InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone/PDA website viewMobile View

INTERIORS
AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN BUILDINGS
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
BASEMENT WATERPROOFING
BATHROOM VENTILATION
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CRAWL SPACES
  Crawl Space Dryout Procedures
  Crawl Space Safety Advice
  Crawlspace Mold Advice
  MOLD CLEANUP by MEDIA BLASTING
  Mold on Dirt Floors
ELECTRICAL
  Electrical Inspection Safety
ENVIRONMENTAL HAZARDS
FIBERGLASS INSULATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
  FIRST PRIORITIES
  BUILDING ENTRY PROCEDURE
  ELECTRICAL SAFETY for Flood Damage Inspectors
  FOUNDATION INSPECTION FOR FLOOD DAMAGE
  FLOOD RESPONSE CHECKLIST
  FLOOD VENTS
  FLOODS IN BUILDINGS-mold
  SEWAGE CONTAMINATION IN BUILDINGS
  SEWAGE PATHOGENS in SEPTIC SLUDGE
FLOOD DAMAGE TO FOUNDATIONS
FLOORING TYPES & DEFECTS
FOUNDATION WATERPROOFING
FREEZE-PROOF A BUILDING
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSEWRAP - TYVEK INSTALLATION DETAILS
ICE DAM PREVENTION
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION
MOBILE HOME INSPECTIONS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEANUP with BLEACH
MOLD CLEANUP - WOOD FRAMING & PLYWOOD
MOLD CLEANING MISTAKES
MOLD EXPERT, WHEN TO HIRE
MOLD INFORMATION CENTER
MOLD TEST KITS
MOLD RESISTANT DRYWALL
MOLD PREVENTION
MOLD on or in CARPETS
ODORS & SMELLS DIAGNOSIS & CURE
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME
SEARS KIT HOUSES
STAIN DIAGNOSIS
STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES
STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
THERMAL TRACKING
WATER ENTRY in BUILDINGS
WINTERIZE A BUILDING

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us



Wet crawl space unsafe to enter (C) Daniel FriedmanHow to Dry Out a Crawl Space and Keep it Dry, avoiding crawl space mold, insect damage, rot, & allergens
InspectAPedia®  -    

  • Step by step guide to remove moisture and water from crawlspaces and to keep the crawl area dry
  • Crawl space de-watering, crawl space sealants, and crawl space insulation & ventilation advice
  • Mold prevention, insect pest damage risk reduction, allergen reduction in crawl spaces
  • Crawl space ventilation vs. dehumidification and conditioning to avoid moisture
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

This article describes the steps needed to dry out a building crawl space and how to keep it dry and clean. Damp or wet crawl spaces invite mold contamination, insect attack, and structural rot and may also contribute to bacterial hazards. Keeping these spaces dry and clean is not difficult if we address the steps needed in the right order. The crawl space shown in our page top photo was in our opinion not a readily accessible area because of flooding. This decision is made by the inspector on the scene, not by anyone else. Also see MOLD CLEANING MISTAKES for a master list of the principal ways that people foul up mold cleanup projects.

© Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

How to Dry Out a Problem Crawl Space

Before entering a crawl space to inspect its condition or to clean up the crawl space or make repairs in the crawl area, first please see Crawl Space Safety Advice.

Frozen water in a wet crawl space (C) Daniel Friedman

Stop water from entering the crawl space from outside: this means attend to roof gutters and downspouts - the most common cause of crawl space water entry or high moisture in most areas.

Our photo shows frozen water in a wet and cold crawl space below a condominium in Poughkeepsie, New York. The very wet masonry blocks along the rear wall of the crawl area and water stains higher on these walls tell us where the water is coming from.

If a building site is unusually wet or springs are adjacent to the building foundation, additional steps such as the installation of a drainage system and sump pump inside or exterior foundation drainage and waterproofing could be necessary.

But before pursuing those costly measures, be absolutely certain that roof runoff and surface runoff have been directed well away from the building.

Inspect the building exterior, from roof to ground, for sources of water that need to be directed away from the structure.

Also see BASEMENT WATERPROOFING and see FOUNDATION WATERPROOFING that discuss various methods used to keep water and excessive moisture out of buildings or to get rid of water that has leaked into a building.

foam insulation on water pipes (C) Daniel Friedman

Stop water from entering the crawl space from inside: this means:

  • Inspect the building interior, attic to basement and crawl spaces, also looking for sources of leaks, moisture, improper venting, that could affect the structure. In the basement and crawl spaces, look for visual evidence of the pattern of water entry - where has water been entering the building? Trace that water to its source and cause.
  • Repair any leaks in building drains over or in the crawl space. Check below bathrooms, kitchens, and also check hot water heating lines or steam condensate return lines in the crawl space.
  • Repair any leaks in supply piping in the crawl space.
  • Insulate cold water pipes in the crawl space to stop dripping of condensation that forms on the cold water lines in humid weather. It's a good idea to do this in the basement too.

Also see FREEZE-PROOF A BUILDING.

Crawl space vent shown from inside the crawl area (C) Daniel Friedman

Crawl space venting – this is a debated topic as in humid weather venting outside air into a cool crawl space might increase crawl space moisture.

We no longer recommend simple passive venting nor humidistat-controlled venting except in special circumstances.

When our onsite inspection indicates a long-standing moisture problem in such an area the best current advice is to stop venting the crawl space and to convert it to a dry, conditioned space.

Step by Step Guide to Drying out the Crawl Area and Keeping it Dry

An iffy crawl space (C) Daniel Friedman

Remove crawl space debris from the area.

Not only are nails, splinters, and possibly rodents that may be in the debris a hazard to workers entering the area, these materials also invite termites, carpenter ants, or rodents which in turn damage the building.

Old cardboard boxes and stored junk invite mold growth and rodents.

Do not bring mold-suspect boxes of stored items out of the crawl space (or basement) back into the living area of the building. Take them outside for inspection and if appropriate, cleaning and salvage.

Contaminated insulation in a crawl space (C) Daniel Friedman

Is there wet or falling or rodent-infested fiberglass insulation in the crawl area? If so there is a high risk of mold or rodent contaminants that could present a fungal, bacterial, or viral airborne hazard. We recommend completely removing all fiberglass insulation from crawl spaces.

Do not enter such an area without protective gear.

See Mold in Fiberglass Insulation.

Fiberglass is an effective and cost-effective building insulation product that performs very well in many applications. And from the factory you can expect fiberglass building insulation products to be nice and clean. But we do not recommend this material for use in crawl spaces or other tight, limited-access under-building areas nor for use against foundation walls.

If the floors above a crawl area or the rim joist or perimeter of the building need to be insulated we prefer to use spray foam or solid foam insulation in such areas because they resist moisture uptake. Here is a photo of a crawl space that was insulated with spray foam insulation.

But don't insulate the crawl space yet. There is more cleaning, drying, and sealing work needed first.

Remove other Hazardous Materials Such as Asbestos in Poor Condition, or Mold Contaminants from the Crawl Space

Asbestos in crawl area (C) Daniel Friedman

Is there asbestos insulation in the crawl space? Often we find a crawl area in which the asbestos pipe insulation is not just hanging (photo at left) but has fallen onto the crawl space floor.

Asbestos pipe or HVAC duct insulation that has been disturbed,damaged, or deteriorated, including asbestos that has fallen to the floor should be removed and cleaned up by a professional.

Do not enter such an area without protective equipment; take care that you do not track hazardous materials out of the crawlspace and into other building areas.

Do not track asbestos debris back into other building areas.

Mold on framing in a crawl space (C) Daniel Friedman

Is there evidence of mold contamination such as areas of wood, paper, or other material covered with mold or mold-suspect material.

If the crawl area has more than 30 sq.ft. of contiguous toxic or allergenic mold it should be cleaned by a professional mold remediation company.

Beware: often the most serious mold we find in crawl spaces is not the mold you see on wood framing but rather the mold you don't see in fiberglass insulation in a damp or wet area. See Mold in Fiberglass Insulation for details.

Beware also of rodent-infested crawl areas; there may be bacterial or viral hazards from these animals, or from their urine and feces, and in some areas there may be a Hantavirus hazard.

Hantavirus pulmonary syndrome (HPS) is a deadly disease from rodents. Humans can contract the disease when they come into contact with infected rodents or their urine and droppings. HPS was first recognized in 1993 and has since been identified throughout the United States. Although rare, HPS is potentially deadly. Rodent control in and around the home remains the primary strategy for preventing hantavirus infection. - US CDC

See Crawl Space Safety Advice and Crawlspace Mold Advice for details. Do not enter such an area without protective gear.

Should we Use a Vacuum Cleaner to Clean up the Crawl Space?

Do not use a household vacuum cleaner nor an ordinary shop-vac to clean up crawl space dust and debris. Those machines will temporarily but significantly increase the level of airborne dust and debris. Since that dust and debris may contain harmful particles, tossing it into the air increases the risk of cross contamination from the crawl space into other building areas such as a basement or even upper floors in the building.

To vacuum and clean surfaces in a crawl area use a HEPA-rated vacuum cleaner that will trap very fine particulates, and select a vacuum cleaner model that does not have air bypass leaks that escape from the equipment when they should be passing through the filter.

Do we need to Set up Dust Containment and Negative Air to Clean Up the Crawl Space?

Containment barrier for mold remediation (C) Daniel FriedmanNegative air machines and dust barriers are procedures used by professional mold remediation companies, asbestos removal experts, and building flood damage restoration companies. These measures reduce the risk of blowing contaminated dust and debris into other building areas - an event which could be a health risk, especially to occupants who are in fragile health. Photo courtesy of Anabec, Inc.

Even an amateur, do-it-yourself cleanup project would benefit from these methods.

But you should recognize when your cleanup project needs the help of a professional. Here are some examples of conditions that mean you should hire a professional to clean up a crawl area:

There is asbestos material that needs to be removed

  • The area contains a large reservoir of harmful mold, more than 30 square feet of contiguous moldy material
  • The area has been contaminated with sewage and sewer backups
  • The people who plan to do the cleanup are not fit, healthy, and properly dressed and equipped
  • Other building occupants are at particular risk of health effects from stirred-up building dust that may contain mold, fiberglass insulation fragments, bacterial, viral, or other hazards. Examples are the elderly, infants, asthmatics, people suffering from COPD, or people suffering from MCS.

See MOLD EXPERT, WHEN TO HIRE and DO IT YOURSELF MOLD CLEANUP.

Should we use a Power Washer to Clean up the Crawl Space?

Post-Cleanup using a baking soda spray processIf there is room to work, a power washer is a very effective way to clean surfaces, but the increase in water and moisture in the crawl space can make mold or other building-related moisture conditions worse.

In some circumstances such as a crawl area or basement that can be well ventilated, in dry weather, that is well drained, and where other measures are taken to avoid sending a surge of moisture upstairs, power washing might be possible.

Alternative dry-spray surface cleaning methods called media blasting include use of dry-ice spray and baking soda or other abrasive particles, even sand or walnut shell fragments. See MOLD CLEANUP by MEDIA BLASTING. Our photo shows the ceiling over a basement after cleaning by media blasting.

When Is it Good Practice to Use Biocides or Fungal sprays in a Crawl Space or in Other Building Areas?

For full details of this topic, please see MOLD SPRAYS, SEALANTS, PAINTS. The basics are just below.

Spraying a biocide at a mold remediation project (C) Daniel Friedman

  1. First it is important to physically remove contaminated or moldy materials and debris or materials and debris that have been contaminated with sewage or flood water sludge and mud.
  2. Second it is important to physically clean the contaminated surfaces in a crawl space such as moldy joists or subflooring.
  3. Third, use of a biocide, disinfectant, or surface encapsulating spray as a final step makes people feel more confident about the mold or sewage cleanup, but although this is a widespread practice, the use of biocides is questioned by experts.

    One could certainly question the usefulness, effectiveness, and wisdom of spraying carpeting such as shown in our photo. If the carpeting is so infected as to "need" spraying with a disinfectant, it should be removed and the surfaces cleaned instead.


    Anabec NG2000™ and Bioshield BST Protectant RTU75™ are products used in mold remediation projects. These companies produce fungicides and fungicidal sealants as well as related items.

    CalBrite™ (Caltex International) was sold to one of our clients as a biocidal spray but the client's product's package indicated that it was a deck cleaner. The company makes a variety of products used in or on buildings. In general, deck spray products are intended for outdoor use to clean wood-framed decks and deck surfaces. A representative of the company stated that information here is incorrect, but was unwilling to provide specifics. In an unfortunate response to our telephone request for clarifying information, Caltex declined to provide any information whatsoever, and instead threatened litigation, as you can hear in this Caltex recording. Readers can contact company where perhaps they will have better luck obtaining product information.

    Microban Nuocide™ ( Microban antimicrobial products) is an example of a broad spectrum biocidal spray that is in wide popular use by mold and flood damage remediation contractors.

    Also see Protex™ 63, a sealant and coating formulated for exterior use.
 

When is it Good Practice to use Fungicidal Sealants and Encapsulant Sprays in a Crawl Space or in Other Building Areas?

For full details of this topic, please see MOLD SPRAYS, SEALANTS, PAINTS. The basics are just below.

Encapsulant mold spray on top of thick debris (C) Daniel Friedman Clear Fosters 4051 encapsulant spray (C) Daniel Friedman

Clean, don't just spray: Do not, however, permit the use of biocides, disinfectants, sprays, or encapsulants as a substitute for the physical cleaning that must come first.

Otherwise there is risk that you will leave harmful contaminants and particles in the building, and it is likely that cleanup will be inadequate. Look at the thick debris sprayed-over in this building. Simply stirring the debris shows that this approach was ineffective.

Fiberlok IAQ 6000 HD™ (above, left, misapplied), Anabec X70™ waterborne sealant, and Fosters 4051™ (clear coating shown at above right) produce sealants frequently used by mold and flood damage remediation companies.

Once the crawl area has been cleaned of debris and moldy materials, and crawl space water has removed, and after we've eliminated the sources of crawl space water entry, we are ready to take the next steps to keep the crawl area clean and dry.

Details about use of fungicidal sealants and sprays are at MOLD SPRAYS, SEALANTS, PAINTS.

When, Where, How, & Why to Install Moisture Barriers, Heat & Dehumidification Equipment in the Crawl Space

Plastic moisture barrier installed in a crawl space following mold remediation (C) Daniel Friedman

Provide a moisture barrier over any dirt floors and extending up foundation walls but not up to nor in contact with wood framing or sills.

Moisture barriers may be 6-mil poly or other special basement sealer products such as special moisture-sealing concrete coatings.

The crawl space moisture barrier system shown here uses mechanical fasteners and adhesive to secure the plastic barrier to the foundation walls near the tops (but short of wood framing to reduce insect attack risk).

We install moisture barriers to stop the "pumping action" that draws moisture into a building through the foundation walls or through the crawl space dirt or concrete floor. Moisture pumping occurs as moisture evaporates off of the indoor surface into building air. This process invites movement of additional water molecules through the outside surfaces and into the building.

Mold remediation completed in a problem crawl space (C) Daniel FriedmanChoose your crawl space plastic vapor barrier material carefully. Some plastics can give off an obnoxious odor themselves - an effect which may become suddenly noticeable and more significant than you anticipated once you've spread a smelly plastic out over a large crawl space area below a building.

It may take some time for such odors to dissipate. (We don't have data on possible health effects of the volatiles and gases comprising the odor from smelly plastic vapor barriers. Contact us if you do.) The white reinforced plastic material shown in the photos here was not producing any noticeable smells at the time of our inspection.

Our photo shows a successful cleanup of a very moldy crawl area that had a gravel and dirt floor. The framing was cleaned, dried, then sealed with a Fosters™ clear fungicidal encapsulant, and a heavy poly vapor barrier was placed on the crawl area floor and sealed neatly throughout. Even high quality workmanship such as this job may not last however, if the building owners do not take the outside steps to keep water out of the crawl area.

Moisture warning when installing concrete in a crawl space: Poured concrete or similar dense coating on crawl space floors and lower walls is a crawl space sealing and cleaning process offered by some mold and flood damage remediators as an alternative to the plastic vapor barrier.

Before pouring concrete or similar coatings into a confined space under a building you should determine if the surge of moisture that will be generated under the building is going to be a problem for other building areas. If so, you'll need to take steps to direct that moisture outside rather than up through the building.

Puddles on plastic in a crawl space (C) Daniel Friedman

 

Be sure that the dirt floor moisture barrier slopes to a drain.

A great many installations we see, even in company product literature, show multiple low spots in a crawl space, each of which is subject to ponding and water retention from leaks or other unanticipated water entry into a crawl space or basement.

Dehumidifying a crawl space (C) Daniel Friedman

How to install a continuous dehumidification system in a crawl space: (with a permanent drain hookup so the system can run unattended. Use an A/C condensate pump to a building drain if a gravity drain connection is not feasible.

First remove the mold, remove any moldy insulation, then correct the water entry problems, then clean the surfaces, then you can put your dehumidifier to work to keep the space dry.

This installation could have done a better job on the plastic but the dehumidifier is well placed near the center of the crawl space.

If your crawl area is large, add one or more small fans blowing towards the dehumidifier from remote areas of the crawl space. You'll find this makes an enormous improvement in the rate of dehumidification.

Don't even bother to try to dehumidify the crawl space if the area is taking on standing water or puddles. First you'll have to solve the water entry problem. Cleaning up puddles or active foundation leaks with a dehumidifier won't work any more than you can suck the dust off a the living room carpet by standing across the house in the kitchen and waving your vacuum cleaner wand in the air. (This is also why an indoor "air cleaner" cannot remove a problem mold or allergen source in a building.)

Don't put a new dehumidifier into a moldy crawl space if you're going to clean up the mold. Doing so will increase the airborne mold level in some cases - yes as things dry out the mold will begin to release more spores than ever. Also you'll contaminate your dehumidifier with mold spores.

We like to set our crawl space dehumidifiers to 45% RH or lower. We've made lots of humidity measurements. When the humidity right close to the dehumidifier is 45%, you'll find that more distant crawl spaces will have a higher humidity level, especially close to the foundation walls. So if you're trying to dry out the whole area, don't set your dehumidifier above 45% RH.

A dehumidifier in a crawl space will also provide some heat in that area; if the crawl space is too cold (despite perimeter insulation) it may be necessary to add a small level of heat there. Some building also permit introduction of dry heat into these areas.

Make sure your crawl space electrical wiring is safe and meets current electrical codes. Receptacles (such as the electrical outlets you may want to use to power your crawl space fans or dehumidifier) should be GFCI protected and all of the circuits there such as wiring for lighting should be AFCi protected. See AFCIs ARC FAULT CIRCUIT INTERRUPTERS for details on the 2008 National Electrical Code requirements for AFCIs and GFCIs.

Add a heat source to the crawl area to help keep it dry. If plumbing supply or drain lines are in the crawl space that will be another reason to add heat if your building is located in a freezing climate. You don't need much. An air supply register cut into an existing supply duct in the crawl area may be enough, or a small section of heating baseboard if your building uses hot water heating. In crawl spaces where these heat sources are not convenient, add a small electric baseboard or oil-filled electric heater with a thermostat that turns it on at low temperatures.

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also list books on the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

INTERIORS
AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN BUILDINGS
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
BASEMENT WATERPROOFING
BATHROOM VENTILATION
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
CRAWL SPACES
  Crawl Space Dryout Procedures
  Crawl Space Safety Advice
  Crawlspace Mold Advice
  MOLD CLEANUP by MEDIA BLASTING
  Mold on Dirt Floors
ELECTRICAL
  Electrical Inspection Safety
ENVIRONMENTAL HAZARDS
FIBERGLASS INSULATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOOD DAMAGE TO FOUNDATIONS
FLOORING TYPES & DEFECTS
FOUNDATION WATERPROOFING
FREEZE-PROOF A BUILDING
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSEWRAP - TYVEK INSTALLATION DETAILS
ICE DAM PREVENTION
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION
MOBILE HOME INSPECTIONS
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
MOLD CLEANUP with BLEACH
MOLD CLEANUP - WOOD FRAMING & PLYWOOD
MOLD CLEANING MISTAKES
MOLD EXPERT, WHEN TO HIRE
MOLD INFORMATION CENTER
MOLD TEST KITS
MOLD RESISTANT DRYWALL
MOLD PREVENTION
MOLD on or in CARPETS
ODORS & SMELLS DIAGNOSIS & CURE
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME
SEARS KIT HOUSES
STAIN DIAGNOSIS
STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES
STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
THERMAL TRACKING
WATER ENTRY in BUILDINGS
WINTERIZE A BUILDING

  • Harriet Burge, Harvard School of Public Health, and EM Laboratory, a private mold and environmental testing lab - email to D.F. August, 2004. Dr. Burge is an educator, writer, and consultant in the field of indoor air quality and mold contamination.
  • Product literature and MSDS sheets for the biocides and fungicidal sealants listed in this article.
  • US Centers for Disease Control, CDC: www.cdc.gov/ncidod/diseases/hanta/hps/ describes the risks associated with hantavirus.

Directory of Producers of Mold Remediation Products, Fungicidal Sprays, Sealants, Biocides, Washes

See MOLD SPRAY SOURCES & TYPES for our complete product list;

We have no financial interest in any of these products. This data was discovered by internet search. We have no independent scientific data as yet regarding the effectiveness, toxicity, chemical composition, nor durability of these products. Producers of mold remediation products are welcome to Contact Us by email (please, not by telephone) to suggest product listings, website technical content, or technical corrections.

  • Anabec Systems - 9393 Main St. • P.O. Box 433 • Clarence, NY 14031 see http://www.anabec.com/index.cfm Tel: 800-369-8463 Anabec NG2000™ produces many products used in mold remediation projects.
  • Bioshield BST - Bioshield BST Protectant RTU75™ - Bioshield Technologies - Bio Shield Technologies
    P.O. Box 15, Clarks Summit, Pa 18411, Tel: 717-489-1728 Fax - 717-489-0228
    Email – info@bioshieldtech.com
    Web – www.bioshieldtech.com - http://www.bioshieldtech.com/Contact-Us-a/138.htm The company indicates that it
    "... offer a wide assortment of ... antimicrobial and personal protection products .... We work with only the industry’s leading manufacturers—DuPont, Agion, Discovery Medical, Anabec Systems, Woodward Labs, ..."
  • Caltex International Ltd., 60 Presidential Plaza, Suite 1405, Syracuse, NY 13202 Toll Free: 315-425-1040 Email: caltex@caltexinternational.com Website: (deck cleaning) http://www.caltexinternational.com/section/business_opportunities/deck_cleaning/
    [Uncooperative in providing technical information]
  • Fiberlok Technologies, Tel: 800-342-3755 - http://www.fiberlock.com/products/8360.html
    MSDS sheets for the company's products can be found at http://www.fiberlock.com/products/msds.html
    The company refers website visitors to a dealer locator network and states
    "In the event you are unable to locate a distributor near you, please call us at 1-800-342-3755 "
  • Foster Products, 1105 Frontenac St., Aurora IL 60504, Tel: 800-231-9541, Email: fosterproducts@hbfuller.com - http://www.fosterproducts.com/ -
    MSDS sheets for the company's products can be found at http://www.fosterproducts.com/default.aspx?PageID=msds
  • Microban Antimicrobial Products - http://www.microban.com/. The company indicates that
    "Microban® antimicrobial protection is built-in to products during manufacturing to provide continuous antimicrobial product protection. Microban protection can be found in hundreds of consumer, industrial and medical products around the world."
  • Protex 63, Trask Research, W.M. Barr, P.O. Box 1879, Memphis, TN 38101, - http://www.traskresearch.com/contact.html - Tel: 1-866-370-2499 The company indicates that
    "Protex 63 is an EPA registered fungicidal sealant that seals against mold, mildew, and green algae" and
    "Protex™ 63 is a durable, sealant and coating that resists mold, mildew and algal growth. Protex™ dries clear and does not affect the appearance of most surfaces. Protex™ is especially formulated for exterior use."
    MSDS data sheets are available from the manufacturer.
  • Rocima™40, produced by Dow Chemical Company's subsidiary Rohm and Haas, is a
    "Broad spectrum, non-metallic liquid fungicide for a wide variety of fungal organisms"
    http://www.rohmhaas.com/wcm/products/product_detail.page?display-mode=tds&product=1120851
    The MSDS can be found at http://www.rohmhaas.com/wcm/products/product_detail.page?display-mode=msds&product=1120851

Other Mold Cleaning Products, Paint Additives, Fungicidal Sealants, Paints, Coatings

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
INTERIORS
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
WATER ENTRY in BUILDINGS
WINTERIZE A BUILDING

ENVIRONMENTAL HAZARDS GUIDE
AIR POLLUTANTS, COMMON INDOOR
ALLERGEN TESTS for BUILDINGS
ALLERGY TESTS for PEOPLE
ALLERGY TEST ACCURACY
FLOODS IN BUILDINGS-priorities
MOLD INFORMATION CENTER
ACTION GUIDE - WHAT TO DO ABOUT INDOOR MOLD
DO IT YOURSELF MOLD CLEANUP
MOLD ACTION GUIDE - WHAT TO DO ABOUT MOLD
MOLD CLEANERS - WHAT TO USE
MOLD CLEANUP COMPANIES
MOLD CLEANUP GUIDE- HOW TO GET RID OF MOLD
ODORS, Smells, Gases in Buildings-Diagnosis & Cure

More Information

InspectAPedia® Home & Site Map
Air Conditioning
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Privacy Policies
Contact Us

More Information on Building Diagnostic Inspections and Repairs

    ...
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

02/01/2010 - 03/28/1992 - InspectApedia.com/structure/Crawl_Space_Dryout.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark