InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
Home | Air
Conditioning
| Electrical
-
Energy Saving
| Environment
Indoor
| Exteriors | Heating | Home
Inspection
| Insulate
-
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Solar
Energy
| Structure | Contact Us
Directory of Professionals to Inspect or Test a Building



AGE of a BUILDING - how to determine
AIR BYPASS LEAKS
AIR LEAK DETECTION TOOLS
AIR LEAK MINIMIZATION
AIR SEALING STRATEGIES
ANIMAL ALLERGENS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN BUILDINGS
ATTIC LEAKS, CONDENSATION & ATTIC MOLD
ATTIC VENTILATION
BASEMENT HEAT LOSS
BASEMENT LEAKS Moisture or Mold
BASEMENT WATERPROOFING
BATHROOM VENTILATION
BEST CONSTRUCTION PRACTICES GUIDE
BLOWER DOORS & AIR INFILTRATION
BRICK LINED WALLS
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE
CATHEDRAL CEILING INSULATION
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COMBUSTION AIR for TIGHT BUILDINGS
CRAWL SPACES
  Crawl Space Dryout Procedures
  CRAWL SPACE GROUND COVERS
  Crawl Space Safety Advice
  Crawlspace Mold Advice
  MOLD CLEANUP by MEDIA BLASTING
  Mold on Dirt Floors
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
EARTHQUAKE DAMAGED FOUNDATIONS
EFFLORESCENCE, Salts & White / Brown Deposits
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENERGY SAVINGS in BUILDINGS
ENVIRONMENTAL HAZARDS
EXTERIORS of BUILDINGS
FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS MOLD
FIREPLACE Damage & Unsafe Hearths - Settlement
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
  FIRST PRIORITIES
  BUILDING ENTRY PROCEDURE
  DRINKING WATER - EMERGENCY PURIFICATION
  DRINKING WATER - EMERGENCY SOURCES
  ELECTRICAL SAFETY for Flood Damage Inspectors
  FLOOD DAMAGE TO FOUNDATIONS
  FLOOD DAMAGE TO FOUNDATIONS
  FLOOD RESPONSE CHECKLIST
  GENERAL MOLD PREVENTION
  SEPTIC SYSTEMS & FLOODS
  SEWAGE CONTAMINATION IN BUILDINGS
  Wind Damage to Roofs
FLOOD DAMAGED FOUNDATIONS
FLOOD VENTS & FLOOD PORTS
FLOODS IN BUILDINGS-mold
FLOORING CHOICES OVER CONCRETE SLABS
FLOORING TYPES & DEFECTS
FOUNDATION BULGE or LEAN MEASUREMENTS
FOUNDATION CRACKS & DAMAGE GUIDE
FOUNDATION WATERPROOFING
FRAMING DAMAGE, INSPECTION, REPAIR
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FREEZE-PROOF A BUILDING
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
Heat Tapes: Use on Roofs for Ice
HEATING COST SAVINGS METHODS
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET
ICE DAM PREVENTION
Ice Dams: Comparing Two Houses
INSULATION CHOICES
INSULATION FACT SHEET- DOE
INSULATION IDENTIFICATION GUIDE
INSULATION LOCATION in BUILDINGS - WHERE TO INSULATE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION for SOUND CONTROL in BUILDINGS
  INSULATION LOCATION for SWIMMING, INDOOR
INSULATION MOLD
INSULATION R-Values & Properties
INSULATION INSPECTION & IMPROVEMENT
INTERIORS of BUILDINGS
LOG HOME GUIDE
MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
  ATTIC CONDENSATION CAUSE & CURE
  Attic Moisture or Mold Sources
  BASEMENT HEAT LOSS
  BASEMENT LEAKS Moisture or Mold
  BASEMENT WATERPROOFING
  Chimney Leaks
  CRAWL SPACE Dryout Procedures
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  EFFLORESCENCE, Salts & White / Brown Deposits
  FLOOD Damage Assessment & Repairs
  FLOOD DAMAGED FOUNDATIONS
  FLOOD VENTS & FLOOD PORTS
  FLOODS IN BUILDINGS-priorities
  FOUNDATION WATERPROOFING
  HUMIDITY CONTROL & TARGETS INDOORS
  HOUSEWRAP AIR & VAPOR BARRIERS
  LOG HOME Leak Diagnosis & Cure
  LOG HOME Condensation &Moisture
  MOISTURE CALCULATIONS
  MOISTURE PROBLEMS: CAUSE & CURE
  MOLD in BUILDINGS
  ROOF VENTILATION SPECIFICATIONS
  Soffit Intake Vents & Attic Condensation
  WATER ENTRY in BUILDINGS
  VENTILATION DESIGN PROBLEMS & SOLUTIONS
  WHOLE HOUSE VENTILATION Strategies
Mold Growth Resistance of Foam Insulation
MOLD INFORMATION CENTER
  MOLD PREVENTION
  MOLD RESISTANT DRYWALL
  MOLD on or in CARPETS
  CARPET TEST GUIDE
  MVOCs & MOLDY MUSTY ODORS
NOISE / SOUND DIAGNOSIS & CURE
ODORS & SMELLS DIAGNOSIS & CURE
PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS
RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME
SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES
SINK HOLES
SLAB CRACK EVALUATION
SOUND CONTROL in BUILDINGS
Splits in Structural Wood Beams
STAIN DIAGNOSIS
STAIRS, RAILINGS, LANDINGS, RAMPS
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
THERMAL TRACKING Indicates Heat Loss
VAPOR BARRIERS
VENTILATION in BUILDINGS
WATER ENTRY in BUILDINGS
  ATTIC LEAKS Moisture or Mold
  BASEMENT De-Watering Systems
  BASEMENT HEAT LOSS
  BASEMENT LEAKS Moisture or Mold
    Cold Pour Joint Leaks
    Form Tie Leaks
    Wall Crack Leaks
    Floor-Wall Joint Leaks
  BASEMENT WATERPROOFING
    BASEMENT DE-WATERING SYSTEMS
    EXTERIOR WATER SOURCE ELIMINATION
    FOUNDATION DRAINS & FRENCH DRAINS
    FOUNDATION WATERPROOFING
    GEOTEXTILES & DRAINAGE MATS
    SEALERS, Basement Floor & Wall Moisture
    SITE DRAINAGE
    SUMP PUMPS GUIDE
    WINDOW LEAKS INTO BASEMENT
  CRAWL SPACE Dryout Procedures
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  EFFLORESCENCE, Salts & White / Brown Deposits
  FLOOD Damage Assessment & Repairs
  FLOOD DAMAGED FOUNDATIONS
  FLOOD VENTS & FLOOD PORTS
  FLOODS IN BUILDINGS-priorities
  FOUNDATION WATERPROOFING
  HUMIDITY CONTROL & TARGETS INDOORS
  HOUSEWRAP AIR & VAPOR BARRIERS
  LOG HOME Leak Diagnosis & Cure
  LOG HOME Condensation &Moisture
  MOISTURE CALCULATIONS
  MOISTURE PROBLEMS: CAUSE & CURE
  MOLD in BUILDINGS
  SEWAGE CONTAMINATION
  SUMP PUMPS GUIDE
  WET BASEMENT PREVENTION
    Wet Conditions - Foundation Collapse
    Living With a Basement that Floods
    Steps to Prevent Basement Water Entry
    Soil Testing
    Water Entry Priorities
    True Foundation Waterproofing
    Foundation Footing Drain Details
    Foundation Drainage Backfill Details
    Finish Grading
    Repairs Cure Basement Leaks
WIND TURBINES
WINDOWS & DOORS
  SKYLIGHT LEAK DIAGNOSIS & REPAIR
  SITE BUILT DOUBLE GLAZED WINDOWS
  SLOPED GLAZING DETAILS
  SUNGAIN, FILMS, LOW-E GLASS
  VERTICAL GLAZING DETAILS
  WINDOW / DOOR ENERGY EFFICIENT, DOE
  WINDOW LEAKS INTO BASEMENT
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Roofing
Plumbing Water Septic
Structure
Accuracy & Privacy Policies
Contact Us



Evidence of deep building flooding (C) Daniel Friedman

Water Entry & Water Damage to Buildings
InspectAPedia®  -    

  • Guide to detecting and evaluating leaks and water entry into buildings
  • Foundation & Structural Damage due to Building Leaks & Water Entry
  • How to Dry Out Buildings after Flooding & Leaks, Prevent Further Damage, Mold, etc.
  • Basement / Crawlspace Water Removal & Leak Prevention Systems
  • Basement waterproofing & foundation coatings or sealants: Wet Basement or Wet Crawl Space Causes & Cures
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/appointment.htm.

Here we discuss the causes of water entry, leak, or actual flooding of buildings, the damage that is caused, and how best to cure water entry problems on buildings. In the page top photo our client points to a flood line on the heating boiler expansion tank, showing us the high-water level reached in this building basement. Observing evidence of the frequency, extent, source, and causes of leaks, water entry, and actual building flooding is a critical step in evaluating a building as well as in planning the cure for building leaks, water entry, and mold.

Our page top photo shows our client pointing to flood lines on a heating system expansion tank, indicating that this building was subject to severe deep flooding. We learned from neighbors that a nearby river had flooded this home and others in its neighborhood repeatedly over the 60 year life of the building.

© Copyright 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Building Leaks, Water Entry, Flooding, Moisture: Diagnosis, Evaluation, Cure, Prevention - Key Concepts

Visual inspection of a the exterior and interior of a building can provide ample evidence of the history of leaks and water entry at a property. Even when a building is brand new, an experienced home inspector or waterproofing or de-watering contractor can spot conditions that are likely to lead to future leaks, water entry, flooding, and moisture or even mold problems at a structure.

Because building leaks, water entry, and flooding and their related damage, ranging from structural damage to costly mold damage are such a large topic, we divide our building water problem inspection, discussion, and advice into these major categories.

Three Degrees of Building Wetness

We also divide our wet building thinking into these degrees of severity:

Damp or moist conditions in a building: in most areas basements and crawl spaces are damp; certainly anywhere that we have masonry construction below ground level we can expect higher humidity and dampness; depending on the degree of moisture and other building conditions, damp or moist conditions can cause mold or other building problems.

Wet conditions in a building: some limited areas of a basement or crawl space floor have been or are regularly wet or showing puddles in some weather conditions, but water does not extend over the entire building floor.

Flood conditions in a building: water extends over the entire building floor, extending from a fraction of an inch to virtually filling the building and even flooding upper floor levels if a building is located in a flood plain or flooded area.

How Long Does It Take for a Building To Dry Out After a Flood or Leak

The length of time required for wet conditions in a building to dry out is quite variable, depending on multiple factors. The time for water to dry in a wall cavity can be substantial, depending on:

  • the original wetness level: Was the building flooded, was there a plumbing leak, is the moisture due to trapped condensation?
  • the building materials involved: more porous materials dry more rapidly and permit the cavities they cover to dry more rapidly
  • the amount of air movement in and out of wet or damp building cavities as well as along the outer surfaces of damp materials or wet building cavities (this is why we supplement use of dehumidifiers with area fans when drying out a building).
  • the permeability of building surface coverings: more porous materials dry more rapidly; building walls, floors, ceilings that include openings or cracks might dry more rapidly, but probably unevenly and unreliably nonetheless
  • temperatures and relative humidity outside the wet building cavities on all sides
  • other factors such as weather involving wind (and wind direction), intermittent rain or snow, etc.

A Comparison of the Effectiveness of Basic Building Dry-Out Procedures

We have inspected numerous buildings after flooding or severe plumbing leaks, and we have examined and tested the results of various building dry-out, "de watering", or "water extraction" methods used by contractors. Observations:

Even when drywall is measured (using a moisture meter) as "dry", we have pulled off wall baseboard trim to find visible water and soaking conditions in such locations. Readers who need to know how to properly respond to flooded buildings should see our series of articles beginning at FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP and also FLOOD RESPONSE CHECKLIST.

  • Simply operating a dehumidifier and/or fans will not remove moisture from wet building cavities fast enough to avoid a risk of hidden mold contamination.
  • Making small 2" diameter openings along the bottom of a wall, or even along the bottom and top of a wall between each wall stud pair in order to try to speed wall cavity dryout has proven ineffective and has resulted in severe mold contamination in some locations.
  • Strip cuts at the entire length of the bottom of walls in a room that has been flooded, removing the bottom 12" of drywall or plasterboard is often sufficient to dry out cavities that were not flooded to higher levels, but check for wet materials such as wet insulation at higher levels in the wall cavity and extend the strip cut higher as necessary.
  • Complete wall covering demolition indoors is often needed on at least one side of the wall to rapidly dry cavities that were wet from above, such as during a fire extinguishment, an upper floor plumbing leak, or severe building flooding. Similar approaches may be used for wet ceilings.
  • Wet carpeting needs to be removed and disposed-of;
  • Wet finish flooring that has buckled or moved will probably have to be demolished. Often it is possible to allow subflooring to remain in place if it is not water-damaged. See TRAPPED MOLD BETWEEN WOOD SURFACES for details.
  • Wet building insulation needs to be removed and disposed-of, not re-used.

Six Topics to Sort Out Building Leaks, Water Entry Cause, Cure, and Prevention

A series of detailed articles addressing these categories are listed below. Contact Us to suggest changes and additions to this material.

  • Present building condition: how wet or dry is the building, what building surfaces or cavities have become wet, what steps have already been taken or need to be taken to dry out the building. See WATER ENTRY in BUILDINGS for a discussion of sources of building leaks, moisture, and moisture related problems other than actual building flooding.
  • Building water entry damage control: what emergency steps should we take to minimize damage to a building that has suddenly been wet by leaks or flooding? (If your home has been flooded see FLOODS IN BUILDINGS-priorities first)
  • Building water entry history: Identify evidence of the leak, water entry, moisture, or flood history at the building.
  • Building water entry causes: identify building or site conditions likely to cause leaks, moisture, basement or crawl space water entry, or actual flooding at the building. Often on older buildings there has been a history of water entry and there may be multiple sources of water entry, confusing insurance claims as well as proper building repair procedures.
  • Building Leaks & water entry cures: what should we do, in what priority order, to stop recurrent water and moisture problems at a building?
  • Building water entry and flood damage prevention: what should we do at any building to prevent future leaks, condensation, water entry, or actual flooding at a building

Evidence of Prior Building Water Entry & Flooding

Flood lines in a crawl area (C) Daniel Friedman

This home inspection client was not happy to learn that the home she had recently purchased had been the subject of recurrent basement and crawl space flooding.

Flood lines in a building indicate the depth of water entry. Careful observation of water and mud stains can also indicate the number of significant floods that have occurred as well as possibly their frequency.

Even after a post-flood cleanup it is usually the case that clues of a building's history of leaks and water entry can be found.

See FLOOD Damage Assessment & Repairs.

Links to Key Articles on Diagnosing & Curing Moisture and Water Problems in Buildings

Clogged footing drain (C) Daniel Friedman

Photo of a mud-clogged footing drain

Our client saved this partly-clogged footing drain that was excavated from around their nearly-new but very wet home to show how quickly soils can enter and block drainage at a property if the system was not properly installed.

Scroll down to see our links to building water-entry related articles on the detection, diagnosis, cure, and prevention of building water damage and water related problems such as rot and mold.

Key building water entry diagnosis and cure articles:

Share this Article      

...

Technical Reviewers & References

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

STRUCTURAL INSPECTIONS & DEFECTS
BASEMENT WATERPROOFING
BATHROOM VENTILATION
BLOWER DOORS & AIR INFILTRATION
BRICK LINED WALLS
BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE
CATHEDRAL CEILING INSULATION
CHIMNEY INSPECTION DIAGNOSIS & REPAIR
COMBUSTION AIR for TIGHT BUILDINGS
CRAWL SPACES
  Crawl Space Dryout Procedures
  CRAWL SPACE GROUND COVERS
  Crawl Space Safety Advice
  Crawlspace Mold Advice
  MOLD CLEANUP by MEDIA BLASTING
  Mold on Dirt Floors
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE
ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR
ENERGY SAVINGS in BUILDINGS
ENVIRONMENTAL HAZARDS
FIBERGLASS INSULATION
FIBERGLASS HAZARDS
FIBERGLASS MOLD
FIREPLACE Damage & Unsafe Hearths - Settlement
FLAT ROOF MOISTURE & CONDENSATION
FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP
  FIRST PRIORITIES
  BUILDING ENTRY PROCEDURE
  DRINKING WATER - EMERGENCY PURIFICATION
  DRINKING WATER - EMERGENCY SOURCES
  ELECTRICAL SAFETY for Flood Damage Inspectors
  FLOOD DAMAGE TO FOUNDATIONS
  FLOOD DAMAGE TO FOUNDATIONS
  FLOOD RESPONSE CHECKLIST
  GENERAL MOLD PREVENTION
  SEPTIC SYSTEMS & FLOODS
  SEWAGE CONTAMINATION IN BUILDINGS
FLOODS IN BUILDINGS-mold
FLOORING CHOICES OVER CONCRETE SLABS
FLOORING TYPES & DEFECTS
FOUNDATION WATERPROOFING
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FREEZE-PROOF A BUILDING
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
Heat Tapes: Use on Roofs for Ice
HEATING COST SAVINGS METHODS
HOUSEWRAP AIR & VAPOR BARRIERS
HUMIDITY LEVEL TARGET
ICE DAM PREVENTION
Ice Dams: Comparing Two Houses
INSULATION CHOICES
INSULATION FACT SHEET- DOE
INSULATION for GREENHOUSE or SOLARIUM
INSULATION IDENTIFICATION GUIDE
INSULATION LOCATION in BUILDINGS - WHERE TO INSULATE
  INSULATION CHOICES
  INSULATION FACT SHEET- DOE
  INSULATION LOCATION & QUANTITY for ATTICS
  INSULATION LOCATION for BASEMENT FLOORS
  INSULATION LOCATION for BASEMENT WALLS
  INSULATION LOCATION for BRICK VENEER WALLS
  INSULATION LOCATION for CAPES, CRAWLSPACES
  INSULATION LOCATION for CATHEDRAL CEILINGS
  INSULATION LOCATION for GREENHOUSE or SOLARIUM
  INSULATION LOCATION for PASSIVE SOLAR FLOOR SLAB
  INSULATION LOCATION for SOUND CONTROL in BUILDINGS
  INSULATION LOCATION for SWIMMING, INDOOR
INSULATION MOLD
INSULATION R-Values & Properties
INSULATION INSPECTION & IMPROVEMENT
LOG HOME GUIDE
MOBILE HOME INSPECTIONS
MOISTURE CONTROL in BUILDINGS
Mold Growth Resistance of Foam Insulation
MOLD INFORMATION CENTER
NOISE / SOUND DIAGNOSIS & CURE
ODORS & SMELLS DIAGNOSIS & CURE
PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
PLASTER & BEAVERBOARD & DRYWALL
PASCAL CALCULATIONS
RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
ROOF VENTILATION SPECIFICATIONS
ROT, FUNGUS, TERMITES
  TERMITE SHIELDS vs TERMITICIDE
ROT, TIMBER FRAME
SAFETY HAZARDS & INSPECTIONS
SEARS KIT HOUSES
SOLAR ENERGY SYSTEMS
  PASSIVE SOLAR DESIGN METHOD
  PASSIVE SOLAR ENERGY MONITORING
  PASSIVE SOLAR FLOOR TILES, PHASE CHANGE
  PASSIVE SOLAR HEAT PERFORMANCE
  PASSIVE SOLAR HOME, LOW COST
  PHOTOVOLTAIC POWER SYSTEMS
  SLAB INSULATION, PASSIVE SOLAR
  SOLAR COLLECTOR AIR or GAS COLLECTION
  SOLAR COLLECTOR EFFICIENCY COMPARISONS
  SOLAR COLLECTOR FILMS
  SOLAR COLLECTOR WOOD HOUSINGS
  SOLAR HEATING SYSTEMS
  SOLAR HOT WATER HEATERS
  SOLAR HOUSE EVALUATION
  SOLAR SHADES & SUNSCREENS
  SUNGAIN, FILMS, LOW-E GLASS
  SWIMMING POOL SOLAR HEAT, INDOOR
  SWIMMING POOL SOLAR HEAT, OUTDOOR DIAGNOSIS
SOUND CONTROL in BUILDINGS
STAIN DIAGNOSIS
STAIRS, RAILINGS, LANDINGS, RAMPS
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
STRUCTURAL INSPECTIONS & DEFECTS
SUMP PUMPS GUIDE
THERMAL EXPANSION of MATERIALS
THERMAL MASS in BUILDINGS
  THERMAL MASS FLOOR SLABS
  THERMAL MASS in UPSTAIRS
  THERMAL MASS WALL DESIGN
THERMAL TRACKING Indicates Heat Loss
VAPOR BARRIERS
VENTILATION in BUILDINGS
WATER ENTRY in BUILDINGS
  ATTIC LEAKS Moisture or Mold
  BASEMENT HEAT LOSS
  BASEMENT LEAKS Moisture or Mold
  BASEMENT WATERPROOFING
    BASEMENT DE-WATERING SYSTEMS
    EXTERIOR WATER SOURCE ELIMINATION
    FOUNDATION DRAINS & FRENCH DRAINS
    FOUNDATION WATERPROOFING
    GEOTEXTILES & DRAINAGE MATS
    SEALERS, Basement Floor & Wall Moisture
    SITE DRAINAGE
    SUMP PUMPS GUIDE
    WINDOW LEAKS INTO BASEMENT
  Chimney Leaks
  CRAWL SPACE Dryout Procedures
  DEW POINT CALCULATION for WALLS
  DEW POINT TABLE - CONDENSATION POINT GUIDE
  EFFLORESCENCE, Salts & White / Brown Deposits
  FLOOD Damage Assessment & Repairs
  FLOOD DAMAGED FOUNDATIONS
  FLOOD VENTS & FLOOD PORTS
  FLOODS IN BUILDINGS-priorities
  FOUNDATION WATERPROOFING
  HUMIDITY CONTROL & TARGETS INDOORS
  HOUSEWRAP AIR & VAPOR BARRIERS
  LOG HOME Leak Diagnosis & Cure
  LOG HOME Condensation &Moisture
  MOISTURE CALCULATIONS
  MOISTURE PROBLEMS: CAUSE & CURE
  MOLD in BUILDINGS
  SEWAGE CONTAMINATION
  SUMP PUMPS GUIDE
  WATER ENTRY in BUILDINGS
WIND TURBINES
WINDOWS & DOORS
  SKYLIGHT LEAK DIAGNOSIS & REPAIR
  SITE BUILT DOUBLE GLAZED WINDOWS
  SLOPED GLAZING DETAILS
  SUNGAIN, FILMS, LOW-E GLASS
  VERTICAL GLAZING DETAILS
  WINDOW / DOOR ENERGY EFFICIENT, DOE
  WINDOW LEAKS INTO BASEMENT
WINTERIZE A BUILDING

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building design, inspection, and repair, and about indoor environment testing, diagnosis, and cleanup are at the InspectAPedia Bookstore.
  • ...
...

More Information

InspectAPedia® Home & Site Map
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Links to more information on inspection, diagnosis, and repair of defects in foundations and structures
goto InspectAPedia.com - authoritative, in-depth Building Diagnostic and Repair Information for building buyers, owners, inspectorsInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

03/07/2010 - 07/13/1999 - InspectApedia.com/structure/Water_Entry.htm - © 2010 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark