECTION
SEPTIC FILTERS
SEPTIC FLOOD RESPONSE

SEPTIC INSPECTION BOOK
SEPTIC INSPECTION & TEST GUIDE
SEPTIC LIFE EXPECTANCY
SEPTIC LIFE MAXIMIZING STEPS

SEPTIC METHANE GAS
SEPTIC ODORS

SEPTIC PUMPS
SEPTIC PUMPING REPAIR

SEPTIC REFERENCES

SEPTIC & CESSPOOL SAFETY
SEPTIC SUPPLIES & PARTS
SEPTIC SYSTEM DEFINITIONS

SEPTIC SYSTEM DESIGN ALTERNATIVES
  Master List of Septic System Types
  ALTERNATIVE SEPTIC DESIGNERS
  ALTERNATIVE SEPTIC PRODUCTS
  AEROBIC SEPTIC SYSTEMS
  ALTERNATING BED SEPTIC SYSTEMS
  BIOGAS PRODUCTION & USE
  CESSPOOLS
  DISINFECTION SYSTEMS, SEPTIC EFFLUENT
  DRYWELL DESIGN & USES
  EVAPORATION-TRANSPIRATION SEPTIC SYSTEMS
  FILTERS SEPTIC & GREYWATER
  FIXED-FILM PROCESS SEPTIC SYSTEMS
  GRAVELLESS SEPTIC SYSTEMS
  GRAVITY/SIPHON DOSING SYSTEMS
  GREYWATER SYSTEMS
  HOLDING TANK SEPTIC SYSTEMS
  LAGOON SEPTIC SYSTEMS
  MEDIA FILTER SEPTIC SYSTEMS
  MOUND SEPTIC SYSTEMS
  OUTHOUSES & LATRINES
  PEAT FILTER SEPTICS
  PRESSURE DOSING SEPTIC SYSTEMS
  RAISED BED SEPTIC SYSTEMS
  SAND BED SEPTIC SYSTEMS
  SEEPAGE PITS
  SEPTIC SYSTEM PUMPS
  SEQUENCING BATCH SEPTIC SYSTEMS
  SEWAGE TREATMENT SYSTEMS
  STEEP SLOPE SEPTIC DESIGNS
  TOILETS, INSPECT, INSTALL, REPAIR
  TOILET ALTERNATIVES
  TOILET TYPES
  Toilet Types, Flush Methods
  TOILETS, DON'T FLUSH LIST
  TRAPS on PLUMBING FIXTURES
  VEGETATED SUBMERGED SEPTIC BEDS
  Wastewater Treatment Levels
  Wastewater Dispersal Methods
  WETLAND SEPTIC SYSTEMS

SEPTIC SYSTEM DESIGN BASICS
  DRYWELL DESIGN & USES
  FILTERS SEPTIC & GREYWATER
  SEEPAGE PITS
  SEPTIC CLEARANCES
  SEPTIC SOIL & PERC TESTS
  SEPTIC TANK SIZE
  SEPTIC TANK DEPTH
  SEPTIC TANK TEES
  SEPTIC DRAINFIELD SIZE
  SEPTIC DRAINFIELD SHAPE
  SEPTIC TANK PUMPING FREQUENCY
  SEPTIC TANK PUMPING PROCEDURE
  SEPTIC SYSTEM PUMPS
  SEPTIC TREATMENTS & CHEMICALS
  STEEP SLOPE SEPTIC DESIGNS
SEPTIC SYSTEM DESIGN MANUAL - Online

SEPTIC DRAINFIELD FAILURE DIAGNOSIS
SEPTIC DRAINFIELD INSPECTION & TEST
SEPTIC DRAINFIELD LIFE
SEPTIC DRAINFIELD LOCATION
SEPTIC DRAINFIELD RESTORERS?
SEPTIC DRAWINGS

SEPTIC DYE TEST PROCEDURE

SEPTIC FAILURE LAWSUIT
SEPTIC FAILURE SIGNS
SEPTIC FIELD INSPECTION
SEPTIC FILTERS
SEPTIC FLOOD RESPONSE

SEPTIC INSPECTION BOOK
SEPTIC INSPECTION & TEST GUIDE
SEPTIC LIFE EXPECTANCY
SEPTIC LIFE MAXIMIZING STEPS

SEPTIC METHANE GAS
SEPTIC ODORS

SEPTIC PUMPS
SEPTIC PUMPING REPAIR

SEPTIC REFERENCES

SEPTIC & CESSPOOL SAFETY
SEPTIC SUPPLIES & PARTS

SEPTIC SYSTEMS, HOME BUYERS GUIDE to

SEPTIC SYSTEM INSPECTION & TEST GUIDE
SEPTIC SYSTEMS INSPECTION COURSE
  SEPTIC INSPECTION TYPES & LEVELS
  SEPTIC FAILURE CAUSES
  SEPTIC TANK GRASS or SNOWMELT
  SEPTIC TANK INSPECTION PROCEDURE
  SEPTIC DRAINFIELD FAILURES
  SEPTIC D-BOX INSPECTION
  SEPTIC DRAINFIELD INSPECTION
  SEPTIC DYE TEST PROCEDURE
  SEPTIC FAILURE CAUSES
  SEPTIC FAILURE CRITERIA
  SEPTIC FAILURE SIGNS
  SEPTIC FAILURE SPOTS
  SEPTIC INSPECTION WORK SHEETS
SEPTIC INSPECTION TYPES & LEVELS

SEPTIC SYSTEM ODORS
SEPTIC SYSTEMS ONLINE BOOK
SEPTIC SYSTEM PUMPS
SEPTIC SYSTEM SAFETY WARNINGS
SEPTIC SYSTEM TYPES, MASTER LIST

SEPTIC TANKS
SEPTIC TANK BAFFLES
SEPTIC TANK COVERS
SEPTIC TANK, HOW TO FIND
  SEPTIC SEARCH SAFETY
  WHO KNOWS SEPTIC LOCATION?
  FIND MAIN WASTE LINE EXIT
  DISTANCE TO SEPTIC TANK
  POSSIBLE SEPTIC TANK LOCATIONS
  VISUAL CLUES LOCATE the SEPTIC TANK
  WHERE TO LOOK for the SEPTIC TANK
  SEPTIC TANK DEPTH
  SEPTIC TANK LOCATING EQUIPMENT
  SEPTIC TANK LOCATION SKETCH
SEPTIC TANK GRASS or SNOWMELT
SEPTIC TANK INSPECTION PROCEDURE
SEPTIC TANK LEAKS
SEPTIC TANK LEVELS of SEWAGE

SEPTIC TANK PUMPING SCHEDULE
SEPTIC TANK PUMPING PROCEDURE
SEPTIC TANK SAFETY
SEPTIC TANK SIZE
SEPTIC TANK TEES
SEPTIC TESTS: DYE & LOADING TESTS
SEPTIC TREATMENTS & CHEMICALS

SEWAGE & SEPTIC CONTAMINANTS
SEWAGE BACKUP, WHAT TO DO
SEWAGE BACKUP TEST & CLEANUP
SEWAGE BACKUP PREVENTION
SEWAGE CONTAMINATION in buildings
SEWAGE CONTAMINANTS in FRUIT / VEGETABLES
SEWAGE EJECTOR / GRINDER PUMPS
SEWAGE LEVELS in SEPTIC TANKS
SEWAGE NITROGEN CONTAMINANTS
SEWAGE PATHOGENS in SEPTIC SLUDGE
SEWAGE PUMPS

SEWER BACKUP PREVENTION
SEWER GAS ODORS
SEWER LINE REPLACEMENT

SINKHOLES, WARNING SIGNS
SMELL PATCH TEST to Track Down Odors
SOAKAWAY BED FAILURE DIAGNOSIS
SULPHUR & SEWER GAS SMELL SOURCES
SUMP PUMPS

TOILETS, INSPECT, INSTALL, REPAIR
TOILET ALTERNATIVES
TOILET FLUSHOMETER VALVES
TOILET INSTALLATION PROCEDURE
TOILET OVERFLOW EMERGENCY
TOILET PLUGS, SEWER BACKUP
TOILET REPAIR GUIDE
TOILET TYPES
Toilet Types, Flush Methods
TOILETS, DON'T FLUSH LIST
TRAPS on PLUMBING FIXTURES
TREATMENTS & CHEMICALS, SEPTIC

VIDEO GUIDES: Septic Videos
WASHING MACHINES

WASTEWATER TREATMENT BASICS

WATER, WELLS, WATER TANKS: TESTING GUIDE
WATER PURIFIERS

WATER QUALITY TESTS, CONTAMINANTS, TREATMENT
WATER QUANTITY IMPROVEMENT
WATER QUANTITY USAGE GUIDE

WATER SOFTENERS & CONDITIONERS
WATER SUPPLY & DRAIN PIPING

WATER TESTS, CONTAMINANTS, TREATMENT
WATER TREATMENT EQUIPMENT CHOICES

WELLS CISTERNS & SPRINGS
WELL CLEARANCES

WETLAND SEPTIC SYSTEMS

More Informationn

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
AIR CONDITIONING & HEAT PUMPS
BOOKSTORE
ELECTRICAL
ENERGY SAVINGS
ENVIRONMENT
EXTERIORS
HEATING
HOME INSPECTION
INDOOR AIR QUALITY
INSULATION
INTERIORS
MOLD INSPECT/TEST/CLEANUP
NOISE
ODORS
PLUMBING
ROOFING
SEPTIC SYSTEMS
SOLAR ENERGY
STRUCTURE
VENTILATION
WATER SUPPLY

ACCURACY & PRIVACY POLICIES
EXPERT DIRECTORY
CONTACT



New York State Septic System Design Regulations 75-A.6 Septic tank design specifications
InspectAPedia®  -         

  • Design specifications for septic tanks
  • Questions & answers about septic tank design specifications & regulations

Septic tank design specifications: Section 6 of the septic design regulations discusses the design specifications for septic tanks, including septic tank size requirements, septic tank cover access, septic tank characteristics, steel septic tanks, tanks for aerobic septic systems, and related details.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This document uses the New York State wastewater treatment standard for individual household septic systems (Appendix 75-A) to provide an example of state regulated design and installation of both conventional tank and leach field septic systems and alternative septic system designs, including raised septic systems, septic mound systems, intermittent sand filter septic systems, and evaportion-transpiration septic systems.

Also see SEPTIC CODES & REFERENCES and SEPTIC CONSULTANTS. Citation of this article by reference to this website and brief quotation for the sole purpose of review are permitted. Use of this information at other websites, in books or pamphlets for sale is reserved to the author. Technical review by industry experts has been performed and is ongoing - reviewers welcomed and are listed at "References."

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Effective Date: 12/01/90 Title: Appendix 75-A.6 - Septic tanks Section 75-A.6 Septic tanks.

(a) General information about Septic Tank Design

(1) Septic tank capacities shall be based upon the number of household bedrooms. An expansion attic shall be considered as an additional bedroom.


Table 3 specifies the minimum septic tank capacities and minimum liquid surface
areas.


TABLE 3

MINIMUM SEPTIC TANK CAPACITIES

NUMBER OF     MINIMUM TANK          MINIMUM LIQUID
BEDROOMS      CAPACITY (GALLONS) SURFACE AREA (SQ. FT.)
------------ ------------------- -----------------------

1, 2, 3        1,000                     27
4              1,250                     34
5              1,500                     40
6              1,750                     47

NOTE: Septic tank size requirements for more than six bedrooms shall be calculated by adding 250 gallons and seven square feet of surface area for each additional bedroom. A garbage grinder shall be considered equivalent to an additional bedroom for determining tank size.

(2) Septic tank covers shall always be accessible. Where manholes are more than 12 inches below final grade, an extension collar shall be provided over each opening. Extension collars shall not be brought flush with the ground surface unless the cover can be locked to prevent tampering. Driveways or other facilities shall not be constructed above septic tanks unless specially designed and reinforced to safely carry the load imposed.

(b) Design and Installation of Septic Tanks

(1) General Requirements for Septic Tanks. The following applies to all septic tanks regardless of material.

(i) A minimum liquid depth of 30 inches. The maximum depth for determining the allowable design volume of a tank shall be 60 inches. Deeper tanks provide extra sludge storage, but no credit shall be given toward design volume.

(ii) The minimum distance between the inlet and outlet shall be six feet. All tanks shall meet the minimum surface area requirement for the specific design volume specified in Table 3. The effective length of rectangular tanks should not be less than two nor greater than four times the effective width.

(iii) Tanks must be watertight, constructed of durable material not subject to corrosion, decay, frost damage, or cracking. After installation, all septic tanks shall be able to support at least 300 pounds per square foot (psf).

(iv) Tanks with a liquid depth of 48 inches or more shall have a top opening with a minimum of 20 inches in the shortest dimension to allow entry into the tank. Tanks with a liquid depth less than 48 inches shall have a top opening that is at least 12 inches in the shortest dimension.

(v) Tanks shall have inlet and outlet baffles, sanitary tees or other devices to prevent the passage of floating solids and to minimize disturbance of settled sludge and floating scum by sewage entering and leaving the tank. Outlet designs such as gas deflection baffles are strongly recommended in all tanks. Inlet and outlet baffles shall extend a minimum of 12 inches and 14 inches respectively, below the liquid level in tanks with a liquid depth of less than 40 inches, and 16 and 18 inches respectively, in tanks with a liquid depth of 40 inches or greater. The distance between the outlet baffle and the outlet shall not exceed six inches. Baffles shall be constructed of a durable material not subject to corrosion, decay or cracking.

(vi) There shall be a minimum of one inch clearance between the underside of the top of the tank and the top of all baffles, partition and/or tees to permit venting of tank gases. Multi-chamber and multi-tank systems shall also be designed to permit the venting of tank gases.

(vii) Tanks shall be placed on at least a three inch bed of sand or pea gravel. This will provide for proper leveling and bearing. Additional instructions provided by the manufacturer shall also be followed.

(viii) There shall be a minimum drop in elevation of two inches between the inverts of the inlet and outlet pipes.

(ix) Garbage grinders. An additional 250 gallons of capacity and seven square feet of surface area is required when a garbage grinder can reasonably be expected at the time of construction or in the future. A gas deflection baffle or other acceptable outlet modification, and a dual compartment tank or two tanks in series must also be provided.

(2) Design Specifications for Multi-compartment septic tanks or tanks in series.

(i) Dual compartments are recommended for all tanks and shall be required on all tanks with an interior length of ten feet or more.

(ii) The first compartment or tank (inlet side) shall account for 60 to 75% of the required total design volume. (iii) The baffle separating the compartments shall extend from the bottom of the tank to at least six inches above the invert of the outlet pipe.

(iv) Compartments shall be connected by a four inch vertical slot at least 18 inches in width, a six inch elbow, or two 4-inch elbows located at a distance below the liquid level equal to one-third the distance between the invert of the outlet and the bottom of the tank. At least one access manhole shall be provided into each compartment.

(v) Tanks in series should be connected by a single pipe with a minimum diameter of four inches.

(vi) The volume and surface area for meeting the requirements of Table 3 shall be based upon the total volume and surface areas of all the tanks and chambers.

(3) Design Specifications for Concrete septic tanks.

(i) Concrete shall have a minimum compressive strength of 2,500 pounds per square inch (psi) at 28 days set; 3,000 psi concrete is recommended as a minimum.

(ii) Wall thickness shall be a minimum of three inches unless the design has been certified by a New York licensed professional engineer as complying with all appropriate requirements for thin-wall construction. All walls, bottom and top shall contain reinforcing to assure support for 300 psi.

(iii) All joints shall be sealed such that the tank is watertight; joints below the liquid level must be tested for water tightness prior to backfilling.

(iv) The walls and floor of cast-in-place tanks shall be poured at the same time (monolithic pour).

(4) Design Specifications for Fiberglass and Polyethylene Septic Tanks. These tanks must meet the following additional requirements:

(i) These tanks shall not be installed in areas where the groundwater level can rise to the level of the bottom of the septic tank.

(ii) Particular care must be taken during installation, bedding, and backfilling of these units so as to prevent damage to tank walls. The manufacturer's installation instructions shall be followed.

(iii) All tanks should be sold by the manufacturer completely assembled. If, because of size, the tank is delivered to the site in sections, all joints shall be sealed with watertight gaskets and shall be tested for water tightness after installation, and prior to backfilling.

(5) Design Specifications for Steel Septic Tanks. Steel septic tanks must have a label indicating corrosion protection complying with Underwriters Laboratories, Inc., Standard UL-70 or equivalent.

(6) Design specifications for Aerobic Septic Units. A homeowner may choose to install an aerobic unit instead of a septic tank under the following conditions:

(i) The unit shall have a label indicating compliance with the standards for a Class I unit as described in the National Sanitation Foundation (NSF) Standard 40 or equivalent.

(ii) The rated capacity of the unit shall be equal to or greater than the design flow as determined from Table 1.

(iii) The absorption system that follows the unit shall be sized in the exact same manner as it would for a septic tank.

(iv) Units which do not include as a standard feature a service contract which provides for, as a minimum, semiannual inspections and annual pumping for three years or more are prohibited.

(v) The surface discharge of aerobic unit effluent is strictly prohibited.

Questions & Answers regarding this article

Questions & answers about septic tank design specifications & regulations

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

SEPTIC AUTHORITIES
  75-A.0 New York State Regulation of Private Septic Systems
  75-A.1 Introduction to Septic Systems, Definitions of Septic System Terms
  75-A.2 Regulation of Sewage Treatment Systems by other agencies
  75-A.3 Sewage flows and design flow estimates
  75-A.4 Soil and site appraisal for Septic Systems
  75-A.5 House or building sewer line specifications
  75-A.6 Septic tank capacity requirements, installation, and placement
  75-A.7 Distribution lines, distribution boxes, gravity flow, pressure distribution, dosing, siphons
  75-A.8 Subsurface treatment of effluent, absorption field requirements, leach field design criteria
  75-A.9 Alternative Septic System Designs
  75-A.10 Other systems
  75-A.11 New product/system design interim approval
SEPTIC REFERENCES CODES
SEPTIC SYSTEM DESIGN MANUAL - Online
SEPTIC SYSTEMS ONLINE BOOK

SEPTIC SYSTEM DESIGN ALTERNATIVES
SEPTIC SYSTEM DESIGN BASICS

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Inspecting Septic Systems: Online Book, Inspection, Test, Diagnosis, Repair, & Maintenance: our Online Septic Book: Septic Testing, Loading & Dye Tests, Septic Tank Pumping, Clearances, details of onsite waste disposal system inspection, testing, repair procedures.

  • Advanced Onsite Wastewater Systems Technologies, Anish R. Jantrania, Mark A. Gross. Anish Jantrania, Ph.D., P.E., M.B.A., is a Consulting Engineer, in Mechanicsville VA, 804-550-0389 (2006), Advanced Onsite Wastewater Systems Technologies. Outstanding technical reference especially on alternative septic system design alternatives. Written for designers and engineers, this book is not at all easy going for homeowners but is a text we recommend for professionals--DF.
  • AEROBIC SEPTIC SYSTEMS
  • Builder's Guide to Wells and Septic Systems, Woodson, R. Dodge: $ 24.95; MCGRAW HILL B; TP; Quoting from Amazon's description: For the homebuilder, one mistake in estimating or installing wells and septic systems can cost thousands of dollars. This comprehensive guide filled with case studies can prevent that. Master plumber R. Dodge Woodson packs this reader-friendly guide with guidance and information, including details on new techniques and materials that can economize and expedite jobs and advice on how to avoid mistakes in both estimating and construction. Chapters cover virtually every aspect of wells and septic systems, including on-site evaluations; site limitations; bidding; soil studies, septic designs, and code-related issues; drilled and dug wells, gravel and pipe, chamber-type, and gravity septic systems; pump stations; common problems with well installation; and remedies for poor septic situations. Woodson also discusses ways to increase profits by avoiding cost overruns.
  • Country Plumbing: Living with a Septic System, Hartigan, Gerry: $ 9.95; ALAN C HOOD & TP; Quoting an Amazon reviewer's comment, with which we agree--DF:This book is informative as far as it goes and might be most useful for someone with an older system. But it was written in the early 1980s. A lot has changed since then. In particular, the book doesn't cover any of the newer systems that are used more and more nowadays in some parts of the country -- sand mounds, aeration systems, lagoons, etc.

Design Manuals for Septic Systems

  • US EPA Onsite Wastewater Treatment Systems Manual [online copy, free] Top Reference: US EPA's Design Manual for Onsite Wastewater Treatment and Disposal, 1980, available from the US EPA, the US GPO Superintendent of Documents (Pueblo CO), and from the National Small Flows Clearinghouse. Original source http://www.epa.gov/ORD/NRMRL/Pubs/625R00008/625R00008.htm Onsite wastewater treatment and disposal systems, Richard J Otis, published by the US EPA. Although it's more than 20 years old, this book remains a useful reference for septic system designers. U.S. Environmental Protection Agency, Office of Water Program Operations; Office of Research and Development, Municipal Environmental Research Laboratory; (1980)
  • Eco John® Innovative Toilet Solutions, Global Inventive Industries, Fountain Valley CA, PDF, product brochure
  • "International Private Sewage Disposal Code," 1995, BOCA-708-799-2300, ICBO-310-699-0541, SBCCI 205-591-1853, available from those code associations.
  • "Manual of Policy, Procedures, and Guidelines for Onsite Sewage Systems," Ontario Reg. 374/81, Part VII of the Environmental Protection Act (Canada), ISBN 0-7743-7303-2, Ministry of the Environment,135 St. Clair Ave. West, Toronto Ontario M4V 1P5 Canada $24. CDN.
  • Manual of Septic Tank Practice, US Public Health Service's 1959.

Onsite Wastewater Disposal Books

  • Onsite Wastewater Disposal, R. J. Perkins; Quoting from Amazon: This practical book, co-published with the National Environmental Health Association, describes the step-by-step procedures needed to avoid common pitfalls in septic system technology. Valuable in matching the septic system to the site-specific conditions, this useful book will help you install a reliable system in both suitable and difficult environments. Septic tank installers, planners, state and local regulators, civil and sanitary engineers, consulting engineers, architects, homeowners, academics, and land developers will find this publication valuable.
  • Onsite Wastewater Treatment Systems, Bennette D. Burks, Mary Margaret Minnis, Hogarth House 1994 - one of the best septic system books around, suffering a bit from small fonts and a weak index. (DF volunteers to serve as indexer if Burks/Minnis re-publish this very useful volume.)

    While it contains some material more technical than needed by homeowners, Burks/Minnis book on onsite wastewater treatment systems a very useful reference for both property owners and septic system designers. We refer to it often. While Minnis says the best place to buy this book is at Amazon (our link at left), you can also see this book at Minnis' website at http://web page .pace.edu/MMinnisbook
  • Septic Tank/Soil-Absorption Systems: How to Operate & Maintain [ copy on file as /septic/Septic_Operation_USDA.pdf ] - , Equipment Tips, U.S. Department of Agriculture, 8271 1302, 7100 Engineering, 2300 Recreation, September 1982, web search 08/28/2010, original source: http://www.fs.fed.us/t-d/pubs/pdfimage/82711302.pdf
  • Soil Percolation Tests soil perc testing guide and instructions
  • Percolation Testing Manual, CNMI Division of Environmental Quality, PO Box 501304, Saipan, MP 96950
  • Planting Over Septic System Component", Daniel Friedman (author/editor, InspectAPedia.com), The Innovator, Winter/Spring 2008, BCOSSA, British Columbia OnSite Sewage Association, 201-3542 Blansard St., Victoria BC V8X 1W3 Canada
  • Save the Septic System - Do Not Flush These Items Down the Toilet, Daniel Friedman, InspectAPedia.com - PDF document, printable
  • SEPTIC STANDARDS
  • SEPTIC MAGAZINES
  • Septic System Owner's Manual, Lloyd Kahn, Blair Allen, Julie Jones, Shelter Publications, 2000 $14.95 U.S. - easy to understand, well illustrated, one of the best practical references around on septic design basics including some advanced systems; a little short on safety and maintenance. Both new and used (low priced copies are available, and we think the authors are working on an updated edition--DF. Quoting from one of several Amazon reviews: The basics of septic systems, from underground systems and failures to what the owner can do to promote and maintain a healthy system, is revealed in an excellent guide essential for any who reside on a septic system. Rural residents receive a primer on not only the basics; but how to conduct period inspections and what to do when things go wrong. History also figures into the fine coverage.
  • Test Pit Preparation for Onsite Sewage Evaluations, State of Oregon Department of Environmental Quality, Portland OR, 800 452-4011. PDF document. We recommend this excellent document that offers detail about soil perc tests, deep hole tests, safety, and septic design. Readers should also see Soil Percolation Tests and for testing an existing septic system, also see Dye Tests
  • Grass is Always Greener Over the Septic Tank, Bombeck, Erma: $ 5.99; FAWCETT; MM; This septic system classic whose title helps avoid intimidating readers new to septic systems, is available new or used at very low prices. It's more entertainment than a serious "how to" book on septic systems design, maintenance, or repair. Not recommended -- DF.
  • US EPA Onsite Wastewater Treatment Systems Manual Top Reference: US EPA's Design Manual for Onsite Wastewater Treatment and Disposal, 1980, available from the US EPA, the US GPO Superintendent of Documents (Pueblo CO), and from the National Small Flows Clearinghouse. Original source http://www.epa.gov/ORD/NRMRL/Pubs/625R00008/625R00008.htm
  • Water Wells and Septic Systems Handbook, R. Dodge Woodson. This book is in the upper price range, but is worth the cost for serious septic installers and designers. Quoting Amazon: Each year, thousands upon thousands of Americans install water wells and septic systems on their properties. But with a maze of codes governing their use along with a host of design requirements that ensure their functionality where can someone turn for comprehensive, one-stop guidance? Enter the Water Wells and Septic Systems Handbook from McGraw-Hill.
    Written in language any property owner can understand yet detailed enough for professionals and technical students this easy-to-use volume delivers the latest techniques and code requirements for designing, building, rehabilitating, and maintaining private water wells and septic systems. Bolstered by a wealth of informative charts, tables, and illustrations, this book delivers:
    * Current construction, maintenance, and repair methods
    * New International Private Sewage Disposal Code
    * Up-to-date standards from the American Water Works Association
  • Wells and Septic Systems, Alth, Max and Charlet, Rev. by S. Blackwell Duncan, $ 18.95; Tab Books 1992. We have found this text very useful for conventional well and septic systems design and maintenance --DF. Quoting an Amazon description:Here's all the information you need to build a well or septic system yourself - and save a lot of time, money, and frustration. S. Blackwell Duncan has thoroughly revised and updated this second edition of Wells and Septic Systems to conform to current codes and requirements. He also has expanded this national bestseller to include new material on well and septic installation, water storage and distribution, water treatment, ecological considerations, and septic systems for problem building sites.
  • The NSFC Products List has an excellent list of design manuals/modules available from their website or by telephone 800-624-8301
  • Submissions welcome. send us a suggested document link or request an exchange of website links
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com