MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
ACCEPTABLE MOLD LEVEL
ACCURACY OF VARIOUS MOLD TEST METHODS
  Causes of Variation in Airborne Particle Levels
  Indoor vs. Outdoor Spore Counts
  Extent of Variation of Airborne Particle Counts
  Particle Levels vs Sampler Height
  Particle Levels vs Windows/Doors
  PARTICLE & MOLD LEVELS in DUCTWORK
  Concentration Bursts of Mold Spores
  False Negative Results in Mold Tests
  Mold Culture Plate Test Errors
  Why Use Airborne Mold/Particle Sampling?
  Visual Inspection and History for Mold
  VALIDITY of MOLD TESTING METHODS

ACTION GUIDE - WHAT TO DO ABOUT INDOOR MOLD
ACTIVITY of MOLD in BUILDINGS
AIRBORNE MOLD SPORE COUNT ACCURACY
AIRBORNE PARTICLE ANALYSIS METHODS
MOLD CLEARANCE: FOLLOWUP STEPS
AGE of MOLD - Old is the Mold?
AIRBORNE MOLD SPORE COUNT ACCURACY
AIR LEAK DETECTION TOOLS
AIR LEAK SEALING PROCEDURE

AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
ALLERGEN TESTS for BUILDINGS
ALLERGENS in BUILDINGS, RECOGNIZING
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ENTRY POINTS in BUILDINGS

ASBESTOS CLEANUP COMPANIES
ASBESTOS ROOFING / SIDING DUST
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN BUILDINGS
ASBESTOS ROOFING / SIDING DUST
ATTORNEYS and EXPERT WITNESSES
ATTIC MOLD

BASEMENT MOLD
BASEMENT MOLD WATER IMPACT
BASICS YOU NEED to FIND, TEST, REMOVE MOLD
BASKETBALL MOLD SYNDROME - BBMS
BATHROOM MOLD

BIBLIOGAPHY for ENVIRONMENTAL HEALTH, MOLD, IAQ
BIOLOGICAL POLLUTANTS in the HOME - EPA

BLACK MOLD, HARMLESS COSMETIC
BLACK MOLD, TOXIC & ALLERGENIC

BLEACHING MOLD, Advice about
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING

BIOLOGICAL POLLUTANTS
BIOLOGICAL POLLUTANTS in the HOME - EPA
Bisphenol-A, BPA

BLACK MOLD, HARMLESS COSMETIC
BLACK MOLD, TOXIC & ALLERGENIC

BOOK MOLD, Moldy Book Cleaning
BOOKSTORE - ENVIRONMENTAL
BUYERS GUIDE - home inspections for mold

CARBON MONOXIDE - CO
CARPETS & PADDING ODORS IN BUILDINGS
CARPET DUST IDENTIFICATION
CARPETING & INDOOR AIR QUALITY
CARPET MOLD CONTAMINATION
CARPET TEST GUIDE
CAT DANDER in BUILDINGS
Cell phone Radiation Hazards
CHAIN OF CUSTODY - TEST SAMPLE
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHINESE DRYWALL HAZARDS
CLEARANCE INSPECTIONS - MOLD CLEANUP
CONSTRUCTION DETAILS TO AVOID MOLD
CRAWLSPACE MOLD

DIRT FLOOR MOLD CONTAMINATION
DO IT YOURSELF MOLD CLEANUP
DO-IT-YOURSELF MOLD CLEANUP WARNINGS
DRYWALL MOLD
DUST ANALYSIS for FIBERGLASS
DUST SAMPLING PROCEDURE

EFFLORESCENCE, Salts & White / Brown Deposits
EMF ELECTROMAGNETIC FIELDS & HUMAN EXPOSURE
EMF RF FIELD & FREQUENCY DEFINITIONS
ENERGY SAVINGS in BUILDINGS
FEAR of MOLD - MYCOPHOBIA
Fiberboard Insulation Sheathing Mold
Fiberglass Enviro-Scare
FIBERGLASS HAZARDS
FIBERGLASS INSULATION
FIBERGLASS INSULATION MOLD
FIBERGLASS PARTICLE CONTAMINATION TEST
FIELD INVESTIGATION SERVICE
FIND MOLD, ESSENTIAL STEPS
FIND MOLD in BUILDINGS, HOW TO
FIRE DAMAGE vs MOLD DAMAGE
FLASHLIGHT HELPS FIND MOLD
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN BUILDINGS-mold
FLOOR & SUBFLOOR MOLD, HIDDEN
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS
FORMALDEHYDE HAZARDS
FOUNDATION WATERPROOFING
FRENCH DRAINS
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

FUNGICIDAL SPRAY & SEALANT USE GUIDE

GASES, EXPOSURE, TESTING
  Carbon Dioxide - CO2
  Carbon Monoxide - CO
  METHANE GAS SOURCES
GAS MEASUREMENT TOOLS
Gas Toxicity Levels

HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING SYSTEM ODORS
House Dust Analysis
HOUSEWRAP AIR & VAPOR BARRIERS

HIDDEN MOLD, HOW TO FIND
  PHOTO GUIDE to FIND HIDDEN MOLD
  Hidden Mold Behind Paneling
  Hidden Mold Between Framing & Sheathing
  Hidden Mold in Flooring & Subflooring
  Hidden Mold in Wall Cavities
  Spotting Hard-to-See Mold
  Wall test cuts to spot hidden mold
  LIGHT AIM FINDS MOLD
  Light colored toxic molds
  LIGHT, flashlight to find mold
  Moisture Gradients and Mold
  Other Places to Look for Hidden Mold
  INSULATION MOLD
  SAMPLE POINT CHOICES FOR MOLD TEST
  MOLD TESTING & SAMPLING MISTAKES
HUMIDITY CONTROL & TARGETS INDOORS

IAQ ISSUES, OTHER
INDOOR AIR HAZARDS TABLE
Indoor Air Pollution Book Online CPSC
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INDOOR AIR QUALITY METHODS COMPARED

INSULATION INSPECTION & IMPROVEMENT
INSULATION MOLD
ITCHY FABRICS

LABORATORY SERVICES
LEAD POISONING HAZARDS GUIDE
LEAD CONTAMINATION in WATER, HOW to TEST
LEAD EXPOSURE HAZARDS INDOORS
LEAD HAZARDS & FEAR: Enviro-Scare
LEAD IN DRINKING WATER, HOW to REDUCE
LEAD PIPES in BUILDINGS
LEAD PAINT REMOVAL ALTERNATIVES
LEAD in ROOFING, EFFECTS
LEAD TEST KIT for HOME USE
LEAD WATER PIPING HAZARDS & REMEDIES
LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
Legionella Legionnaires' Disease
Legionella BACTERIA & HVAC Equipment
MEDIA BLASTING for MOLD REMOVAL

MILDEW in BUILDINGS ?
MILDEW ERRORS - MOLD PHOTOS
MILDEW REMOVAL & PREVENTION

MOISTURE CONTROL in BUILDINGS

MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD ACTIVITY in BUILDINGS
MOLD AGE - Old is the Mold?

MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD APPEARANCE - STUFF THAT IS NOT MOLD
MOLD ATLAS & PARTICLES INDEX
MOLD BY MICROSCOPE
MOLD in the PETRI DISH, PHOTOS
Mold on Books, Book Conservation

MOLD CLASSES, HAZARD LEVELS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEANUP - BLEACH
MOLD CLEANUP - HEALTH RISKS
MOLD CLEANUP - LIMITATIONS
MOLD CLEANUP - MISTAKES to AVOID
MOLD CLEANUP - MEDIA BLASTING
MOLD CLEANUP - SAFETY WARNINGS
MOLD CLEANUP - WOOD FLOORING
MOLD CLEANUP - WOOD FRAMING & PLYWOOD
MOLD CLEARANCE INSPECTIONS
MOLD CLINICAL REFERENCE TEXTS
MOLD CONSULTANTS/INSPECTORS
MOLD CONTAMINATION LEVELS
MOLD CULTURE PHOTOS
MOLD CULTURE TEST KIT VALIDITY
MOLD DETECTION & INSPECTION GUIDE
MOLD DOCTORS - ENVIRONMENTAL MEDICINE

MOLD EXPERT, WHEN TO HIRE
MOLD EXPOSURE, FOOD HAZARDS
MOLD EXPOSURE RISK LEVELS
MOLD EXPOSURE STANDARDS

MOLD FAQ's
MOLD FREQUENCY in BUILDINGS
MOLD GROWTH ON SURFACES, PHOTOS
MOLD GROWTH on SURFACES, TABLE OF
MOLD GROWTH in/on BUILDING INSULATION
MOLD INFORMATION CENTER
MOLD INSPECTORS & MOLD TESTERS
MOLD INSPECTION SERVICE
MOLD INVESTIGATION PROCEDURE TIPS
MOLD INVESTIGATION REPORTS

MOLD KILLING GUIDE
MOLD LAB REPORTS
MOLD LEVEL IN AIR, VALIDITY
MOLD LEVEL REPORTS
MOLD LEVELS IN BUILDINGS
MOLD by MICROSCOPE

MOLD ODORS, MUSTY SMELLS
MOLD on or in CARPETS
MOLD ON DIRT FLOORS
MOLD PREVENTION GUIDE

MOLD RELATED ILLNESS GUIDE
MOLD RELATED ILLNESS SYMPTOMS
MOLD SAFETY WARNINGS
MOLD SPRAYS, SEALANTS, PAINTS
MOLD STANDARDS
MOLD STANDARDS - GOVERNMENT
MOLD STANDARDS - WORLD WIDE
MOLD TOXICITY VARIATION

MOLD TEST KITS
MOLD TEST KITS for DIY MOLD TESTS
MOLD TEST METHODS, ACCURACY
MOLD TEST PROCEDURES
MOLD TEST REASONS
MOLD TESTING METHOD VALIDITY
MOLD TESTING SERVICES

MSDS Material Safety Data Sheets
MVOCs & MOLDY MUSTY ODORS
MYCOTOXIN EFFECTS of MOLD EXPOSURE

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST
ODORLESS CHEMICALS / GASES: CHECK FOR?
ODORS, PLUMBING SYSTEM
ODORS, SEPTIC or SEWER
ODORS, SULPHUR SMELL SOURCES
ODORS, URINE REMOVAL
ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS IN WATER
OIL HEAT ODORS
OIL TANK LEAK ODORS
OZONE for MOLD OR ODORS

PAINTS & COATINGS ODORS IN BUILDINGS
Particulates & Allergens Indoors
Pesticide Exposure Hazards
PET ALLERGEN REMEDIES
PLASTIC CONTAINERS, TANKS, TYPES
PLASTIC HEATER VENT
PLASTIC ODORS-SCREENS, SIDING
PLUMBING SYSTEM ODORS

RADON HAZARD TESTS & MITIGATION
RENTERS & TENANTS GUIDE TO MOLD
ROBIGUS & Wheat Rust Fungus
ROT, TIMBER FRAME
SEPTIC BACKUP PREVENTION
SEPTIC BACKUP REPAIR
SEPTIC METHANE GAS
SEPTIC SYSTEM ODORS
SMELL PATCH TEST to Track Down Odors
SEWER GAS ODORS
SEWER GAS ODORS in COLD WEATHER
SEWAGE BACKUP, WHAT TO DO
SEWAGE BACKUP TEST & CLEANUP
SEWAGE BACKUP PREVENTION
SOUND CONTROL in BUILDINGS
SIDING VINYL
  VINYL SIDING INSPECTION & REPAIR
  VINYL SIDING INSTALLATION
  VINYL Siding or PLASTIC Window ODORS in Buildings
  VINYL CHLORIDE HEALTH INFO
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on BUILDINGS - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE

TECHNICAL & LAB PROCEDURES
THERMAL TRACKING Indicates Heat Loss
TRAPPED MOLD BETWEEN WOOD SURFACES

VENTILATION in BUILDINGS
VINYL Siding or PLASTIC Window ODORS in Buildings
VINYL CHLORIDE HEALTH INFO

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in BUILDINGS
WATER ODORS, CAUSE CURE
World Trade Center Collapse Dust Photos

More Information

Photograph: Mold under carpeting on tack strips indicate history of water entry, suspect moldy carpet - Daniel Friedman Mold Sampling & Mold Testing Mistakes to Avoid
InspectAPedia®  -         

  • Sampling mistakes to avoid when testing mold
  • Choosing the wrong mold to sample, missing the important mold
  • Testing stuff that is not mold
  • Testing just the "black mold"
  • Testing in the wrong building areas
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This document describes how to avoid common mistakes people make when trying to find mold and test for mold in buildings, such as testing only the "black mold" on surfaces or relying only on air tests to screen buildings for problem mold.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

SAMPLING MISTAKES - Common Mold Surface Sampling and Other Mold Testing Errors

These mistakes amount to collecting mold test samples in the wrong place, or failing to collect mold test samples in other important places.

  • Looking just for "black mold": Sampling the "scary toxic black mold" on drywall low on the wall while failing to observe the light-colored but more airborne and thus harmful molds such as Aspergillus sp. or Penicillium sp. growing higher and less visibly on the surface. See What mold looks like in a home
  • Using bad lighting: Sampling the "easy to see" mold and missing the "hard to see" mold without first looking carefully with a flashlight. See Using proper lighting to see important mold contamination in buildings
  • Bad choice of test surface: Sampling inorganic surfaces like concrete when nearby organic surfaces like drywall paper or wood paneling are present.
  • Testing Harmless Particles: Sampling things that are obviously not mold and not harmful particles. See Stuff that is Not Mold

Other Common Mold Inspection Mistakes to be Avoided

  • Wrong mold test methods: Relying on screening "mold tests" such as "air tests", mold swabs, or mold cultures, to alone indicate the presence or absence of a mold problem in a building. None of these is reliable when used in place of or without a careful and expert visual inspection and each of which has severe methodological errors and variability in results.

  • Inspecting Easy Areas: Looking only in the easy to inspect areas - such as the living space or attic, and ignoring the crawl space.

  • Overemphasis of Attics Overemphasizing attic mold - where conditions such as condensation often produce less-problematic Cladosporium sp. molds which do not as easily move down into the living area. But do not ignore attics completely and especially do not ignore attic knee wall areas outside bedrooms such as in a cape cod style home.

  • Under-Inspecting Crawl Spaces: Failing to inspect crawl spaces - where conditions are often conducive to problem mold growth, especially when people are concerned about or may have found problem mold in other building areas

  • Ignoring Wall & Ceiling Cavities: Ignoring building cavities - which can, depending on wall or ceiling penetrations and the nature of air movement in a particular building, contain significant reservoirs of problem mold. Some experts opine that mold in cavities never affects building occupants. Our own field investigation has traced high levels of indoor airborne Aspergillus sp. to non-visible reservoirs in fiberglass insulation, so I would not ignore this possibility.

  • Omitting Insulation Ignoring non-visible but significant mold contamination in building insulation. Tape sampling is not useful for porous materials like insulation. We have devised special methods for screening such substances.

There are lots of other errors and inaccuracies that can confound "testing" buildings for mold, such as relying on air sampling or cultures alone, i.e. "testing" rather than performing a thorough visual inspection (by an expert who knows where to look), and obtaining a building leak history.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

More Reading:
Fiberglass in Indoor Air, HVAC ducts, and Building Insulation
How to Test For Mold Sampling techniques (air, surface, culture, etc) and errors
USING LIGHT TO FIND MOLD - Using proper lighting to see important mold contamination in building
Stuff that is Not Mold
Toxic Mold and Toxic Gas Testing Methods Compared

About the Author

Daniel FriedmanInspectAPedia.com/sickhouse.htm

Daniel Friedman is a mold/indoor air quality investigator and home inspector as well as a professional writer in Poughkeepsie, New York. He is a member of the American Industrial Hygiene Association and the American Society of Home Inspectors. He presently chairs ASHI's national Standards of Practice Committee and has led ASHI's Education and Technical Committees as well as serving on ASHI's Exam, and Ethics/Professional Practices Committees. His poetry has appeared in Emphasis, a national publication of MENSA, and his non-fiction articles and essays have appeared in The Journal of Light Construction, the Old House Journal, The ASHI Technical Journal, Progressive Builder and New Shelter. His news reporting and photography have appeared in the Journal of Light Construction, and in various newspapers including the New York Times, Richmond Times Dispatch, Richmond News Leader, and the Poughkeepsie Journal.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Environmental Health & Investigation Bibliography - our technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Adkins and Adkins Dictionary of Roman Religion discusses Robigus, the Roman god of crop protection and the legendary progenitor of wheat rust fungus.
  • Kansas State University, department of plant pathology, extension plant pathology web page on wheat rust fungus: see http://www.oznet.ksu.edu/path-ext/factSheets/Wheat/Wheat%20Leaf%20Rust.asp
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • US EPA - Mold Remediation in Schools and Commercial Building US EPA
  • US EPA - Una Breva Guia a Moho - Hongo - en Espanol

Mold Contamination Testing, Cleanup, Prevention: references & products

  • GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminantsThe Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
  • Aerobiology, Building Science, Microscopy, & Laboratory References, an extensive technical bibliography
  • Allergens: what they look like in buildings
  • Associations: Sick House, Sick Building, SBS - Air Quality, Government, Private Associations and Information Resources
  • Atlas of Clinical Fungi, 2nd Ed., GS deHoog, J Guarro, J Gene, & MJ Figueras, Centraalbureau voor Schimmelcultures, Universitat Rovira I Virgili, 2000, ISBN 90-70351-43-9 (you can buy this book at Amazon)
  • Atlas of Mold Related Illness: Index of Symptoms and health, physical, neurological, psychological, and other complaint which people suspect may be mold or building-related.
  • Atlas of Indoor Mold, Online Clinical Mold Atlas, Toxins, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • Black Mold that is Harmless Photos of recognizable, usually harmless black mold on wood, bluestain, ceratocystis, ophistoma
  • Building Floods: quick steps after a building flood or plumbing leak can prevent costly mold contamination
  • Classes of Mold: what types of cosmetic, allergenic, or toxic mold are a problem? Can mold be cleaned-up successfully?
  • Clinical Mold References - Detailed bibliography of mold reference texts
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • "Disease Prevention Program for Certain Vegetable Crops," David B. Langston, Jr., Extension Plant Pathologist - Vegetables, University of Georgia (PDF document) original source: www.reeis.usda.gov/web/crisprojectpages/209797.html
  • "Disease Prevention in Home Vegetable Gardens," Patricia Donald, Department of Plant Microbiology and Pathology, Lewis Jett
    Department of Horticulture, University of Missouri Extension - extension.missouri.edu/publications/DisplayPub.aspx?P=G6202
  • "Management of Powdery Mildew, Leveillula taurica, in Greenhouse Peppers," Ministry of Agriculture and Lands, British Columbia - Original source: www.agf.gov.bc.ca/cropprot/peppermildew.htm
  • Environmental Health & Investigation Bibliography - our own technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Fiberglass: Mold in Fiberglass Insulation© 2005 comments about a field study in process, & more about health hazards from fiberglass insulation - DJF
  • Fifth Kingdom, Bryce Kendrick, ISBN13: 9781585100224, is available from the InspectAPedia online bookstore - we recommend the CD-ROM version of this book. This 3rd/edition is a compact but comprehensive encyclopedia of all things mycological. Every aspect of the fungi, from aflatoxin to zppspores, with an accessible blend of verve and wit. The 24 chapters are filled with up-to-date information of classification, yeast, lichens, spore dispersal, allergies, ecology, genetics, plant pathology, predatory fungi, biological control, mutualistic symbioses with animals and plants, fungi as food, food spoilage and mycotoxins.
  • Fungi, Identifying Filamentous, A Clinical Laboratory Handbook, Guy St-Germain, Richard Summerbell, Star Publishing, 1996, ISBN 0-89863-177-7 (English) (buy at Amazon)
  • Looking for Mold Procedure: what mold is often found where in buildings - simple technical presentation
  • Meruliporia: the house eating fungus or "poria"
  • Mold Action Guide: Step-by-Step Instructions, What to do about mold, mildew, and other indoor allergens
  • MOLD APPEARANCE - WHAT MOLD LOOKS LIKE Photos of what mold looks like in buildings
  • MOLD APPEARANCE - STUFF THAT IS NOT MOLD Photos of NOT-mold material that is sometimes mistaken for mold
  • MOLD ATLAS & PARTICLES INDEX, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • MOLD BY MICROSCOPE Mold under the microscope - photo identification of the most common indoor molds found in buildings
  • Mold FAQs Answers to Most Questions about Indoor Mold, Mold Related Illness, Mold Cleanup, Mold Prevention
  • US EPA: Mold Remediation in Schools and Commercial Building US EPA
  • Mold spores in the Home - a Photo ID Library for detection and identification of mold allergens
  • Mold Test Kits - How to Collect and Send Your Own Mold Sample to our mold testing lab or to any mold lab you wish
  • Most Common Indoor Molds Found in Buildings, A Table of
  • Mycology, Fundamentals of Diagnostic, Fran Fisher, Norma B. Cook, W.B. Saunders Co. 1998, ISBN 0-7216-5006-6 (buy this book at Amazon)
  • Ozone Warnings - Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Rot concerns in buildings-some building mold such as Meruliporia incrassata "Poria" risks serious rot and hidden structural damage
  • US EPA: Una Breva Guia a Moho - Hongo - en Espanol

OTHER IAQ ISSUES: How To Find and Address Other Indoor Air or Indoor Environment Contaminants Besides Mold

Mold or allergens may not be the only or even the main indoor environmental contaminant. Don't let media attention to mold cause so much enviro-scare fear that other, possibly more urgent hazards go un-addressed.

  • Fiberglass building insulation and HVAC duct work insulation hazards
  • Sewage and Septic backup contamination in buildings: inspection, testing, remediation, & references to expert sources
  • Other environmental risks: Asbestos, carbon monoxide, electromagnetic fields, environmental illness, fiberglass, MCS - multiple chemical sensitivity, toxic gases, etc
  • Indoor Gas Sampling Plan for Residential Buildings lists a number of toxic indoor gases which we test for, depending on the building complaint and building conditions
  • Ozone Warnings - Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Pet control - if you can't say goodbye to your bird, cat, dog, guinea pig, hamster, tropical fish, then limit the areas they occupy and limit the airflow from that area to sleeping or other areas of the building, use allergenic bedding, eliminate wall-to-wall carpeting, improve housecleaning including use of a HEPA-rated vacuum cleaner. For more details see our article Dog, Cat, and Other Animal Dander - Information for Asthmatics and Indoor Air Quality
  • Rodents, Mice, Squirrel Control - I find high levels of mouse and rodent dander, fecal dust, and urine-contaminated dust in some buildings, and high levels of these materials in building insulation in those locations. If you have a mouse problem, particularly if mice and their waste (fecals or urine) are contaminating the building HVAC or building insulation, may need both steps to clean up or remove infected materials and steps to stop an ongoing rodent problem. If squirrels are a problem, the cleanup needs to include closing off entry openings into the building. Get some help from a licensed pest control expert.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com