STRUCTURAL INSPECTIONS & DEFECTS

ADVANCED INSPECTION METHODS
AGE of a BUILDING - how to determine
ARCHITECTURE & BUILDING COMPONENT ID

BASKETBALL MOLD SYNDROME - BBMS
BARK SIDE DOWN on DECKS, TRIM, STEPS
BASEMENT WATERPROOFING
BARK SIDE DOWN on DECKS, TRIM, STEPS
BASKETBALL MOLD SYNDROME - BBMS
BEST CONSTRUCTION PRACTICES GUIDE

BRICK FOUNDATIONS & WALLS
BRICK STRUCTURAL WALL Loose Bulged
Brick Thermal Expansion Cracking
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING SAFETY HAZARDS GUIDE
BUILDING SETTLEMENT

CHIMNEY INSPECTION DIAGNOSIS REPAIR
COLUMNS & POSTS, DEFECTS
CONCRETE FOUNDATIONS
CONCRETE FOUNDATIONS, PRE-CAST
Cracks, Checking or Splitting Beams & Log Homes
CRAWL SPACES

DECK & PORCH CONSTRUCTION
DECK COLLAPSE Case Study
DECK FINISHES COATINGS PRESERVATIVES
DECK FLASHING LEAKS, ROT Case Study
DECKS, ROOFTOP CONSTRUCTION

DEBRIS STAINING on ROOFS
DEFINITIONS of Mobile Home, Doublewide, Modular, Panelized
DEFINITIONS of ENGINEERED WOOD OSB LVL etc
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
DISASTER BUILDING INSPECTION & REPAIR SAFEY

EARTHQUAKE DAMAGED FOUNDATIONS
ENERGY SAVINGS in BUILDINGS
ENGINEERED WOOD Flooring
ENGINEERED WOOD Products

FIRE DAMAGE vs MOLD DAMAGE

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
FLOODS IN BUILDINGS-mold
FLOOR, ENGINEERED WOOD & LAMINATES
FLOOR FRAMING & SUBFLOOR for TILE
FLOOR TYPES & DEFECTS
FLOOR TILE ASBESTOS IDENTIFICATION
FLOOR TILE HISTORY & INGREDIENTS

FOOTING & FOUNDATION DRAINS
FOOTINGS EXPOSED, Repair Methods

FOUNDATION BULGE or LEAN MEASUREMENTS
FOUNDATION CONSTRUCTION TYPES
FOUNDATION CONTRACTORS, ENGINEERS
FOOTING & FOUNDATION DRAINS
FOOTINGS EXPOSED, Repair Methods

FOUNDATION CRACKS & DAMAGE GUIDE
  BRICK FOUNDATIONS & WALLS
  BUCKLED FOUNDATIONS due to INSULATION?
  CRAWL SPACES
  EARTHQUAKE DAMAGED FOUNDATIONS
  FOUNDATION CONSTRUCTION TYPES
  FOUNDATION INSPECTION METHODS
  FOUNDATION FAILURES by TYPE & MATERIAL
  FOUNDATION FAILURES by MOVEMENT TYPE
  FLOOD DAMAGE TO FOUNDATIONS
  FOUNDATION DEFECTS OF OMISSION
  FOUNDATION CRACK EVALUATION
    CRACK MONITORING Methods
    DIAGONAL FOUNDATION CRACKS
    HORIZONTAL FOUNDATION CRACKS
    SHRINKAGE vs EXPANSION vs SETTLEMENT
    Sinkholes & Building Damage
    Thermal Expansion Cracking of Brick
    VERTICAL FOUNDATION CRACKS
  FOUNDATION BULGE or LEAN MEASUREMENTS
  FOUNDATION DAMAGE REPORTS
  FOUNDATION DAMAGE SEVERITY
  FOUNDATION INSPECTION STANDARDS
  FOUNDATION MOVEMENT ACTIVE vs. STATIC
  FOUNDATION REPAIR METHODS
  PIER or PILE FOUNDATIONS
  SITE FACTORS AFFECTING FOUNDATIONS
  SLAB CRACK EVALUATION
    Control Joint Cracks in Concrete
    Freezing & Water Damage
    Frost Heave/Expansive Soil Cracks in Slabs
    Seal Cracks by Polyurethane Foam Injection
    Seal Cracks in Concrete, How To
    Settlement Cracks in Slabs
    Settlement Cracks vs. Frost Heaves
    Settlement Cracks vs. Shrinkage Cracks
    Shrinkage Cracks in Slabs
    Shrinkage Cracks Along Foundation Walls
    Standards for Repair of Cracks in Floors

FOUNDATION FAILURES by TYPE & MATERIAL
  BLOCK FOUNDATION & WALL DEFECTS
  BRICK FOUNDATION & WALL DEFECTS
  BRICK STRUCTURAL WALLS Loose, Bulged
  Brick Thermal Expansion Cracking
  BRICK VENEER WALL Loose, Bulged
  BRICK WALL DRAINAGE WEEP HOLES
  CONCRETE POURED FOUNDATION WALL, SLAB DEFECTS
  CONCRETE PRE-CAST FOUNDATION DEFECTS
  STONE FOUNDATION DEFECTS
  WOOD FOUNDATION DEFECTS

FOUNDATION FAILURES by MOVEMENT TYPE
  BRICK FOUNDATIONS & WALLS
  BUCKLED FOUNDATIONS due to INSULATION?
  BULGED vs. LEANING FOUNDATIONS
  COMBINATIONS OF FOUNDATION MOVEMENT
    Bulge & step cracks
    Earthquake Damage to Foundations
    Flood Damage to Foundations
    Foundation Movement During Collapse
    Other Foundation Step cracks
  HORIZONTAL MOVEMENT IN FOUNDATIONS
    Bulging, Leaning & Sliding Wall
    Horizontal Foundation Creep
    Horizontal Movement & step cracks in brick
    Impact Damage to Foundations
    Thermal Expansion Cracking in Brick
  SETTLEMENT IN FOUNDATIONS
  SHRINKAGE CRACKS in CONCRETE
  VERTICAL MOVEMENT IN FOUNDATIONS
    Diagonal Cracks in Concrete Foundations
    Diagonal Step Cracking in Masonry
    Differential vs. Uniform Settlement Cracks
    Leaning or Tipping Buildings
    Uniform Width vs. Tapered Foundation Cracks
    Vertical Cracks

FOUNDATION INSPECTION METHODS
FOUNDATION INSULATION OPTIONS
FOUNDATION MATERIALS, Age, Types

FOUNDATION REPAIR METHODS
  Bulged foundation Repairs
  Crack Repair Methods
  FOOTINGS EXPOSED, Repair Methods
  Horizontal Movement Repairs
  Seal Cracks by Polyurethane Foam Injection
  Seal Cracks in Concrete, How To
  Shrinkage Crack Repairs
  SLAB CRACK REPAIR
  Vertical Foundation Movement Repairs

FOUNDATION SETTLEMENT
FOUNDATION WATERPROOFING

FRAMING DAMAGE, INSPECTION, REPAIR
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING & SUBFLOOR for TILE
FRAMING MATERIALS, Age, Types
FRAMING METAL STUD PERFORMANCE
FRAMING METHODS, Age, Types
FRAMING SIZE & Spacing, Age, Types
FRAMING TABLES, SPANS for DECKS

FRENCH DRAINS
FROST HEAVES, FOUNDATION, SLAB
FRT PLYWOOD

GALVANIC SCALE & METAL CORROSION
GLUES ADHESIVES, EXTERIOR CONSTRUCTION
GRADING & SITE WORK, EXTERIOR
GUTTERS & DOWNSPOUTS

HOUSE PARTS, DEFINITIONS
HOUSEWRAP INSTALLATION DETAILS

I-JOISTS, Wood Roof Floor

KIT HOMES, Aladdin, Sears, Wards, Others

LEED GREEN BUILDING CERTIFICATION

LOG HOME GUIDE
LVL Laminated Veneer Lumber, Beams

MOBILE HOMES, DOUBLEWIDES, TRAILERS
MODULAR HOME CONSTRUCTION

MOISTURE CONTROL in BUILDINGS

NOISE / SOUND DIAGNOSIS & CURE

OSB - Oriented Strand Board

PANELIZED CONSTRUCTION
PLASTER BULGES & PILLOWS
PLASTER, LOOSE FALL HAZARDS
PLYWOOD Roof, Wall, Floor Decks & Sheathing
PORCH CONSTRUCTION & SCREENING
PRE-CUT & KIT HOMES
Preservative-Treated Framing Lumber

RAILINGS, DECK & PORCH
RAILINGS, STAIRWAY
RETAINING WALL DESIGNS, TYPES, DAMAGE
RETAINING WALL GUARD RAILINGS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SEARS KIT HOUSES
SEPTIC & CESSPOOL SAFETY
SHEATHING, FIBERBOARD
SHEATHING, Gypsum board
SHEATHING Homasote & Other Board
SHEATHING, OSB
SHEATHING, Plywood
SHEATHING, FOIL FACED - VENTS
SIDING, Sheathing Identification - Photo Guide
SINKHOLES, WARNING SIGNS
SINKING BUILDINGS

SLAB CRACK EVALUATION
  Control Joint Cracks in Concrete
  Freezing & Water Damage
  Frost Heave/Expansive Soil Cracks in Slabs
  Settlement Cracks in Slabs
  Settlement Cracks vs. Frost Heaves
  Settlement Cracks vs. Shrinkage Cracks
  Shrinkage Cracks in Slabs
  Shrinkage Cracks Along Foundation Walls

SLAB CRACK REPAIR
  Control Joint Cracks in Concrete
  Seal Cracks by Polyurethane Foam Injection
  Seal Cracks in Concrete, How To
  Standards for Repair of Cracks in Floors
  Vertical Foundation Movement Repairs

SOLAR ENERGY SYSTEMS
Splits in Structural Wood Beams
STAIN & BIODETERIORATION AGENT CATALOG
STAINS on BUILDINGS - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STONE FOUNDATIONS
STRAW BALE CONSTRUCTION
STRESS SKIN INSULATED PANELS
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

TERMITES, ROT
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
TRIM, EXTERIOR CHOICES, INSTALLATION
TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in BUILDINGS
VENTILATION in BUILDINGS

WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in BUILDINGS
WIND ENERGY SYSTEMS
WIND TURBINES & LIGHTNING
WINDOWS & DOORS, Age, Types

WINTERIZE A BUILDING
WOOD FOUNDATIONS

More Information

Photograph of a concrete slab control joint How to Seal Cracks in Concrete Floors & Walls
InspectAPedia®  -    

  • Recommended methods for sealing cracks in concrete floors & slabs
  • Concrete expansion joint sealant products, epoxies, caulks
  • When should we not seal a foundation wall or floor slab crack?
  • Questions and answers about sealing floor cracks
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article how to seal and repair of cracks in poured concrete slabs, floors, or walls. Also see How to Repair Foundation Cracks Using Polyurethane Foam Injection which explains how to use this special method for sealing non-structural cracks in masonry walls or floors, and see FOUNDATION REPAIR METHODS for a more extensive discussion of types of foundation damage and how it is repaired.

This website describes how to recognize and diagnose various types of foundation failure or damage, such as foundation cracks, masonry foundation crack patterns, and moving, leaning, bulging, or bowing building foundation walls.

Types of foundation cracks, crack patterns, differences in the meaning of cracks in different foundation materials, site conditions, building history, and other evidence of building movement and damage are described to assist in recognizing foundation defects and to help the inspector separate cosmetic or low-risk conditions from those likely to be important and potentially costly to repair.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How to seal control joint & expansion joint cracks in concrete slabs

Photograph of a sketch of typical crack patterns in a poured concrete slab

Warning: some crack sealing operations may make crack diagnosis or monitoring more difficult

First of all do not just seal a crack if the crack size, shape, pattern, location, or other evidence indicate that something important is going on with the foundation.

If for example we think that there may be active foundation movement or settlement going on and if that condition is going to be monitored for evidence of further movement, just pushing a flexible sealant or caulk into a crack is leaves some worries unattended:

  • Using a flexible sealant in a structural crack may make it difficult to see small amounts of future movement since the sealant may stretch and tolerate small increases in crack width. This can increase the difficulty of crack monitoring and diagnosis
  • Using a sealant in a foundation or floor slab crack may fail to address the underlying cause of the problem such as foundation settlement or frost heaving which need to be addressed
  • Using a sealant in a crack, except for some structural epoxies, may seal but not "repair" the damage in any structural sense

We may decide to seal a cracked wall or floor slab anyway, to try to reduce water entry in a building, but remember the implications of sealing we've just listed.

How to seal a cracked masonry foundation wall or floor slab

To seal a shrinkage crack or a control joint crack in a poured concrete slab, regardless of whether or not it has occurred at an expansion or control joint, it may be appropriate to seal the surface to resist water entry and radon gas entry. Control joints are also sealed to provide a smooth and clean concrete surface which does not collect surface moisture or debris. Keeping surface water from entering at a control joint might in some cases also help avoid uneven soil settlement below the slab and tipped or heaved slab sections.

To seal a control joint or expansion joint crack in a concrete slab use a flexible sealant designed for foundation crack repair or sealing. The radon mitigation industry offers special foundation caulks and sealants for that purpose as well. (If water is coming up through a concrete floor or slab, sealing cracks is probably not going to be enough - you need to address the cause of water below the floor.)

List of materials used to fill poured concrete slab control joints include:

  • Pre-fabricated control joint strips of plastic or other material
  • Masonry caulks or radon sealant caulks
  • Semi rigid epoxy resin crack fillers intended for concrete expansion joints such as
    • Shor D 65-80®
    • Elasta Gel 6170 Epoxy® flexible epoxy and expansion joint sealant, two component, no VOC, flexible epoxy resin which is rated for use on parking decks and, according to the manufacturer, Lone Star Epoxies, can also be used to repair concrete spalling on such surfaces.
    • other semi-rigid, epoxy products
  • Special poly urea caulks designed as a joint filler

Any sealant that is going to be used to fill a control joint in a slab needs to have the ability to bond to the sides of the cut or opening of the joint, to remain flexible over temperature and moisture changes, and to withstand both compression and expansion as the concrete moves in response to curing and in response to temperature and moisture changes.

Epoxy, for example, is not generally used to fill the expansion joint in newly-poured concrete because the concrete is just too wet and has too much movement for the epoxy to bond and perform acceptably. Similarly, a special product would be needed to fill a control joint in concrete in very cold weather.

Typical concrete crack preparation for sealant with an epoxy product

Carson Dunlop Associates' sketch below shows three common methods used to seal cracks in masonry walls in an effort to stop foundation leaks.

Concrete crack patching methods (C) Cason Dunlop Assoc

  1. Cleaning a concrete crack for patching and sealing: The crack or expansion joint must be cleaned of all debris; power washing and vacuuming may work but inspect the crack or joint to be sure it is clean along its entire length.

    Otherwise the sealant may fail to adhere and the crack will leak. Wire-brushing or chipping the crack sides is not normally required when using an epoxy sealant.

    (Traditional concrete or masonry patching (and plaster repairs), on the other hand, was traditionally applied after cracks were chipped and widened into an inverted "vee" shape to help keep the patch material in the crack.)
  2. Mix the epoxy sealant according to the manufacturer's directions. Some low volume epoxy sealants are supplied in a dispenser which mixes the two parts together in the proper ratio automatically during dispensing from a tube (see your dentist for an example.) Other crack sealants such as prepared caulks, may come pre-mixed in a tube.
  3. Install the backer rod specified by the sealer manufacturer if you are sealing an expansion joint. Sand (clean, dry) may be used as a filler for cracks - an easier approach if you are repairing an irregular crack in a floor. Sand should stop about 3/4" from the top of the floor surface to give adequate volume of sealer epoxy in the crack. The backer rod provides a flexible filler that keeps the sealant in the joint during curing and also reduces the total volume of concrete crack sealer epoxy needed. We recommend using backer rods also if sealing wide cracks in concrete walls or floors, but first you need to have those cracks evaluated to determine the cause as other important structural repairs could be needed first.
  4. Epoxy crack patch cure time: Keep traffic off of the sealed crack until the sealant has cured. Typically a thin film will form on a crack filler epoxy in 8 hours, the sealant will be hard enough to withstand traffic in 24 hours, and it will fully cure in about a week.

These notes are based on epoxy product application information available from Lone Star Epoxies.

Use of Polyurea as a control joint filler in concrete slabs

Wall crack repair by polyurea injection (C) Carson Dunlop Assoc

Polyurea joint filler products for concrete control joints have received attention for filling concrete control joints and is increasingly used in that application since this material is resistant to moisture, has high adhesion properties when used with concrete, and will cure in very cold weather.

Polyurea sealant products are also reported to be useful in sealing control joints in "green" concrete which has not yet had its full 28 day period of initial curing.

Carson Dunlop Associates' sketch (left) illustrates foundation wall crack repair using epoxy or polyurethane injection.

See also Polyurethane Foam Injection for details of the procedure for using polyurethane foam to seal foundation cracks.

Use of Epoxy-supported Grouts as a control joint or crack filler in concrete slabs or walls

Epoxy grouts are available which can be mixed and trowelled into a concrete crack or joint. These products are less flexible than the control joint fillers described above. In our opinion, an epoxy grout filler may work fine to provide a well-bonded repair to a stable wall or floor crack in an area where there is no anticipated further movement such as from temperature or moisture variations. But read the manufacturer's intended application before buying an epoxy reinforced grout for building crack repair. Do not use the product where it was not intended unless a call to the manufacturer provides you with good information that it's acceptable to do so.

On the one hand we like using a rigid material to fix a supposedly stable crack in a residential building since the fact that the patch is inelastic means it will be easy to see if there is ongoing or new building movement.

On the other hand, a small amount of moment in a foundation wall or floor slab due to changes in temperature will leave a flexible crack filler un-damaged and sealed where a rigid material may fail.

Epoxy Grout Product examples include

  • Ramset™ Epoxy Grout - a pourable epoxy resin, also can be mixed with sand and applied with trowel.
  • Epoxy grouts (ANSI 118.3 1988) for tile applications (watch out for proper tile surface cleaning within the cure time; cleanup is done using water)
  • Laticrete™ epoxy grouts

List of the Types of Tile Grouts, their Bonding Agents and other Properties

  • Portland cement grout (ANSI 108.10 1985)
  • Latex-modified portland cement grouts (we've used these with good success indoors in tile floors for better water resistance)
  • Epoxy grouts (described above) usually with a water-dissolved mix
  • Modified Epoxy grouts (ANSI 118.8 1988.) combining portland cement and epoxy (some sources say the chemical resistance is similar to straight Portland cement but the result is a harder grout - just what chemicals are resisted may vary among products)
  • Furan resin grouts use furfuryl alcohol in their prodcuts - no water is used. These are highly acid-resistant, also difficult to install.

Questions and answers about sealing floor cracks in Slabs

Question: should we seal floor cracks exposed when we pulled up basement carpeting? Our house had a radon problem.

We have had our home mitigated for radon. The latest reading is 2.9. Therefore, we feel we are controlling the radon successfully. We are in the process of removing carpet from a 8' X 12" bathroom in the basement. In preparation for installing an overlay linoleum we found a irregular crack in the concrete floor.

Our question is - should we seal this crack with some time of sealer that could be painted on and would this be effective? If so, what type of product would you recommend? - F.H.

Reply: In general, sealing exposed floor slab cracks is a good idea where there was a radon concern, though if your mitigation system is working it might not be critical.

Hairline concrete slab cracks (C) Daniel FriedmanA competent onsite inspection by an expert might find other cracks, openings, or sources for radon gas leakage that you'd want to address, but usually that would have been done when your radon mitigation system was installed.

Following the installation of a radon mitigation system the installer is expected to make a follow-up radon gas level measurement to be sure that the mitigation is working as expected, and s/he also inspects the home to see if you have exhaust fans or other features that could accidentally interfere with proper operation of the radon mitigation system itself.

If all of that was done, the added radon gas leakage into your home from pulling up carpet to expose a floor crack should not be significant. Nevertheless it would be good practice to seal any floor slab cracks that you expose.

Here are some things to consider:

If your floor slab cracks are hairline (less than 1/8" across - see our photograph above left) they may be normal concrete shrinkage and they may be too fine to seal with a polyurethane sealant (see our polyurethane sealant link below). In that case a sealant paint or a combination of mesh tape and sealant used to cover cracks in concrete before installing tile would still work well.

Concrete slab crack (C) Daniel FriedmanFor larger floor slab cracks (such as shown in our photo at left) there are some sealants ("caulks") widely used by radon mitigators that work well in floor or wall cracks, typically polyurethanes. The crack is vacuumed or cleaned, and when dry, sealed.

More sophisticated floor slab crack sealing is done if you are going to put down ceramic tile: the repair includes a strengthening mesh glued to the floor over the crack to resist the transmission of the crack upwards through the ceramic tiles. Under carpet you don't need that step.

At SLAB CRACK REPAIR and Seal Cracks by Polyurethane Foam Injection at we discuss methods to seal cracks in floors.

At How to Remove Indoor Radon we include more details on how to get the radon level down in homes. You'll see that sealing and caulking to stop radon gas from entering at floor or wall cracks or joints is important.

While you're at it, don't forget to check for gaps that may have opened between the floor slab and the foundation wall - seal those too.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

FOUNDATION BULGE or LEAN MEASUREMENTS
  How to Measure Foundation Movement
  Example of Measuring Foundation Bulge
FOUNDATION CONSTRUCTION TYPES
FOUNDATION CONTRACTORS, ENGINEERS
FOOTING & FOUNDATION DRAINS
FOOTINGS EXPOSED, Repair Methods

FOUNDATION CRACKS & DAMAGE GUIDE
  BRICK FOUNDATIONS & WALLS
  BUCKLED FOUNDATIONS due to INSULATION?
  CRAWL SPACES
  EARTHQUAKE DAMAGED FOUNDATIONS
  FOUNDATION CONSTRUCTION TYPES
  FOUNDATION INSPECTION METHODS
  FOUNDATION FAILURES by TYPE & MATERIAL
  FOUNDATION FAILURES by MOVEMENT TYPE
  FLOOD DAMAGE TO FOUNDATIONS
  FOUNDATION DEFECTS OF OMISSION
  FOUNDATION CRACK EVALUATION
    CRACK MONITORING Methods
    DIAGONAL FOUNDATION CRACKS
    HORIZONTAL FOUNDATION CRACKS
    SHRINKAGE vs EXPANSION vs SETTLEMENT
    Sinkholes & Building Damage
    Thermal Expansion Cracking of Brick
    VERTICAL FOUNDATION CRACKS
  FOUNDATION BULGE or LEAN MEASUREMENTS
  FOUNDATION DAMAGE REPORTS
  FOUNDATION DAMAGE SEVERITY
  FOUNDATION INSPECTION STANDARDS
  FOUNDATION MOVEMENT ACTIVE vs. STATIC
  FOUNDATION REPAIR METHODS
  PIER or PILE FOUNDATIONS
  SITE FACTORS AFFECTING FOUNDATIONS
  SLAB CRACK EVALUATION
    Control Joint Cracks in Concrete
    Freezing & Water Damage
    Frost Heave/Expansive Soil Cracks in Slabs
    Settlement Cracks in Slabs
    Settlement Cracks vs. Frost Heaves
    Settlement Cracks vs. Shrinkage Cracks
    Shrinkage Cracks in Slabs
    Shrinkage Cracks Along Foundation Walls
  SLAB CRACK REPAIR
    Control Joint Cracks in Concrete
    Seal Cracks by Polyurethane Foam Injection
    Seal Cracks in Concrete, How To
    Standards for Repair of Cracks in Floors

FOUNDATION FAILURES by TYPE & MATERIAL
  BLOCK FOUNDATION & WALL DEFECTS
  BRICK FOUNDATION & WALL DEFECTS
  BRICK STRUCTURAL WALLS Loose, Bulged
  Brick Thermal Expansion Cracking
  BRICK VENEER WALL Loose, Bulged
  BRICK WALL DRAINAGE WEEP HOLES
  CONCRETE POURED FOUNDATION WALL, SLAB DEFECTS
    Cold Pour Joints
    Shrinkage Cracks in Concrete
    Holes & Penetrations
    Settlement Cracks
    Form Tie Marks & Leak Points
    Other Concrete Wall or Floor Damage
  CONCRETE PRE-CAST FOUNDATION DEFECTS
  STONE FOUNDATION DEFECTS
  WOOD FOUNDATION DEFECTS

FOUNDATION FAILURES by MOVEMENT TYPE
  BRICK FOUNDATIONS & WALLS
  BUCKLED FOUNDATIONS due to INSULATION?
  BULGED vs. LEANING FOUNDATIONS
  COMBINATIONS OF FOUNDATION MOVEMENT
    Bulge & step cracks
    Earthquake Damage to Foundations
    Flood Damage to Foundations
    Foundation Movement During Collapse
    Other Foundation Step cracks
  HORIZONTAL MOVEMENT IN FOUNDATIONS
    Bulging, Leaning & Sliding Wall
    Horizontal Foundation Creep
    Horizontal Movement & step cracks in brick
    Impact Damage to Foundations
    Thermal Expansion Cracking in Brick
  SETTLEMENT IN FOUNDATIONS
  SHRINKAGE CRACKS in CONCRETE
  VERTICAL MOVEMENT IN FOUNDATIONS
    Diagonal Cracks in Concrete Foundations
    Diagonal Step Cracking in Masonry
    Differential vs. Uniform Settlement Cracks
    Leaning or Tipping Buildings
    Uniform Width vs. Tapered Foundation Cracks
    Vertical Cracks

FOUNDATION INSPECTION METHODS
FOUNDATION INSULATION OPTIONS
FOUNDATION MATERIALS, Age, Types

FOUNDATION REPAIR METHODS
  Bulged foundation Repairs
    Pilasters for Repair of Bulge, Cracks
    Reinforcing Steel I-Beams for Wall Bulge
    Foundation Anchors for Foundation Movement
    Reinforcing Sister Walls for Foundations
    Cables for Repair of Foundations
    Reconstruction of Bulged Cracked Foundations
  Crack Repair Methods
  FOOTINGS EXPOSED, Repair Methods
  Horizontal Movement Repairs
  Seal Cracks by Polyurethane Foam Injection
  Seal Cracks in Concrete, How To
  Shrinkage Crack Repairs
    How to Seal Cracks in Concrete
    Polyurethane Foam Injection
  SLAB CRACK REPAIR
  Vertical Foundation Movement Repairs

FOUNDATION SETTLEMENT
FOUNDATION WATERPROOFING
FRENCH DRAINS

SINKHOLES, WARNING SIGNS
SINKING BUILDINGS

SLAB CRACK EVALUATION
  Control Joint Cracks in Concrete
  Freezing & Water Damage
  Frost Heave/Expansive Soil Cracks in Slabs
  Settlement Cracks in Slabs
  Settlement Cracks vs. Frost Heaves
  Settlement Cracks vs. Shrinkage Cracks
  Shrinkage Cracks in Slabs
  Shrinkage Cracks Along Foundation Walls

SLAB CRACK REPAIR
  Control Joint Cracks in Concrete
  Seal Cracks by Polyurethane Foam Injection
  Seal Cracks in Concrete, How To
  Standards for Repair of Cracks in Floors

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.

Repair of Foundation Cracks

For detailed information about foundation repair methods, including repairs to various kinds of cracks in concrete, see:

  • How to Seal Cracks in Concrete - you are currently on this web page.
  • Shrinkage Crack Repairs
  • Polyurethane Foam Injection for details of the procedure for using polyurethane foam to seal foundation cracks.
  • Cracks at Control Joints in Concrete how we prevent shrinkage cracks in poured concrete floors and walls
  • FOUNDATION REPAIR METHODS for our catalog of Foundation Repair Methods - Examples of Typical Foundation Repairs for various types of foundation cracks, leaks, settlement, movement, or other failures
  • "Best Practices for Concrete Sidewalk Construction," Balvant rajani, Canadian National Research Council
  • "Design Considerations for Perlite Roof Slabs," a chapter in "Perlite Concrete Grade for Lightweight Concrete Construction", United Perlite Corporation
  • Quality Standards for the Professional Remodeling Industry, National Association of Home Builders Remodelers Council, NAHB Research Foundation, 1987.
  • Quality Standards for the Professional Remodeler, N.U. Ahmed, # Home Builder Pr (February 1991), ISBN-10: 0867183594, ISBN-13: 978-0867183597
  • Lone Star Epoxies, Rowlett TX, product literature, includes application instructions for this flexible epoxy resin concrete expansion joint sealer. ls@lsepoxies.com - 10/06/08
  • Ramset™ Epoxy Grout, Australia,
  • Laticrete™ Epoxy grouts

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
  • The Journal of Light Construction has generously given reprint permission to InspectAPedia.com for certain articles found at this website. All rights and contents to those materials are ©Journal of Light Construction and may not be reproduced in any form.
  • Appliances and Home Electronics, - energy savings, U.S. Department of Energy
  • Avongard foundation crack progress chart for structural crack monitoring
  • Basement Moisture Control, U.S. Department of Energy
  • Building Failures, Diagnosis & Avoidance, 2d Ed., W.H. Ransom, E.& F. Spon, New York, 1987 ISBN 0-419-14270-3
  • Building Pathology, Deterioration, Diagnostics, and Intervention, Samuel Y. Harris, P.E., AIA, Esq., ISBN 0-471-33172-4, John Wiley & Sons, 2001 [General building science-DF] ISBN-10: 0471331724 ISBN-13: 978-0471331728
  • Building Pathology: Principles and Practice, David Watt, Wiley-Blackwell; 2 edition (March 7, 2008) ISBN-10: 1405161035 ISBN-13: 978-1405161039
  • The Circular Staircase, Mary Roberts Rinehart
  • Construction Drawings and Details, Rosemary Kilmer
  • Crawl Space Moisture Control, U.S. Department of Energy
  • Design of Wood Structures - ASD, Donald E. Breyer, Kenneth Fridley, Kelly Cobeen, David Pollock, McGraw Hill, 2003, ISBN-10: 0071379320, ISBN-13: 978-0071379328
    This book is an update of a long-established text dating from at least 1988 (DJF); Quoting:
    This book is gives a good grasp of seismic design for wood structures. Many of the examples especially near the end are good practice for the California PE Special Seismic Exam design questions. It gives a good grasp of how seismic forces move through a building and how to calculate those forces at various locations. THE CLASSIC TEXT ON WOOD DESIGN UPDATED TO INCLUDE THE LATEST CODES AND DATA. Reflects the most recent provisions of the 2003 International Building Code and 2001 National Design Specification for Wood Construction. Continuing the sterling standard set by earlier editions, this indispensable reference clearly explains the best wood design techniques for the safe handling of gravity and lateral loads. Carefully revised and updated to include the new 2003 International Building Code, ASCE 7-02 Minimum Design Loads for Buildings and Other Structures, the 2001 National Design Specification for Wood Construction, and the most recent Allowable Stress Design.
  • Diagnosing & Repairing House Structure Problems, Edgar O. Seaquist, McGraw Hill, 1980 ISBN 0-07-056013-7 (obsolete, incomplete, missing most diagnosis steps, but very good reading; out of print but used copies are available at Amazon.com, and reprints are available from some inspection tool suppliers). Ed Seaquist was among the first speakers invited to a series of educational conferences organized by D Friedman for ASHI, the American Society of Home Inspectors, where the topic of inspecting the in-service condition of building structures was first addressed.
  • Domestic Building Surveys, Andrew R. Williams, Kindle book, Amazon.com
  • Defects and Deterioration in Buildings: A Practical Guide to the Science and Technology of Material Failure, Barry Richardson, Spon Press; 2d Ed (2001), ISBN-10: 041925210X, ISBN-13: 978-0419252108. Quoting:
    A professional reference designed to assist surveyors, engineers, architects and contractors in diagnosing existing problems and avoiding them in new buildings. Fully revised and updated, this edition, in new clearer format, covers developments in building defects, and problems such as sick building syndrome. Well liked for its mixture of theory and practice the new edition will complement Hinks and Cook's student textbook on defects at the practitioner level.
  • Guide to Domestic Building Surveys, Jack Bower, Butterworth Architecture, London, 1988, ISBN 0-408-50000 X
  • "Avoiding Foundation Failures," Robert Marshall, Journal of Light Construction, July, 1996 (Highly recommend this article-DF)
  • "A Foundation for Unstable Soils," Harris Hyman, P.E., Journal of Light Construction, May 1995
  • "Backfilling Basics," Buck Bartley, Journal of Light Construction, October 1994
  • "Inspecting Block Foundations," Donald V. Cohen, P.E., ASHI Reporter, December 1998. This article in turn cites the Fine Homebuilding article noted below.
  • "When Block Foundations go Bad," Fine Homebuilding, June/July 1998
  • Historic Preservation Technology: A Primer, Robert A. Young, Wiley (March 21, 2008) ISBN-10: 0471788368 ISBN-13: 978-0471788362
  • Log Homes: Minimizing Air Leakage in Log Homes, U.S. Department of Energy
  • Manual for the Inspection of Residential Wood Decks and Balconies, by Cheryl Anderson, Frank Woeste (Forest Products Society), & Joseph Loferski, October 2003, ISBN-13: 978-1892529343, $39.00 at Amazon.com or at the InspectAPediaBookstore
  • Masonry structures: The Masonry House, Home Inspection of a Masonry Building & Systems, Stephen Showalter (director, actor), DVD, Quoting:
    Movie Guide Experienced home inspectors and new home inspectors alike are sure to learn invaluable tips in this release designed to take viewers step-by-step through the home inspection process. In addition to being the former president of the National Association of Home Inspectors (NAHI), a longstanding member of the NAHI, the American Society of Home Inspectors (ASHI), and the Environmental Standard Organization (IESO), host Stephen Showalter has performed over 8000 building inspections - including environmental assessments. Now, the founder of a national home inspection school and inspection training curriculum shares his extensive experience in the inspection industry with everyday viewers looking to learn more about the process of evaluating homes. Topics covered in this release include: evaluation of masonry walls; detection of spalling from rebar failure; inspection of air conditioning systems; grounds and landscaping; electric systems and panel; plumbing supply and distribution; plumbing fixtures; electric furnaces; appliances; evaluation of electric water heaters; and safety techniques. Jason Buchanan --Jason Buchanan, All Movie Review
  • Masonry Design for Engineers and Architects, M. Hatzinikolas, Y. Korany, Canadian Masonry (2005), ISBN-10: 0978006100, ISBN-13: 978-0978006105
  • Masonry Structures: Behavior and Design, Robert G. Drysdale, Ahmid A. Hamid, Lawrie R. Baker, The Masonry Society; 2nd edition (1999), ISBN-10: 1929081014, ISBN-13: 978-1929081011
  • Masonry, Engineered: Using the Canadian Code, J. I. Gainville, Cantext publications (1983), ASIN: B0007C37PG
  • Masonry, Non-reinforced masonry design tables, Hans J. Schultz, National Concrete Producers Association and the Canadian Masonry Contractors Association (1976), ASIN: B0007C2LQM
  • Moisture Control in Buildings, U.S. Department of Energy
  • Moisture Control in Walls, U.S. Department of Energy
  • Quality Standards for the Professional Remodeling Industry, National Association of Home Builders Remodelers Council, NAHB Research Foundation, 1987.
  • Quality Standards for the Professional Remodeler, N.U. Ahmed, # Home Builder Pr (February 1991), ISBN-10: 0867183594, ISBN-13: 978-0867183597
  • R-Value of Wood, U.S. Department of Energy
  • Slab on Grade Foundation Moisture and Air Leakage, U.S. Department of Energy
  • Straw Bale Home Design, U.S. Department of Energy provides information on strawbale home construction - original source at http://www.energysavers.gov/your_home/designing_remodeling/index.cfm/mytopic=10350
  • More Straw Bale Building: A Complete Guide to Designing and Building with Straw (Mother Earth News Wiser Living Series), Chris Magwood, Peter Mack, New Society Publishers (February 1, 2005), ISBN-10: 0865715181 ISBN-13: 978-0865715189 - Quoting:
    Straw bale houses are easy to build, affordable, super energy efficient, environmentally friendly, attractive, and can be designed to match the builder’s personal space needs, esthetics and budget. Despite mushrooming interest in the technique, however, most straw bale books focus on “selling” the dream of straw bale building, but don’t adequately address the most critical issues faced by bale house builders. Moreover, since many developments in this field are recent, few books are completely up to date with the latest techniques.
    More Straw Bale Building is designed to fill this gap. A completely rewritten edition of the 20,000-copy best--selling original, it leads the potential builder through the entire process of building a bale structure, tackling all the practical issues: finding and choosing bales; developing sound building plans; roofing; electrical, plumbing, and heating systems; building code compliance; and special concerns for builders in northern climates.
  • "Vapor Barriers or Vapor Diffusion Retarders", U.S. DOE: how vapor barriers work, types of vapor diffusion barriers, installing vapor barrier
  • Ventilation for energy efficient buildings, Purpose, Strategies, etc.,
  • ...

Sinkholes and Sudden Land Subsidence References, Products, Consultants

  • "A Hole in the Ground Erupts, to Estonia's Delight", New York Times, 9 December 2008 p. 10.
  • History of water usage in Estonia: (5.7 MB PDF) jaagupi.parnu.ee/freshwater/doc/the_history_of_water_usage_systems_in_estonia.pdf
  • "Quebec Family Dies as Home Vanishes Into Crater, in Reminder of Hidden Menace", Ian Austen, New York Times, 13 May 2010 p. A8. see http://www.nytimes.com/
  • "Quick Clay", Wikipedia search 5/13/2010 - http://en.wikipedia.org/wiki/Quick_clay
  • Florida DEP - Department of Environmental Protection, & Florida Geological survey (http://www.dep.state.fl.us/geology/default.htm) on Florida sinkholes: Effects of Sinkholes on Water Conditions Hernando County, Florida, Brett Buff, GIS in Water Resources, 2008, Dr. David R. Maidment, Photos - Tom Scott, Florida Geographic Survey - Web Search 06/09/2010 - http://www.dep.state.fl.us/geology/geologictopics/jacksonsink.htm
    and - http://www.dep.state.fl.us/geology/geologictopics/sinkhole.htm
    also see
    Lane, Ed, 1986, Karst in Florida: Florida Geological Survey Special Publication 29, 100 p.
  • Foundation Engineering Problems and Hazards in Karst Terranes, James P. Reger, Maryland Geological Survey, web search 06/05/2010, original source: http://www.mgs.md.gov/esic/fs/fs11.html
    Maryland Geological Survey, 2300 St. Paul Street, Baltimore, MD 21218
  • "Frost Heaving Forces in Leda Clay", Penner, E., Division of Building Research, National Research Council of Canada, Canadian Geotechnical Journal, NRC Research Press, 1970-2, Vol 7, No 1, PP 8-16, National Research Council of Canada, Accession number 1970-023601, Quoting from original source

The frost heaving forces developed under a 1 ft. (30.5 cm) diameter steel plate were measured in the field throughout one winter. The steel plate was fixed at the ground surface with a rock-anchored reaction frame. heave gauges and thermocouples were installed at various depths to determine the position and temperature of the active heaving zone. The general trend was for the surface force to increase as the winter progressed. when the frost line approached the maximum depth the force was in excess of 30,000 lb (13,608 KG). Estimates of the heaving pressure at the frost line ranged from 7 to 12 psi (0.49 to 0.84 KG/cm) square during this period. The variation of surface heaving force was closely associated with weather conditions. Warming trends resulting in a temperature increase of the frozen layer caused the forces to decline.

  • "Geoscape Ottowa-Gatineau Landslides", Canada Department of Natural Resources, original source http://geoscape.nrcan.gc.ca/ottawa/landslides_e.php - quoting from that source:

    Leda clay slopes in the Ottawa valley are vulnerable to catastrophic landslides. More than 250 landslides, historical and ancient, large and small, have been identified within 60 km of Ottawa. Some of these landslides caused deaths, injuries, and property damage, and their impact extended far beyond the site of the original failure. In spectacular flowslides, the sediment underlying large areas of flat land adjacent to unstable slopes liquefies. The debris may flow up to several kilometres, damming rivers and causing flooding, siltation, and water-quality problems or damaging infrastructure. Geologists and geotechnical engineers can identify potential landslide areas, and appropriate land-use zoning and protective engineering works can reduce the risk to property and people.

    Deposits of Leda clay, a potentially unstable material, underlie extensive areas of the Ottawa-Gatineau region. Leda clay is composed of clay- and silt-sized particles of bedrock that were finely ground by glaciers and washed into the Champlain Sea. As the particles settled through the salty water, they were attracted to one another and formed loose clusters that fell to the seafloor. The resulting sediment had a loose but strong framework that was capable of retaining a large amount of water. Following the retreat of the sea, the salts that originally contributed to the bonding of the particles were slowly removed (leached) by fresh water filtering through the ground. If sufficiently disturbed, the leached Leda clay, a weak but water-rich sediment, may liquefy and become a 'quick clay'. Trigger disturbances include river erosion, increases in pore-water pressure (especially during periods of high rainfall or rapid snowmelt), earthquakes, and human activities such as excavation and construction.

    After an initial failure removes the stiffer, weathered crust, the sensitive clay liquefies and collapses, flowing away from the scar. Failures continue in a domino-like fashion, rapidly eating back into the flat land lying behind the failed slope. The flowing mud may raft intact pieces of the stiffer surface material for great distances.

  • Kochanov, W. E., 1999, Sinkholes in Pennsylvania: Pennsylvania
    Geological Survey, 4th ser., Educational Series 11, 33 p., 3rd printing April 2005, Pennsylvania Department of Conservation and Natural Resources / Bureau of Topographic and Geologic Survey, DCNR Educational Series 11, Pennsylvania Geological Survey, Fourth Series, Harrisburg,
    1999 - web search 06/05/2010, original source: http://www.dcnr.state.pa.us/topogeo/hazards/es11.pdf - Quoting from the document introduction:
    The first 18 pages of this booklet contain an explanation of how sinkholes develop. In order to tell the sinkhole story, it is important to discuss a number of related geologic disciplines. The words used to describe sinkholes and these disciplines may be a bit unfamiliar. However, general explanations are given throughout the booklet to help clarify their meanings. Key words are printed in bold type for emphasis. The more important ones are defined in a Glossary that begins on page 29. The remaining sections, starting with “Sinkholes in the Urban Environment” (page 18), deal with sinkholes and their impact on our environment. This includes recognition of subsidence features and sinkhole repair.
  • [1] Sarah Cervone, [web page] data from the APIRS database, Graphics by Ann Murray, Sara Reinhart and Vic Ramey, Vic Ramey is the editor. DEP review by Jeff Schardt and Judy Ludlow. The web page is a collaboration of the Center for Aquatic and Invasive Plants, University of Florida, and the Bureau of Invasive Plant Management, Florida Department of Environmental Protection contact: varamey@nersp.nerdc.ufl.edu [A primary resource for this article
  • [2] Center for Cave and Karst Studies or the Kentucky Climate Center, both at Western Kentucky University
  • Vanity Fair - web search 06/04/2010 http://www.vanityfair.com/online/daily/2010/06/what-caused-the-guatemala-sinkhole-and-why-is-it-so-round.html
  • Sinkholes, Virginia Division of Mineral Resources,
  • Virginia Department of Mines, Minerals and Energy, www.dmme.virginia.gov Virginia Department of Mines, Minerals and Energy Division of Mineral Resources 900 Natural Resources Drive, Suite 500 Charlottesville, VA 22903 Sales Office: (434) 951-6341 FAX : (434) 951-6365 Geologic Information: (434) 951-6342 http://www.dmme.virginia.gov/ divisionmineralresources.shtml - Web search 06/09/2010

Sink Hole & Related Engineering References

  • Newton, J. G., 1987, Development of sinkholes resulting from man's activities in the eastern United States: US Geological Survey Circular 968, 54 p.
  • Sinclair, W. C., 1982, Sinkhole development resulting from ground-water withdrawal in the Tampa Area, Florida: U.S. Geological Survey Water-Resources Investigations 81-50, 19 p.
  • White, W. B., 1988, Geomorphology and Hydrology of Karst Terrains: Oxford University Press, New York, 464 p.
  • Williams, J. H. and Vineyard, J. D., 1976, Geologic indicators of subsidence and collapse in karst terrain in Missouri: Presentation at the 55th Annual Meeting, Transportation Research Board, Washington, D.C.
  • Barry F. Beck, A. J. (1999). Hydrogeology and Engineering Geology of Sinkholes and Karst. Rotterdam, Netherlands: A. A. Balkema.
  • Beck, B. F. (2003). Sinkholes and the Engineering and Environmental Impacts of Karst. Huntsville, Alabama: The American Society of Civil Engineers.
  • Beck, B. F. (2005). Sinkholes and the Engineering and Envrionmental Impacts of Karst. San Antonio, Texas: The American Society of Civil Engineers.
  • Tony Waltham, F. B. (2005). Sinkholes and Subsidence, Karst and Cavernous Rocks in Engineering and Construction. Chichester, United Kingdom: Praxis Publishing.
  • Whitman D., G. T. (1999). Spatial Interrelationships Between Lake Elevations, Water Tables, and Sinkhole Occurence in Central Florida: A GIS Approach. Photogrammetric Engineering and Remote Sensing , 1169-1178.
  • Cited References from this article:
  • #3. Detecting Sinkholes with Geophysics, Enviroscan, Inc., Lancaster PA 717-396-8922 email@enviroscan.com www.enviroscan.com 2003
  • Sinkholes in Guatemala, Guatemala City, Wikipedia - web search 06/04/2010 - http://en.wikipedia.org/wiki/Guatemala_City