InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


InspectAPedia.com logoMobile View
ENERGY SAVINGS in BUILDINGS
ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY

MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
ACCEPTABLE MOLD LEVEL

ACTION GUIDE - WHAT TO DO ABOUT INDOOR MOLD
ACTIVITY of MOLD in BUILDINGS
AIRBORNE MOLD SPORE COUNT ACCURACY
AIRBORNE PARTICLE ANALYSIS METHODS
MOLD CLEARANCE: FOLLOWUP STEPS
AGE of MOLD - Old is the Mold?
AIRBORNE MOLD SPORE COUNT ACCURACY
AIR LEAK DETECTION TOOLS
AIR LEAK SEALING PROCEDURE

AIR POLLUTANTS, COMMON INDOOR
AIR SEALING STRATEGIES
AIR TEST FOR MOLD: ACCURACY
AIR TEST SAMPLING CASSETTE STUDY
ALLERGEN TESTS for BUILDINGS
ALLERGENS in BUILDINGS, RECOGNIZING
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
ANIMAL ENTRY POINTS in BUILDINGS

ASBESTOS CLEANUP COMPANIES
ASBESTOS ROOFING / SIDING DUST
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN BUILDINGS
ASBESTOS ROOFING / SIDING DUST
ATTORNEYS and EXPERT WITNESSES
ATTIC MOLD

BASEMENT MOLD
BASEMENT MOLD WATER IMPACT
BASICS YOU NEED to FIND, TEST, REMOVE MOLD
BASKETBALL MOLD SYNDROME - BBMS
BATHROOM MOLD

BIBLIOGAPHY for ENVIRONMENTAL HEALTH, MOLD, IAQ
BIOLOGICAL POLLUTANTS in the HOME - EPA

BLACK MOLD, HARMLESS COSMETIC
BLACK MOLD, TOXIC & ALLERGENIC

BLEACHING MOLD, Advice about
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING

BIOLOGICAL POLLUTANTS
BIOLOGICAL POLLUTANTS in the HOME - EPA
Bisphenol-A, BPA

BLACK MOLD, HARMLESS COSMETIC
BLACK MOLD, TOXIC & ALLERGENIC

BOOK MOLD, Moldy Book Cleaning
BOOKSTORE - ENVIRONMENTAL
BUYERS GUIDE - home inspections for mold
CARBON MONOXIDE - CO
CARPETS & PADDING ODORS IN BUILDINGS
CARPET DUST IDENTIFICATION
CARPETING & INDOOR AIR QUALITY
CARPET MOLD CONTAMINATION
CARPET TEST GUIDE
CAT DANDER in BUILDINGS
Cell phone Radiation Hazards
CHAIN OF CUSTODY - TEST SAMPLE
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHINESE DRYWALL HAZARDS
CLEARANCE INSPECTIONS - MOLD CLEANUP
CONSTRUCTION DETAILS TO AVOID MOLD
CRAWLSPACE MOLD
DIRT FLOOR MOLD CONTAMINATION
DO IT YOURSELF MOLD CLEANUP
DO-IT-YOURSELF MOLD CLEANUP WARNINGS
DRYWALL MOLD
DUST ANALYSIS for FIBERGLASS
DUST SAMPLING PROCEDURE

EFFLORESCENCE, Salts & White / Brown Deposits
EMF ELECTROMAGNETIC FIELDS & HUMAN EXPOSURE
EMF RF FIELD & FREQUENCY DEFINITIONS
ENERGY SAVINGS in BUILDINGS
FEAR of MOLD - MYCOPHOBIA
Fiberboard Insulation Sheathing Mold
Fiberglass Enviro-Scare
FIBERGLASS HAZARDS
FIBERGLASS INSULATION
FIBERGLASS INSULATION MOLD
FIBERGLASS PARTICLE CONTAMINATION TEST
FIELD INVESTIGATION SERVICE
FIND MOLD, ESSENTIAL STEPS
FIND MOLD in BUILDINGS, HOW TO
FIRE DAMAGE vs MOLD DAMAGE
FLASHLIGHT HELPS FIND MOLD
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN BUILDINGS-mold
FLOOR & SUBFLOOR MOLD, HIDDEN
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS
FORMALDEHYDE HAZARDS
FOUNDATION WATERPROOFING
FRENCH DRAINS
FREEZE-PROOF A BUILDING
FROST HEAVES, FOUNDATION, SLAB

FUNGICIDAL SPRAY & SEALANT USE GUIDE

GASES, EXPOSURE, TESTING
  Carbon Dioxide - CO2
  Carbon Monoxide - CO
  METHANE GAS SOURCES
GAS MEASUREMENT TOOLS
Gas Toxicity Levels
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING SYSTEM ODORS
House Dust Analysis
HOUSEWRAP AIR & VAPOR BARRIERS

HIDDEN MOLD, HOW TO FIND
HUMIDITY CONTROL & TARGETS INDOORS

IAQ ISSUES, OTHER
INDOOR AIR HAZARDS TABLE
Indoor Air Pollution Book Online CPSC
INDOOR AIR QUALITY & HOUSE TIGHTNESS
INDOOR AIR QUALITY IMPROVEMENT GUIDE
INDOOR AIR QUALITY METHODS COMPARED

INSULATION INSPECTION & IMPROVEMENT
INSULATION MOLD
ITCHY FABRICS

LABORATORY SERVICES
LEAD POISONING HAZARDS GUIDE
LEAD CONTAMINATION in WATER, HOW to TEST
LEAD EXPOSURE HAZARDS INDOORS
LEAD HAZARDS & FEAR: Enviro-Scare
LEAD IN DRINKING WATER, HOW to REDUCE
LEAD PIPES in BUILDINGS
LEAD PAINT REMOVAL ALTERNATIVES
LEAD in ROOFING, EFFECTS
LEAD TEST KIT for HOME USE
LEAD WATER PIPING HAZARDS & REMEDIES
LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
Legionella Legionnaires' Disease
Legionella BACTERIA & HVAC Equipment
MEDIA BLASTING for MOLD REMOVAL

MILDEW in BUILDINGS ?
MILDEW ERRORS - MOLD PHOTOS
MILDEW REMOVAL & PREVENTION

MOISTURE CONTROL in BUILDINGS

MOLD: A COMPLETE GUIDE to TEST CLEAN PREVENT
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD ACTIVITY in BUILDINGS
MOLD AGE - Old is the Mold?

MOLD APPEARANCE - WHAT MOLD LOOKS LIKE
MOLD APPEARANCE - STUFF THAT IS NOT MOLD
MOLD ATLAS & PARTICLES INDEX
MOLD BY MICROSCOPE
MOLD in the PETRI DISH, PHOTOS
Mold on Books, Book Conservation

MOLD CLASSES, HAZARD LEVELS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEANUP - BLEACH
MOLD CLEANUP - HEALTH RISKS
MOLD CLEANUP - LIMITATIONS
MOLD CLEANUP - MISTAKES to AVOID
MOLD CLEANUP - MEDIA BLASTING
MOLD CLEANUP - SAFETY WARNINGS
MOLD CLEANUP - WOOD FLOORING
MOLD CLEANUP - WOOD FRAMING & PLYWOOD
MOLD CLEARANCE INSPECTIONS
MOLD CLINICAL REFERENCE TEXTS
MOLD CONSULTANTS/INSPECTORS
MOLD CONTAMINATION LEVELS
MOLD CULTURE PHOTOS
MOLD CULTURE TEST KIT VALIDITY
MOLD DETECTION & INSPECTION GUIDE
MOLD DOCTORS - ENVIRONMENTAL MEDICINE

MOLD EXPERT, WHEN TO HIRE
MOLD EXPOSURE, FOOD HAZARDS
MOLD EXPOSURE RISK LEVELS
MOLD EXPOSURE STANDARDS

MOLD FAQ's
MOLD FREQUENCY in BUILDINGS
MOLD GROWTH ON SURFACES, PHOTOS
MOLD GROWTH on SURFACES, TABLE OF
MOLD GROWTH in/on BUILDING INSULATION

MOLD INFORMATION CENTER
MOLD INSPECTORS & MOLD TESTERS
MOLD INSPECTION SERVICE
MOLD INVESTIGATION PROCEDURE TIPS
MOLD INVESTIGATION REPORTS

MOLD KILLING GUIDE
MOLD LAB REPORTS
  Purpose of Mold Lab Reports
  Example Mold Report
  Significance of Findings
  What Should Be Done
  Significant Particle Definitions
  Sampling vs human exposure
  Mold exposure standards
  Report Terms & Definitions
  Lab Report Usefulness
  Mold Lab Qualifications
MOLD LEVEL IN AIR, VALIDITY
MOLD LEVEL REPORTS
MOLD LEVELS IN BUILDINGS
MOLD by MICROSCOPE

MOLD ODORS, MUSTY SMELLS
MOLD on or in CARPETS
MOLD ON DIRT FLOORS
MOLD PREVENTION GUIDE

MOLD RELATED ILLNESS GUIDE
MOLD RELATED ILLNESS SYMPTOMS
MOLD SAFETY WARNINGS
MOLD SPRAYS, SEALANTS, PAINTS
MOLD STANDARDS
MOLD STANDARDS - GOVERNMENT
MOLD STANDARDS - WORLD WIDE
MOLD TOXICITY VARIATION

MOLD TEST KITS
MOLD TEST KITS for DIY MOLD TESTS
MOLD TEST METHODS, ACCURACY
MOLD TEST PROCEDURES
MOLD TEST REASONS
MOLD TESTING METHOD VALIDITY
MOLD TESTING SERVICES

MSDS Material Safety Data Sheets
MVOCs & MOLDY MUSTY ODORS
MYCOTOXIN EFFECTS of MOLD EXPOSURE

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST
ODORLESS CHEMICALS / GASES: CHECK FOR?
ODORS, PLUMBING SYSTEM
ODORS, SEPTIC or SEWER
ODORS, SULPHUR SMELL SOURCES
ODORS, URINE REMOVAL
ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS IN WATER
OIL HEAT ODORS
OIL TANK LEAK ODORS
OZONE for MOLD OR ODORS
PAINTS & COATINGS ODORS IN BUILDINGS
Particulates & Allergens Indoors
Pesticide Exposure Hazards
PET ALLERGEN REMEDIES
PLASTIC CONTAINERS, TANKS, TYPES
PLASTIC HEATER VENT
PLASTIC ODORS-SCREENS, SIDING
PLUMBING SYSTEM ODORS
RADON HAZARD TESTS & MITIGATION
RENTERS & TENANTS GUIDE TO MOLD
ROBIGUS & Wheat Rust Fungus
ROT, TIMBER FRAME
SIDING, ASBESTOS CEMENT SHINGLES
SIDING VINYL
  VINYL SIDING INSPECTION & REPAIR
  VINYL SIDING INSTALLATION
  VINYL Siding or PLASTIC Window ODORS in Buildings
  VINYL CHLORIDE HEALTH INFO
SLIDE PREPARATION, MICROSCOPE
SEPTIC METHANE GAS
SEPTIC SYSTEM ODORS
SMELL PATCH TEST to Track Down Odors
SEWER GAS ODORS
SEWER GAS ODORS in COLD WEATHER
SEWAGE BACKUP, WHAT TO DO
SEWAGE BACKUP TEST & CLEANUP
SEWAGE BACKUP PREVENTION
SOUND CONTROL in BUILDINGS
SIDING VINYL
  VINYL SIDING INSPECTION & REPAIR
  VINYL SIDING INSTALLATION
  VINYL Siding or PLASTIC Window ODORS in Buildings
  VINYL CHLORIDE HEALTH INFO
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on BUILDINGS - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAINS on INDOOR SURFACES: PHOTO GUIDE
TECHNICAL & LAB PROCEDURES
THERMAL TRACKING Indicates Heat Loss
TRAPPED MOLD BETWEEN WOOD SURFACES
VENTILATION in BUILDINGS
VINYL Siding or PLASTIC Window ODORS in Buildings
VINYL CHLORIDE HEALTH INFO

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in BUILDINGS
WATER ODORS, CAUSE CURE
World Trade Center Collapse Dust Photos

More Information



InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
AIR CONDITIONING & HEAT PUMPS
BOOKSTORE
ELECTRICAL
ENERGY SAVINGS
ENVIRONMENT
EXTERIORS
HEATING
HOME INSPECTION
INDOOR AIR QUALITY
INSULATION
INTERIORS
MOLD INSPECT/TEST/CLEANUP
NOISE
ODORS
PLUMBING
ROOFING
SEPTIC SYSTEMS
SOLAR ENERGY
STRUCTURE
VENTILATION
WATER SUPPLY

ACCURACY & PRIVACY POLICIES
EXPERT DIRECTORY
CONTACT



SKETCH of a typical aerobic treatment unit tank, aerator, chamber

Mold Test Lab Reports: What A Valid, Useful Mold Report Should Include
InspectAPedia®  -         

  • Mold test laboratory report interpretation
  • Mold test lab report contenta
  • How to read a mold test laboratory report
  • What information should a mold test lab report include?
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This document provides a sample mold test lab report. A mold test lab report can produce a lot of information. In fact it could sound overwhelming. Is there a mold or IAWQ problem? What is the evidence? Where is the problem source? What containment and cleaning are needed?

What building repairs are needed to prevent future problems? How will we assure that the field investigation work is properly done? How will we assure that the mold test lab work was actually done by an expert? Our reports also include professional photo documentation of our microscopic findings in the laboratory.

For a discussion of valid and not very valid site inspection or site investigation reports for mold see Mold Investigation Reports. Also see Mold Test Kit: Six Easy Steps to Get and Mail a Mold Test Kit to our Lab for 24-Hour Analysis and Report.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Purpose of Mold Lab Reports

A "bare" mold-lab report provided by an investigator who performed a "screening inspection" for mold, and who has not also performed a thorough visual inspection of the building is likely to leave the client with no idea about how to proceed, where the problem is, if any, and what to do about it. If you suspect that there is an indoor air problem in the building involving mold or allergens, you need to know the following:

  1. Is there a mold, allergen, or similar environmental problem in the building?
  2. If there is a problem, where is it and how big is it?
  3. What does the lab work indicate about the level of risk to occupants or workers? Are we looking at a "cosmetic-only" concern?
  4. What is the extent of demolition or cleaning needed, and based on the lab results, what is the level of containment and care needed?
  5. What needs to be changed or repaired on the building so that problems don't recur?
  6. And after the cleanup has been completed, was it proper and complete?

In other words, in exchange for being paid a professional fee to investigate a building, the investigator should provide accurate and useful diagnostic and prescriptive information to his or her client.

Example© Mold Test Sample Contents Determination Laboratory Report

The Mold Test Laboratory Report outlined below is typically 6-15 pages in length depending on the number of samples submitted and the variation in content of each sample. The report contains complete detail of laboratory lab findings, a conclusion regarding the extent to which the samples detected or failed to detect presence or absence of an environmental problem, and if a problem was detected, the report includes details about the allergenicity, toxicity, or pathogenicity of the particles found. - © Copyright 2010 Daniel Friedman

Our mold test sample lab report is shown on this web page, just below. Separately, and offered as an on-site building diagnosis service, our diagnostic on-site building environmental hazard or mold inspection report includes our site findings, lab test results, advice for corrective measures, and other detailed advice.

That extensive report described at Mold Investigation and Mold Test Lab Reports. We also provide non-diagnostic non-invasive mold screening inspections and tests for real estate transactions and post-mold remediation (cleanup) project onsite inspection and clearance test reports. Other professional services include odor source detection, gas testing, and diagnostic inspections of overall building condition for building owners or buyers.

Fungal Spore/Allergen Lab Determination Report

Laboratory: Director Daniel Friedman
Laboratory: American Home Service Company
American Industrial Hygiene Association AHIA #149982- American Society of Home Inspectors, Certified Member #0057
Pan American Aerobiology Association - International Aerobiology Association - American Phytopathological Association
Certified Environmental Inspector CEI - Certified Testing Specialist CTS - Certified Environmental Specialist CTS - EAA
Mycological Society of America - NPMA #110947 - ICBO #22178-0 - BOCA-Certified
Certified Massachusetts Title V System Inspector, Massachusetts Department of Environmental Protection

Report Date:

4/15/2006 -- ©

Client:

Paul R. Namewitheld
Building Inspection Services, Inc.
321 Upper Road Drive
Kona Howlie, Maui HI 96790-8054
808-888-0000 cleintemailreportcopy@hawaii.rr.com
Project ID: 060415XXM1DJF
Submitted by: Paul R. Namewitheld
Sampling method: Adhesive Tape
Sampling location: 99 Babmooshoot Road, Kona Howlie, Maui Hawaii - building is located " in a gully surrounded by lush vegetation" with "recent weather conditions over the past 6 weeks have been - an above average amount of rainfall - island wide.

Description: Kitchen area wood plank wall adjacent to propane range. Rural cottage/shack in wet area, RH 58% 78 degF, post and pier foundation, interior open to outdoor conditions (screens only), building in gully surrounded by vegetation. Visible mold-suspect material on 10 sq.ft. in living room on North wall. Building was empty of furnishings at time of inspection. Wall cavities inspected at four test openings, no visible mold, not sampled.

Complaints cited: Tenant experienced a "respiratory episode" and was taken to hospital. Tenant told by a third party that she had Stachybotrys in her home. Tenant says cannot enter the building without becoming sick. Tenant's father is an attorney, threats of litigation may pertain.

Date Sampled: 4/5/06 4:00 PM
Date received by lab: 4/15/06
Date determination completed: 4/15/06
Sample Examination: at 720x-dry by Daniel Friedman, sample prepared in Acid Fuchsin/Lacto phenol cotton blue/KOH/Lactic Acid/or Triacetin with phenol

Sample #Determination
. (numbers, if present, indicate microphotographs of actual sample)
(Fungal spore names are italicized - Genera species)
-001Significant/dominant spores/particles: Aspergillus sp. conidiophores and fungal spores consistent with active fungal growth; A. versicolor present in the sample est. 25% of total mold.
"Significant/dominant, Present, and Incidental" particle levels are defined at the end of the report. Other spores/particles: - not reported unless specific details (such as unexpected spore chains or sample recurrence) appear to warrant.

[Signature] Daniel Friedman, AIHA#149982, ASHI#00577

Determination of genus/species and description completed by: Daniel Friedman, aerobiologist, PAAA/IAAA/AIHA member . These samples were examined in our laboratory using appropriate chemical/stain preparations and a light microscope at magnifications up to 1920X. Genera/species identifications were made based on experience, education, reference texts, and comparison with known samples. Credentials & experience are at InspectAPedia.com/danbio.htm

Significance of Findings: Information about the mold test sample contents

Aspergillus sp."-especially A. fumigatus, is one of the few genera of opportunistic pathogens consistently associated with disease. Aspergillosis is the general term for the infection caused by any species of Aspergillus. Four leading types of Aspergillosis are colonization, allergy, disseminated infection, and toxicity.

Pulmonary colonization and allergic reactions are induced by inhalation of large numbers of conidia."-Fundamentals of Diagnostic Mycology, Fisher & Cook. Reported to be allergenic.

Members of this genus are reported to cause ear infections. Many species produce mycotoxins which may be associated with disease in humans and other animals. Toxin production is dependent on the species or a strain within a species and on the food source for the fungus. Some of these toxins have been found to be carcinogenic in animal species.

Several toxins are considered potential human carcinogens. Common cause of extrinsic asthma (immediate-type hypersensitivity: type I). Acute symptoms include edema and bronchiospasms, chronic cases may develop pulmonary emphysema. - U. Minn.

Aspergillus versicolor: Conidia dimensions 2-3.5 microns. It is commonly found in soil, hay. cotton and dairy products, It can produce a mycotoxin sterigmatocystin and cyclopiaxonic acid. These toxins can cause diarrhea and upset stomach. It is reported to be a kidney and liver carcinogen. This species is only occasionally pathogenic- U. Minn.

General comments about your samples and your field notes: these opinions (written before I examined your tape sample in order to avoid any bias in our comments) are offered as technical background since I have not personally inspected the building you describe.

[items 1-4 deleted for privacy]

5. Use of cultures as building screens for the presence or absence problematic mold is unreliable - only 10% of all molds of any genera will grow on any culture under any circumstances, so a mold culture screening test for mold is 90% wrong at the outset. More so if one considers that certain molds that can be grown in culture only respond to specific culture media. Even if a mold is grown on a culture, given these constraints one cannot reliably infer that the mold grown is the problem material in a building.

Therefore no screening test by air or culture is an adequate substitute for nor superior to the value of a careful visual inspection by an experienced inspector who knows where mold is likely to grow and what it looks like on or in building surfaces and cavities.

6. Stachybotrys chartarum or other Stachybotrys species can be found, at least at small amounts, in most older buildings since it is common to find this mold on drywall in areas subject to water, such as behind floor trim in a bathroom. However no qualified expert would assert the presence or absence of a mold problem in a building without performing a thorough visual inspection of the property.

Therefore the theoretical diagnosis by a third party who asserted that this building has a Stachybotrys problem is nonsense. Finally, despite media attention to this mold, it is not normally an airborne spore and becomes airborne in quantity only if it is mechanically disturbed such as during demolition in a building.

7. Further investigation: The comprehensive visual inspection (already completed) is the most-critical investigation step to be performed in this matter. Based on your field notes, if you are suspicious of a history of leaks into building cavities which might produce a hidden mold or allergen reservoir, you might consider these additional steps:

  1. a screen of settled building dust (tape sample)
  2. an inspection for visible mold on the cavity side of drywall or paneling in most-suspect areas of prior leaks into walls or ceilings
  3. an inspection of suspect building cavities and possible vacuum samples of building insulation if fiberglass insulation is present in wall or ceiling cavities and in particular, if that material is suspected of having been wet from leaks of any kind.

Notes: Please see the web link references on the next page for added depth of information; For future mail-in samples you are welcome to use and copy the chain of custody form and this the mold sampling procedure

What Should be Done About Mold Found in the Samples

What should be done about mold identified in the samples? This report provides a summary of information at hand for mold or particle types identified in the samples.

If the mold test screening samples contain problematic mold, the mold should be removed. If large areas of problematic mold are present professional mold remediation is needed. Occupants who have health concerns or specific complaints should check with their physician for more advice. Additional mold and allergen health and cleanup guidance:

See http://InspectAPedia.com/sickhouse.htm - Mold Information Center - what to do about mold and

See Mold Action Guide: What to do about mold, mildew, and other indoor allergens

When to hire a professional to inspect or clean-up mold

mold contamination in fiberglass insulation

Unless the sample collection was combined with an expert inspection of the building, one cannot be certain of the extent of mold or other particle contamination in a building.

Similarly, without an expert inspection one cannot determine if a sample accurately represents all of the molds present in the building. Mold Spores-General: It is absolutely expected to find mold in air and surface samples.

Mold spores are allergens found outdoors and inside; there is no seasonal pattern to indoor molds; mold growth is related to moisture levels, temperature, and other conditions. Mold growing anywhere in the building is likely to be distributed by the air circulation, more so if the building uses hot-air heat.

The presence of incidental occurrences (one or two deselected in a sample trace) of problematic mold spores is not by itself significant as such spores could have entered with outdoor air.

However if we find recurrent presentations of problematic spores in multiple samples, particularly if the problematic spore appears to be the same species as that which was to have been cleaned and removed during remediation, and if it regularly appears in chains or clusters, additional cleanup may be in order.

The presence of mold spores in chains would suggest that there is some active mold growth in this building. These chains are so fragile that if mold were only entering from outdoors it is more likely that I would only see single spores or very small fragments.

Extensive mold contamination in buildings as well as some individual mold species have been associated with health risk to children and adults, particularly those with forms of respiratory illness such as asthma or those who may have compromised immune systems or may be otherwise at risk. A very wide range of complaints are often expressed by occupants in buildings.

These complaints might be caused-by or aggravated-by mold or other building contaminants. Any environment where extensive allergenic, toxic, or pathogenic mold/fungus is found is a potential health hazard and should be remediated. Qualified experts who will have their own advice should handle remediation of large areas. New York State and other authorities have described remediation procedures and have identified situations where cleanup may be done by the building owner/occupant.

More information is at InspectAPedia.com/sickhouse.htm. Where chronic health concerns are present, it is essential that building occupants consult their physician for diagnosis and advice. Where complaints persist, additional building investigation is appropriate.

Significant/Dominant Particle Levels - what does this mean in a mold test lab report?

"Significant/dominant" means that these particles were present at significant levels in the sample and/or these particles were so frequent that they were the predominant particle found, typically at least 50% of the total fungal concentration observed. Particles listed in this category are likely to be of significance to occupants in the building.

Where the particle is a mold genera or species capable of growing indoors a finding at this level makes it likely that there is one (or more) mold reservoir or mold colony in the building. When the significant/dominant particle(s) present is/are allergenic or toxic mold or an allergen, building investigation to find and clean/remove the problem source is needed.

Present Particle Levels - what does this mean in a mold test lab report?

"Present" means that these are other spores (other than the category just named above) were frequently present in the sample, typically comprising 20% to 50% of the total fungal concentration observed. They are less likely to be of significance to occupants of the building except when particles named are 1. particularly allergenic or toxic 2. are not commonly found in outdoor air or 3. of other technical significance, such as the presence of Pen/Asp spore chains.

The presence of individual or a few spores which may be toxic or allergenic is not normally itself a cause for alarm; however if the building has a history of leaks, water entry, or other hidden moisture problems, the presence of even a few toxic or allergenic spores which are not often found in outdoor air samples may indicate a hidden problem. In these cases further investigation is in order to determine if there is a significant presence elsewhere in the building than from where this sample was taken.

Incidental Particles - what does this mean in a mold test lab report?

"Incidental" means that I found only occasional, or low-levels of fungal spores in the sample provided, typically less than 20% of the total fungal concentration observed, or below the level I usually find in indoor air samples in buildings where there has been a history of leaks, flooding, or known mold contamination. I do not normally report particles in this category except as a point of technical/professional interest. This is a positive description of the quality of indoor air insofar as fungal spores are concerned, but one cannot unequivocally conclude that there is no possible health hazard present because:

1. individual exposure, sensitivity, and health status vary widely;

2. even a zero count does not mean a particle is not present in the building. It means only that that particle was not in the sample provided. A more careful , expert look at the building may disclose particles that an occupant was unable to recognize and thus did not send to the laboratory for determination.

Occasional occurrences of certain mold in samples could indicate a hidden or un-noticed mold problem in the building other than at the spot from which the sample was collected, particularly if the sample was collected by someone who is not expert at building science, indoor air quality, mycology, and related disciplines. Occupant indoor air or environment-related complaints or a building history of leaks would suggest that additional investigation is in order.

Sampling versus human exposure - Interpreting a mold test lab report

"Human allergen exposure differs in that an allergic individual functions not unlike a mobile air sampler in that he moves from site to site throughout the sequence of daily behavior, sampling the various environments s/he passes through. In this respect the human aeroallergen exposure is the sum total of all the various environments passed through in a given period of time, whereas the air sampler exposure is limited to what occurs in a single environment during the same time interval."

Therefore, the samples collected at a site attempt to describe that single environment whereas a human, operating during the same time interval, will be sampling a variety of environments unless s/he is sedentary.

Mold exposure standards give a wide range of mold hazard criteria

Given these complex variables, and adding the significant variation in individual fungal spore size and probable health effects, absolute spore counts, whether viable in culture or non-viable in air or surface dust, may be useful but by themselves they are not reliable as indicators of actual human exposure in buildings where so many variables pertain.

To avoid costly inappropriate mold remediation, a quantitative "exposure standard" would have to take into account not only the wide range of individual vulnerability and exposure, but also the wide range of risk among every genera, species, and strains of mold which might be found in buildings. In many cases necessary research has not been performed.

Mold Report Terms & Definitions: how to read your mold lab report

Conidiophore: the component of a fungus which produces fungal spores. A conidiogenous cell, or a fertile fungal cell which is specialized for the production of conidia (fungal spores). [paraphrased] - Illustrated Dictionary of Mycology, Ulloa and Hanlin. Finding conidiophores in an indoor sample is very strong evidence of an actual growing (or previously growing) fungal colony in the building.

Chlamydospores: are thick-walled resistant spores which develop to permit a fungal species to survive in a dormant state, typically waiting for more favorable conditions for growth. They are an indication of conditions previously favorable to fungal growth, and can produce future fungal activity. -- Illustrated Dictionary of Mycology, Ulloa & Hanlin, American Phytopathological Society, 2002.

Debris at excessive levels: this comment means that the sample contained excessive levels of particle debris. When a sample collects to much debris important particles may be obscured in the debris. If it was an air or vacuum sample, high levels of debris can also cause important particles, particularly small spores such as Penicillium sp. or Aspergillus sp. to fail to adhere to the collection media. Both of these factors tend to make any estimate of the levels of spores or problem particles lower than actual in samples containing excessive levels of debris.

Genera (genus-singular): one of the principal ranks in the naming structure of organisms, this is the first part of the standard two-part species name genera species, for example Aspergillus niger. A given genera e.g. Aspergillus, may be made up of many species members, and individual species may vary considerably in their importance to human health.

Species - (abbreviated sp.) - the lowest principal rank in the nomenclatural hierarchy [for living organisms], consisting of two elements (a binominal): a generic name ["family"] and a species epithet [specific individual member in the family. A genera such as Aspergillus may have more than 100 species, each with different potential medical and other effects.

Finally, the potential medical effects of an individual species may themselves vary depending on growth conditions such as choice of nutrient substrate, stage in sexual development of the organism, and other factors.] - taken in part from Dictionary of the Fungi, 9th ed., Kirk, et als. [annotations by DJF].

In some instances the contents of an indoor sample (air, dust, surface, etc) may contain particles which permit determination of the mold genera, but not the species. In this case we report the finding name as "genera sp." such as Aspergillus sp. rather than the more-detailed example "Aspergillus niger." Where appropriate additional work can often be ordered for such samples in order to determine the individual species as well.

Hyphal fragments or mycelia are components of fungal growth (similar to the roots and branches of a tree); it is common to find small hyphal fragments in outdoor air and possibly in indoor dust. But their presence in indoor air samples, if in quantity or in large segments, suggests an active fungal colony in the building. Their presence in a surface sample in quantity or in large segments indicates that active fungal growth is present or nearby, or that fungal material has been disturbed in the building. May be allergenic. -DF

Mitospores - this is an artificial collection of a large group of fungi which is used by aerobiologists to refer to members of the deuteromycete class of asexual fungi which could not be identified to genera/species in the particular sample. Many of these have been related to the ascomycetes or basidiomycetes groups. If a spore is recognizable as a specific genera or genera/species, particularly one which is already known to be problematic in indoor air it will be so-named and will not be reported in this group.

Spore, conidia, or "fungal spore," "a small unit of propagation, ™ capable of giving rise to a new individual. A spore functions like a seed. ™ Spores can be spread by air, water, insects, or other animals. Illustrated Dictionary of Mycology, Ulloa and Hanlin [paraphrased by DF]. In buildings airborne spores are the ones likely to be of greatest risk to humans, although certain other spores which are not intended to be spread in air can be infectious if placed directly in an eye, an open cut, or on other sensitive tissues. -DF

What should you watch out for in reading a report from a mold testing lab

What about inaccurate, misleading reports? These defects can be quite dangerous: if a significant quantity of toxic material is present in an environment and in the samples collected, it ought to appear in the report. At the same time, a report which "protects" the investigator or laboratory by too-broad warnings risks wasting the client's time and money on a wild goose chase.

A good mold test lab report should identify dominant and significant levels of particles which are found present in air, surface, vacuum, or other samples. Where the laboratory is unable to "speciate" the genera it should so indicate. Sometimes even the presence of a few spores can be significant if they are highly toxic, as they might indicate that a problem material is present or growing somewhere in the building. But a distinction should be made between what is obviously significant by visual inspection (or if necessary by actual quantitative measurement if it was an air sample), and what was found as present but not necessarily significant.

A vague report might, for example, identify a major and common genera like "Cladosporium" by indicating that "Cladosporium sp." was found. Because Cladosporium is perhaps the most common mold genera, and because it's a pretty big family with perhaps 40 or more members or sub species, and because perhaps one of those members or species is toxic, a hasty lab might protect itself by an asterisked note indicating "*

Some members of this genera are toxic." Further, some species are usually found in and associated with outdoor air; others are quite common indoors. This distinction might be a clue about the building condition and its air quality. Without actually identifying the presence of a dangerous species, would it be appropriate to launch a very costly remediation program? Maybe not. To be fair, depending on the sample quality, condition, and content, it is not always possible to determine species by visual inspection.

What inspection methods and testing techniques form the basis of your indoor air/mold investigation report? Mold cultures are unreliable for overall characterization of fungal contamination of indoor air. Home test kits, settlement plates, samplers which collect spores onto petri dishes, and sterile swabs all have a place in the arsenal of tools but not for overall building characterization.

Mold Testing Laboratory qualifications

We wouldn't expect an aerobiology or "mold test lab" to operate without someone at hand who actually has some appropriate knowledge and experience. But watch out for laboratories that are over-worked, processing perhaps thousands of samples monthly with a too-small or under-trained staff. The fact that a laboratory has some certification does not assure you that the "certification" is pertinent to the work being performed in your behalf, nor that the individual actually doing the work is properly trained. In one class I attended a mold test lab supervisor showed me the "cheat sheet" she provides to her afternoon high-school aged employees who are "trained" to look through the microscope for one of the eight common mold species whose photograph appears on a colored card. An under-trained lab technician may be tempted to stop examining a sample as soon as s/he finds one of the "important eight" on the card. In a similar case we found a lab which over-reported the presence of Stachybotrys chartarum which was less important as an airborne presence in that particular building than a very large colony of Aspergillus niger . Why was this error occurring? Because Stachybotrys chartarum is a comparatively large black spore which is easily recognized in a sample while the Aspergillus niger spores are tiny and nearly colorless, requiring more careful and patient microscope work to recognize. But wait a minute! One can hardly expect a laboratory to diagnose a building based simply on a few samples collected by someone else, possibly by someone with no proper experience. The best a lab can do is tell you what's in the sample collected, not whether the sample represents the building and not whether the sample captured the most important problem in the building. How can you be more confident? Inspect the building with knowledge and care. Collect historical and occupant data. Then perform good lab work and lab interpretation based on the site data.

Can you understand your toxic mold test lab report? Finally, you should be able to read and understand your lab report. If you paid a field investigator to examine your building you should be able to ask that person for additional advice concerning the lab results, and you should also be able to ask the lab director questions if the report is not clear. Investigators who disclaim any responsibility to you, saying "ask the lab," and laboratories who say "we just process the sample, ask the investigator" are not being as helpful as they should.

  • Mold Action Guide: follow this easy step by step outline of what to do
  • Mold Detection - Articles on Mold Identification Photos and Tips - How to Find and Recognize Mold in a Building - articles describing how to find problem mold
  • Mold Test Kits - How to Collect and Send Your Own Mold Sample to our mold testing lab
  • Mold Cleanup - How to Clean Up Mold or Remove Mold in Buildings
  • MOLD RESISTANT CONSTRUCTION - How to Prevent Mold Growth in Buildings
  • FAQs Frequently Asked Questions About Mold - this detailed list answers most questions about mold
  • Mold Action Guide after Flooding: How to Minimize Mold Damage After a Building Flood
  • Renters and Tenants how can a tenant deal with a moldy rental apartment or rental home
  • Contact Us to arrange mold/IAQ Building on site mold or other IAQ inspection and testing.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Technical reviewers are invited to comment or ask questions - contact us

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.


MOLD INFORMATION CENTER
BASICS YOU NEED
FLOODS & MOLD CLEAN/PREVENT
MOLD ACTION GUIDE - WHAT TO DO
MOLD EXPERT, WHEN TO HIRE
MOLD RELATED ILLNESS
MOLD DETECTION & INSPECTION
MOLD TEST METHODS, ACCURACY
MOLD TEST PROCEDURES
MOLD TEST REASONS

MOLD TEST KITS
MOLD CULTURES
MOLD CLASSES, HAZARD LEVELS

MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEANUP with BLEACH
MOLD CLEANUP - WOOD FLOORING
MOLD CLEANUP - WOOD FRAMING & PLYWOOD
MOLD CLEANUP HEALTH RISKS
MOLD CLEANUP MISTAKES to AVOID
MOLD CLEANUP - SAFETY WARNINGS

MOLD CLEARANCE INSPECTIONS
MOLD LEVEL REPORTS
MOLD INVESTIGATION PROCEDURE TIPS
MOLD INVESTIGATION REPORTS
MOLD LAB REPORTS
  Purpose of Mold Lab Reports
  Example Mold Report
  Significance of Findings
  What Should Be Done
  Significant Particle Definitions
  Sampling vs human exposure
  Mold exposure standards
  Report Terms & Definitions
  Lab Report Usefulness
  Mold Lab Qualifications
MOLD REMOVAL or CLEANUP
MOLD CLEARANCE INSPECTIONS
ODORS & SMELLS
PREVENT MOLD, HOW TO
TECHNICAL PROCEDURES
ODORS & SMELLS
OTHER IAQ CONCERNS
OUR FIELD SERVICES
OUR LABORATORY SERVICES

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Environmental Health & Investigation Bibliography - our technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Adkins and Adkins Dictionary of Roman Religion discusses Robigus, the Roman god of crop protection and the legendary progenitor of wheat rust fungus.
  • Kansas State University, department of plant pathology, extension plant pathology web page on wheat rust fungus: see http://www.oznet.ksu.edu/path-ext/factSheets/Wheat/Wheat%20Leaf%20Rust.asp
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • US EPA - Mold Remediation in Schools and Commercial Building US EPA
  • US EPA - Una Breva Guia a Moho - Hongo - en Espanol

Mold Contamination Testing, Cleanup, Prevention: references & products

  • GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminantsThe Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
  • Aerobiology, Building Science, Microscopy, & Laboratory References, an extensive technical bibliography
  • Allergens: what they look like in buildings
  • Associations: Sick House, Sick Building, SBS - Air Quality, Government, Private Associations and Information Resources
  • Atlas of Clinical Fungi, 2nd Ed., GS deHoog, J Guarro, J Gene, & MJ Figueras, Centraalbureau voor Schimmelcultures, Universitat Rovira I Virgili, 2000, ISBN 90-70351-43-9 (you can buy this book at Amazon)
  • Atlas of Mold Related Illness: Index of Symptoms and health, physical, neurological, psychological, and other complaint which people suspect may be mold or building-related.
  • Atlas of Indoor Mold, Online Clinical Mold Atlas, Toxins, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • Black Mold that is Harmless Photos of recognizable, usually harmless black mold on wood, bluestain, ceratocystis, ophistoma
  • Building Floods: quick steps after a building flood or plumbing leak can prevent costly mold contamination
  • Classes of Mold: what types of cosmetic, allergenic, or toxic mold are a problem? Can mold be cleaned-up successfully?
  • Clinical Mold References - Detailed bibliography of mold reference texts
  • "A Brief Guide to Mold, Moisture, and Your Home", U.S. Environmental Protection Agency US EPA - includes basic advice for building owners, occupants, and mold cleanup operations. See http://www.epa.gov/mold/moldguide.htm
  • "Disease Prevention Program for Certain Vegetable Crops," David B. Langston, Jr., Extension Plant Pathologist - Vegetables, University of Georgia (PDF document) original source: www.reeis.usda.gov/web/crisprojectpages/209797.html
  • "Disease Prevention in Home Vegetable Gardens," Patricia Donald, Department of Plant Microbiology and Pathology, Lewis Jett
    Department of Horticulture, University of Missouri Extension - extension.missouri.edu/publications/DisplayPub.aspx?P=G6202
  • "Management of Powdery Mildew, Leveillula taurica, in Greenhouse Peppers," Ministry of Agriculture and Lands, British Columbia - Original source: www.agf.gov.bc.ca/cropprot/peppermildew.htm
  • Environmental Health & Investigation Bibliography - our own technical library on indoor air quality inspection, testing, laboratory procedures, forensic microscopy, etc.
  • Fiberglass: Mold in Fiberglass Insulation© 2005 comments about a field study in process, & more about health hazards from fiberglass insulation - DJF
  • Fifth Kingdom, Bryce Kendrick, ISBN13: 9781585100224, is available from the InspectAPedia online bookstore - we recommend the CD-ROM version of this book. This 3rd/edition is a compact but comprehensive encyclopedia of all things mycological. Every aspect of the fungi, from aflatoxin to zppspores, with an accessible blend of verve and wit. The 24 chapters are filled with up-to-date information of classification, yeast, lichens, spore dispersal, allergies, ecology, genetics, plant pathology, predatory fungi, biological control, mutualistic symbioses with animals and plants, fungi as food, food spoilage and mycotoxins.
  • Fungi, Identifying Filamentous, A Clinical Laboratory Handbook, Guy St-Germain, Richard Summerbell, Star Publishing, 1996, ISBN 0-89863-177-7 (English) (buy at Amazon)
  • Looking for Mold Procedure: what mold is often found where in buildings - simple technical presentation
  • Meruliporia: the house eating fungus or "poria"
  • Mold Action Guide: Step-by-Step Instructions, What to do about mold, mildew, and other indoor allergens
  • MOLD APPEARANCE - WHAT MOLD LOOKS LIKE Photos of what mold looks like in buildings
  • MOLD APPEARANCE - STUFF THAT IS NOT MOLD Photos of NOT-mold material that is sometimes mistaken for mold
  • MOLD ATLAS & PARTICLES INDEX, Pathogens, Allergens and Other Indoor Particles - Medical Health Effects of Mold (separate online document)
  • MOLD BY MICROSCOPE Mold under the microscope - photo identification of the most common indoor molds found in buildings
  • Mold FAQs Answers to Most Questions about Indoor Mold, Mold Related Illness, Mold Cleanup, Mold Prevention
  • US EPA: Mold Remediation in Schools and Commercial Building US EPA
  • Mold spores in the Home - a Photo ID Library for detection and identification of mold allergens
  • Mold Test Kits - How to Collect and Send Your Own Mold Sample to our mold testing lab or to any mold lab you wish
  • Most Common Indoor Molds Found in Buildings, A Table of
  • Mycology, Fundamentals of Diagnostic, Fran Fisher, Norma B. Cook, W.B. Saunders Co. 1998, ISBN 0-7216-5006-6 (buy this book at Amazon)
  • Ozone Warnings - Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Rot concerns in buildings-some building mold such as Meruliporia incrassata "Poria" risks serious rot and hidden structural damage
  • US EPA: Una Breva Guia a Moho - Hongo - en Espanol

OTHER IAQ ISSUES: How To Find and Address Other Indoor Air or Indoor Environment Contaminants Besides Mold

Mold or allergens may not be the only or even the main indoor environmental contaminant. Don't let media attention to mold cause so much enviro-scare fear that other, possibly more urgent hazards go un-addressed.

  • Fiberglass building insulation and HVAC duct work insulation hazards
  • Sewage and Septic backup contamination in buildings: inspection, testing, remediation, & references to expert sources
  • Other environmental risks: Asbestos, carbon monoxide, electromagnetic fields, environmental illness, fiberglass, MCS - multiple chemical sensitivity, toxic gases, etc
  • Indoor Gas Sampling Plan for Residential Buildings lists a number of toxic indoor gases which we test for, depending on the building complaint and building conditions
  • Ozone Warnings - Use of Ozone as a "mold" remedy is ineffective and may be dangerous.
  • Pet control - if you can't say goodbye to your bird, cat, dog, guinea pig, hamster, tropical fish, then limit the areas they occupy and limit the airflow from that area to sleeping or other areas of the building, use allergenic bedding, eliminate wall-to-wall carpeting, improve housecleaning including use of a HEPA-rated vacuum cleaner. For more details see our article Dog, Cat, and Other Animal Dander - Information for Asthmatics and Indoor Air Quality
  • Rodents, Mice, Squirrel Control - I find high levels of mouse and rodent dander, fecal dust, and urine-contaminated dust in some buildings, and high levels of these materials in building insulation in those locations. If you have a mouse problem, particularly if mice and their waste (fecals or urine) are contaminating the building HVAC or building insulation, may need both steps to clean up or remove infected materials and steps to stop an ongoing rodent problem. If squirrels are a problem, the cleanup needs to include closing off entry openings into the building. Get some help from a licensed pest control expert.
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com