InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile viewMobile View
ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

AIR CLEANER PURIFIER TYPES
AIR FILTER EFFECTIVENESS
AIR FILTERS, FIBERGLASS PARTICLES
AIR FILTERS for HVAC SYSTEMS
AIR FILTERS, OPTIMUM INDOOR
AIR FILTERS, SOURCES FOR
AIR FILTERING STRATEGIES
AIR FILTERING CONTINUOUS FAN OPERATION
AIR HANDLER / BLOWER UNITS
AIR LEAK DETECTION TOOLS

AIR POLLUTANTS, COMMON INDOOR
Air Quality Improvement Strategies
AIR LEAK SEALING PROCEDURE
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
AIRBORNE MOLD SPORE COUNT ACCURACY
ALLERGEN TESTS for buildings
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings

ASBESTOS CLEANUP COMPANIES
ASBESTOS ROOFING / SIDING DUST
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
  ASBESTOS AIR DUCTS
  Asbestos Air Duct Vibration Dampers
  ASBESTOS in CARPETING, PADDING
  ASBESTOS CEILING TILES, Asbestos-Containing
  ASBESTOS DUCTS, HVAC
  ASBESTOS DUCT INSULATION, Asbestos Paper
  ASBESTOS DUCTS, Transite Pipe
  ASBESTOS FIREPROOFING SPRAY-On Coatings
  ASBESTOS FLOOR TILE IDENTIFICATION
  ASBESTOS FLOOR TILE Laboratory Procedures
  ASBESTOS FLOOR TILE PHOTO ID GUIDE
  ASBESTOS FLOORING HAZARD REDUCTION
  ASBESTOS FLOORING REMOVAL GUIDE
  Asbestos Foamed-Over
  ASBESTOS INSULATION
  ASBESTOS PAPER DUCT INSULATION
  ASBESTOS PIPE INSULATION
  ASBESTOS ROOFING, CEMENT & FIBER CEMENT
    Asphalt-asbestos Roofing Materials
    ASBESTOS ROOFING / SIDING DUST
    Cement-asbestos roof shingles
    Corrugated Cement-Asbestos Roofing
    Environmental Issues - Asbestos Roofing/Siding
    Maintenance Tips for Asbestos Cement Shingles
    OSHA Regulations, Asbestos Roofing, Siding
    Power Washing Asbestos Roofing
    Replacements for Asbestos Cement Shingles
    Roof Paint, Asphalt-asbestos sealants
    Warranty & Class Actions, Fiber Cement Shingles
    Wear Signs on Cement Asbestos Shingles
  ASBESTOS SIDING CEMENT & FIBER CEMENT
    Asbestos vs. fiber-cement
    ASBESTOS ROOFING / SIDING DUST
    Maintenance & Repair Asbestos Cement Shingles
    OSHA Regulations, Asbestos Roofing, Siding
    Painting Cement Asbestos Siding
    Remove & Replace Asbestos Cement Shingles
    Re-Sale Issues - Cement Asbestos siding
    Siding over asbestos cement
    Sources of Replacements for Asbestos Cement Shingles
    Tools to Cut Fiber Cement Shingles
    Wear signs on cement asbestos walls
  Asbestos in unusual places
  Asphalt-asbestos Paints & sealants
  Carbon Nanotube Materials
  TRANSITE PIPE AIR DUCTS
  Transite Pipe Chimneys & Flues
  Transite Pipe Water Supply Piping
  VERMICULITE INSULATION
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS FLOORING REMOVAL GUIDE
ASBESTOS List of Asbestos-Containing Products
ASBESTOS MATERIAL REGULATIONS
ASBESTOS MATERIAL REGULATIONS Update
ASBESTOS MATERIAL REGULATIONS, OSHA Roofing/Siding
ASBESTOS Photo Guide to Materials / Products
ASBESTOS REMOVAL, Amateur, Incomplete
Asbestos Removal, Certification
ASBESTOS REMOVAL GUIDE, FLOORING
ASBESTOS REMOVAL, Wetting Guidelines
ASBESTOS RISK ASSESSMENT
  Asbestos risk: in Good Condition
  Asbestos risk: in Poor Condition
Asbestos Under the Microscope
ATTORNEYS and EXPERT WITNESSES
INSULATION IDENTIFICATION GUIDE
ASBESTOS Photo Guide to Materials / Products
ASBESTOS REMOVAL, Wetting Guidelines
Asbestos Under the Microscope
DUCTS - Asbestos
DUCT INSULATION, Asbestos Paper
DUCTS, Asbestos Transite Pipe
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS
INSULATION IDENTIFICATION GUIDE
  ASBESTOS-FREE INSULATION MATERIALS
  ASBESTOS IDENTIFICATION IN buildings
  Asbestos Pipe Insulation
  Balsam Wool Batt Insulation
  BLOWN-IN INSULATION
  BRICK LINED WALLS
  BRICK VENEER WALL INSULATION
  Cellulose loose fill insulation
  Ceramic Insulation
  Concrete insulation, light-weight
  Cotton Insulating Batts
  Fiberglass Insulation
  Foam Board Insulation
  Foam Insulation Types - Visual Id
  Homasote & Other Insulating Board
  Icynene Foam Spray Insulation
  Insects & Foam Insulation
  Mineral Wool - Rock Wool Insulation
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  Mold in Foam Insulation
  Paper Duct Insulation
  Perlite Insulation
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION
INSULATION INSPECTION & IMPROVEMENT

More Information

New and old fiber cement and asbestos cement shingles side by side (C) Daniel FriedmanSources of Replacements for Asbestos-Cement Wall Siding & Fiber Cement Shingle Cutters
InspectAPedia®  -         

  • Buy fiber cement shingles or fiber cement building siding when replacement or repair of damaged asbestos cement shingles is needed
  • Where to buy tools to cut fiber cement shingles or siding
  • When & how to paint asbestos cement shingle siding
  • How to recognize asbestos building siding or wall cladding materials: asbestos cement or "cement-asbestos siding"
  • During what years was asbestos included in building products?
  • Non-asbestos replacement cement siding is available, it's sometimes mistaken for asbestos
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article explains why, where & how to obtain replacement non-asbestos fiber cement shingles to repair or replace asbestos cement shingle siding. We discuss why & how to paint asbestos cement or fiber cement building siding. This document assists building buyers, owners or inspectors who need to identify asbestos materials (or probable-asbestos) in buildings by simple visual inspection. In the website sections listed below, we provide photographs and descriptive text of asbestos insulation and other asbestos-containing products to permit identification of definite, probable, or possible asbestos materials in buildings.

While an expert lab test using polarized light microscopy may be needed to identify the specific type of asbestos fiber, or to identify the presence of asbestos in air or dust samples, many asbestos-containing building products not only are obvious and easy to recognize, but since there were not other look-alike products that were not asbestos, a visual identification of this material can be virtually a certainty in many cases.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Sources of Replacements for Asbestos Cement Wall Shingles

One manufacturer of cement-asbestos shingles was Ruberoid Co., who made 8" x 16" tapered singles with a surface pattern resembling wood and called "Ru-Ber-Oid-Eternit Tapered Timbertex Asbestos-Cement Shingles." 260 singles/525 lbs/square, were available in a wide range of colors.

Contemporary cement asbestos product manufacturers make reinforced fiber-cement wall and roofing shingles and other products which look like, perform similarly to, and need to be installed similarly to the original asbestos-cement shingles - but these new products are free of asbestos. The replacements for asbestos cement wall siding products are reinforced with a variety of fibers including fiberglass. Other replacements for asbestos-cement siding use both different fibers and a different aggregate (perlite) to replace the asbestos. Some of the substitute products have been in use for more than 30 years (2008).

For maintenance or replacement of asbestos-cement wall siding or roof shingles (or wall siding) contact Supradur Manufacturing Corporation, PO Box 908, Rye NY 10580 800-223-1948, or from within New York State, call 914-967-8230. Ask about their Supradur(R) mineral fiber shingles.

For handling and disposal guidance concerning old cement-asbestos wall siding material contact the US EPA, your state Department of Environmental Protection/Conservation, or your local building and health departments.

Sources of Tools for Cutting Fiber Cement Shingles: Roofing Shingles or Wall Siding Shingles

Watch out: However very old, weathered and worn asbestos cement shingles, such as on a roof or sometimes on a wall that has been painted and is peeling, or roofing or wall cement asbestos shingles that are mishandled during demolition (breaking into many small pieces, running hand or power saws to cut the material) risks creating airborne asbestos-contaminated dust which could be a health and environmental hazard.

Bullet Tools 920 Pro Magnum Shear 9-20 electricity free fiber cement shingle cutter


When we installed asbestos cement shingle siding we rented a guillotine chopper that cut the material while producing a minimum of dust.

A modern version of this fiber cement cutter that is hand-lever operated and does not require electricity is the Bullet Tools 920 Pro Magnum Shear I-20 Electricity Free 20 Inch Flooring and Siding Dust Free Cutter (photo at left) - this is a great tool, but a bit steep for a homeowner or do-it-yoursel'er at around $900.

Malco fiber cement shear cutting tool TSFC


A modern fiber cement shingle cutting tool used for the same purpose is the Malco® TSFC Tubo Shear fiber cement cutting tool also used to cut cement backerboard and similar products.

The Malco fiber cement and backerboard shear is powered by a separate cordless or wall-power connected electric drill.

Malco also produces the TSF2A, a heavy-duty pneumatic shear cutting tool for the same purpose.

Similar shear tools are produced by quite a few other manufacturers including the tools listed below. At Reviewers (scroll down past the links) we list sources to purchase these tools.

  • Makita JS8000 Fiber Cement Shear Kit (variable speed)
  • Kett 1/2 Capacity Steel Shear Head #93 20, (this is just the head, needs to be attached)
  • Kett Electric Fiber Cement Cutting Shears - 120 Volt, 5 Amp, Model# KD-29
  • Kett Fiber Cement Shears KD 1495 (drill powered,
  • Snapper Inc SS204 Fiber Cement Siding Shear Hardi Board cutter.

Added demolition and disposal cost of cement-asbestos products

Also in some communities special measures and added costs are involved because of a requirement for air-testing during removal and possibly costs to dispose of the material in an appropriate landfill. (After all, originally this material came from the land.)

Thanks to reader Van Moore for technical editing and requesting clarification.

Painting Cement Asbestos Building Siding

Should I paint my asbestos cement shingles? Do you need to use special paint for cement asbestos siding?

Painting cement asbestos siding or non-asbestos fiber cement siding is mostly a cosmetic decision. We have never seen this material in a worn, friable condition, but should that occur, one might paint the surface also to stop fiber shedding and to preserve the material.

Fiber cement shingles, both new non-asbestos product and the older asbestos-cement product are provided from the manufacturer with a coated surface, usually white. When the asbestos cement siding is soiled or moldy or has an algae coating we prefer to gently clean the surface with a sprayer, perhaps a deck cleaner solution. If you use a power washer be careful to spray "down" (to avoid blowing water into the building walls) and to keep far enough away that you do not damage the siding or "rough it up" which may cause more rapid deterioration or even fiber or asbestos release.

But sometimes the asbestos cement or fiber cement shingles just look soiled and do not clean up enough to satisfy the homeowner. In general, this siding material can be painted using normal house paints. Check with your paint suppliers because some paints may not be recommended for the surface. But once you paint the siding, you've converted a "no maintenance" surface into one that will occasionally need to be re-painted for cosmetic reasons.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

Google
  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
ASBESTOS ROOFING / SIDING DUST
Asbestos Risk Assessment
Asbestos in Good Condition
Asbestos in Poor Condition
ASBESTOS REMOVAL, Amateur, Incomplete
Asbestos Removal, Certification
Asbestos Foamed-Over
Asbestos Air Ducts
Asbestos Air Duct Vibration Dampers
Asbestos Pipe Insulation
ASBESTOS MATERIAL REGULATIONS
ASBESTOS REGULATION Update
ASBESTOS REMOVAL, Wetting Guidelines
Asbestos Roofing Materials
Asbestos Roof Power Washing
ASBESTOS CEMENT & FIBER CEMENT SIDING
  Asbestos vs. fiber-cement
  Re-Sale Issues - Cement Asbestos siding
  Wear signs on cement asbestos walls
  Maintenance & Repair Asbestos Cement Shingles
  Remove & Replace Asbestos Cement Shingles
  Siding over asbestos cement
  Sources of Replacements for Asbestos Cement Shingles
  Painting Cement Asbestos Siding
  OSHA Asbestos Roof/Siding Regulations
Asbestos in unusual places
Carbon Nanotube Materials
CEILING TILES - Asbestos-Containing
Fireproofing containing Asbestos
ASBESTOS FLOOR TILE IDENTIFICATION
Paper Duct Insulation Containing Asbestos
TRANSITE PIPE AIR DUCTS
Transite Pipe Chimneys & Flues
Transite Pipe Water Supply Piping
Urea Formaldehyde Foam Insulation UFFI
VERMICULITE INSULATION
ASBESTOS Photo Guide to Materials / Products
ASBESTOS REMOVAL, Wetting Guidelines
Asbestos Under the Microscope
MOLD in FOAM INSULATION, RESISTANCE
ASBESTOS-FREE INSULATION MATERIALS

INSULATION IDENTIFICATION GUIDE
  ASBESTOS-FREE INSULATION MATERIALS
  ASBESTOS IDENTIFICATION IN buildings
  Asbestos Pipe Insulation
  Balsam Wool Batt Insulation
  BLOWN-IN INSULATION
  BRICK LINED WALLS
  BRICK VENEER WALL INSULATION
  Cellulose loose fill insulation
  Ceramic Insulation
  Concrete insulation, light-weight
  Cotton Insulating Batts
  Fiberglass Insulation
  Foam Board Insulation
  Foam Insulation Types - Visual Id
  Homasote & Other Insulating Board
  Icynene Foam Spray Insulation
  Insects & Foam Insulation
  Mineral Wool - Rock Wool Insulation
  Mold in Fiberglass Insulation
  Mold on Books, Book Conservation
  Mold on Fiberboard Insulating Sheathing
  MOLD PREVENTION AFTER FLOODING
  MOLD RESISTANT CONSTRUCTION
  Mold in Foam Insulation
  Paper Duct Insulation
  Perlite Insulation
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  VERMICULITE INSULATION
  • Asbestos products and their history and use in various building materials such as asphalt and vinyl flooring includes discussion which draws on Asbestos, Its Industrial Applications, D.V. Rosato, engineering consultant, Newton, MA, Reinhold Publishing, 1959 Library of Congress Catalog Card No.: 59-12535 (out of print).
  • "Handling Asbestos-Containing roofing material - an update", Carl Good, NRCA Associate Executive Director, Professional Roofing, February 1992, p. 38-43
  • EPA Guidance for Controlling Asbestos-Containing Materials in buildings, NIAST, National Institute on Abatement Sciences & Technology, [republishing EPA public documents] 1985 ed., Exposure Evaluation Division, Office of Toxic Substances, Office of Pesticides and Toxic Substances, U.S. Environmental Protection Agency, Washington,D.C. 20460
  • Copy on file as - /hazmat/Asbestos_in_Your_Home_US_EPA.pdf - Asbestos in Your Home - U.S. EPA, Exposure Evaluation Division, Office of Toxic Substances, Office of Pesticides and Toxic Substances, U.S. Environmental Protection Agency, Washington,D.C. 20460
  • NRCA Roofing and Waterproofing Manual, 4th Ed., available from the National Roofing Contractors' Association.
  • "Tips for working with fiber-cement roofing products", Thomas L. Smith, AIA, RRC, Professional Roofing, September 1996
  • Bullet Tools 920 Pro Magnum Shear I-20 Electricity Free 20 Inch Flooring and Siding Dust Free Cutter -(sold at Amazon and at other tool distributors) this is a great tool, but $900. http://www.bullettools.com/ Bullet Tools Company, 3390 W. Hayden Ave., Hayden ID 83835 - 800-406-8998 or international: 208-772-0175. sales@bullettools.com
  • Malco® TSFC Tubo Shear fiber cement cutting tool (sold at Amazon and at other tool distributors) and also the Malco TSF2A Shear Cutting Tool, a heavy-duty pneumatic shear cutting tool for the same purpose (available at Amazon.com) Malco Products, http://www.malcoproducts.com/ specializes in producing tools for the HVAC trade. Malco Products, Inc. - PO Box 400, 14080 State Highway 55 NW, Annandale, MN 55302-0400 P: 800-328-3530 | F: 320-274-2269
  • Makita JS8000 Fiber Cement Shear Kit (variable speed) (sold at Amazon and at other tool distributors)
  • Kett 1/2 Capacity Steel Shear Head #93 20 - (sold at Amazon and at other tool distributors)
  • Kett Electric Fiber Cement Cutting Shears - 120 Volt, 5 Amp, Model# KD-29 - (sold at Amazon and at other tool distributors)
  • Kett Fiber Cement Shears KD 1495 (drill powered)- (sold at Amazon and at other tool distributors)
  • Snapper Inc SS204 Fiber Cement Siding Shear Hardi Board cutter.- (sold at tool distributors)
  • Thanks to reader Van Moore for suggesting clarification of our text on how cementious asbestos-containing materials become friable and unsafe 4/15/2010

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.

Asbestos Hazard, Testing, Removal, References & Products

  • Environmental Health & Investigation Bibliography - our own technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • ASBESTOS IDENTIFICATION IN buildings How to find and recognize asbestos in buildings - visual inspection methods, list of common asbestos-containing materials
  • Asbestos Identification and Testing References
    • Asbestos Identification, Walter C.McCrone, McCrone Research Institute, Chicago, IL.1987 ISBN 0-904962-11-3. Dr. McCrone literally "wrote the book" on asbestos identification procedures which formed the basis for current work by asbestos identification laboratories.
    • Stanton, .F., et al., National Bureau of Standards Special Publication 506: 143-151
    • Pott, F., Staub-Reinhalf Luft 38, 486-490 (1978) cited by McCrone
  • Asbestos in Good Condition
  • Asbestos in Good Condition
  • Asbestos in Your Home U.S. EPA, Exposure Evaluation Division, Office of Toxic Substances, Office of Pesticides and Toxic Substances, U.S. Environmental Protection Agency, Washington,D.C. 20460
  • Asbestos HVAC Ducts and Flues field identification photos and guide
  • Asbestos NESHAP Adequately Wet Guidance, EPA340/1-90-019, December 1990, U.S. ENVIRONMENTAL PROTECTION AGENCY, Office of Air Quality Planning and Standards, Stationary Source Compliance Division, Washington, DC 20460,original web source: http://www.epa.gov/region04/air/asbestos/awet.htm
  • Asbestos paper duct wrap
  • Asbestos products and their history and use in various building materials such as asphalt and vinyl flooring includes discussion which draws on Asbestos, Its Industrial Applications, D.V. Rosato, engineering consultant, Newton, MA, Reinhold Publishing, 1959 Library of Congress Catalog Card No.: 59-12535 (out of print, text and images available at InspectAPedia.com).
  • Asbestos Transite Chimneys, Flues, & Pipes in buildings
  • Asbestos under the microscope
  • Asbestos Vibration Dampers & Asbestos in the Air Handler
  • Ceiling tiles: How to recognize ceiling tiles that may contain asbestos
  • Examples of unusual uses of asbestos in buildings
  • Fiberglass: Indoor Air Quality Investigations: Health Concerns About Airborne Fiberglass: Fiberglass in Indoor Air from HVAC ducts, and Building Insulation
  • Enviro-Scare: Electric Power Lines, Electromagnetic Fields, Cancer Risk, & "Enviro-Scare" - The Normal Curve Cycle of Public Fear of Environmental Issues
  • Dust from the World Trade Center collapse following the 9/11/01 attack: the lower floors of this building contained spray-on fire-proofing asbestos materials.
  • Asbestos Information Links: Asbestos Detection, Testing, Recognition, Hazards, Field Photos, and Information Sources, including health-related links such as legal services and information about mesothelioma and other cancers.
  • "Handling Asbestos-Containing roofing material - an update", Carl Good, NRCA Associate Executive Director, Professional Roofing, February 1992, p. 38-43
  • EPA Guidance for Controlling Asbestos-Containing Materials in buildings, NIAST, National Institute on Abatement Sciences & Technology, [republishing EPA public documents] 1985 ed., Exposure Evaluation Division, Office of Toxic Substances, Office of Pesticides and Toxic Substances, U.S. Environmental Protection Agency, Washington,D.C. 20460