InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS

AIR DISCHARGE at FAUCETS, FIXTURES
AIR INLET VALVE, WATER TANK
AIR VOLUME CONTROLS, WATER TANK

BIOLOGICAL POLLUTANTS
Bisphenol-A, BPA

CHEMICAL CONTAMINANTS in WATER
CHECK VALVES
CHLORAMINE / CHLORINE Tests
CHLORINE IN DRINKING WATER
CHLORINE in WATER, HOW TO TEST FOR

CISTERNS

DEBRIS in WATER SUPPLY, Water Heater
DRINKING WATER TESTING

DRINKING WATER - EMERGENCY PURIFICATION
DRINKING WATER - EMERGENCY SOURCES

EPA GUIDE to WATER QUALITY

FHA WATER TESTS REQUIRED

FILTERS, WATER
FLOW CONTROL VALVES
FOOT VALVES, WELL PIPING

GALVANIC SCALE & METAL CORROSION
GREYWATER SYSTEMS

HARD WATER - SOFTENERS
HEAT TAPE USAGE GUIDE

LEAD POISONING HAZARDS GUIDE
Legionella Legionnaires' Disease

METHANE GAS SOURCES
MVOCs & MOLDY MUSTY ODORS
MSDS Material Safety Data Sheets
MUNICIPAL WATER PRESSURE IMPROVEMENTS

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS IN WATER
OZONE HAZARDS

Pesticide Exposure Hazards

PIPING IN BUILDINGS, Clogs Leaks Types
PLASTIC CONTAINERS, TANKS, TYPES
PLUMBING SYSTEM ODORS
PRESSURE CONTROL SWITCH ADJUSTMENT

RADON HAZARD TESTS & MITIGATION

RELIEF VALVES - Water Tanks

REVERSE OSMOSIS CONCENTRATE DISPOSAL

SEWAGE PATHOGENS in SEPTIC SLUDGE
SEWER GAS ODORS

TANK TYPES: WATER, OIL, EXPANSION, ALL

VALVES, PLUMBING

WATER CONTAMINANT LEVELS
WATER FILTERS
WATER HAMMER NOISE DIAGNOSE & CURE

WATER HEATERS

WATER ODORS, CAUSE CURE

WATER PRESSURE & FLOW MEASUREMENT
WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE REPAIR GUIDE - WELLS

WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS
WATER PUMPS, TANKS, WELLS - BASICS

WATER PUMP CAPACITIES TYPES RATES GPM
WATER PUMP CONTROLS & SWITCHES
WATER PUMP PRESSURE CONTROL SWITCH
WATER PUMP TYPES & LIFE EXPECTANCY
WATER PUMP PRIMING PROCEDURE
WATER PUMP PROBLEM DIAGNOSTIC TABLE

WATER PUMP REPAIR GUIDE
WATER PUMP SHORT CYCLING
WATER PUMP WONT STOP RUNNING

WATER PURIFIERS

WATER QUALITY TESTS, CONTAMINANTS, TREATMENT
WATER QUANTITY IMPROVEMENT

WATER SHUTOFF VALVE LOCATION, USE
WATER SHUTOFF VALVE, WELL PUMP

WATER SOFTENERS & CONDITIONERS
WATER SOURCE ALTERNATIVES

WATER TANK: USES, TROUBLESHOOTING
WATER TANK AIR, HOW TO ADD
WATER TANK AIR INLET VALVE
WATER TANK AIR LOSS SIGNS
WATER TANK AIR VALVE REPAIRS
WATER TANK AIR VOLUME CONTROLS
WATER TANK BLADDERS & CAPTIVE AIR
WATER TANK CAPTIVE AIR vs TRADITIONAL WellMate

WATER TANK CONTROLS & SWITCHES
WATER TANK LIFE EXPECTANCY

WATER TANK PRESSURE CALCULATIONS
WATER TANK PRESSURE GAUGE
WATER TANK PRESSURE RELIEF VALVE

WATER TANK REPAIRS
WATER TANK REPLACEMENT

WATER TANK SAFETY
WATER TANK SIZE & VOLUME

WATER TANK TYPES: WATER, OIL, EXPANSION, ALL

WATER TESTS, CONTAMINANTS, TREATMENT
WATER TEST CHOICES & WATER TEST FEES
WATER TESTING GUIDE
WATER TEST INTERPRETATION

WATER TREATMENT EQUIPMENT CHOICES

WELL PUMP PRIMING PROCEDURE

WELLS CISTERNS & SPRINGS

WINTERIZE A BUILDING

More Information

How to Diagnose & Repair Loss of Water Pressure from Municipal or Well Water Supply
InspectAPedia®  -    

  • How to Diagnose and Fix Bad Total Loss of Water Pressure, Water Pressure Repair Guide - What causes loss of water pressure?
  • Loss of municipal water pressure or flow - diagnostic guide
  • Loss of well water pressure or flow - diagnostic steps
  • How to diagnose loss of water pressure or loss of water in a building
  • Questions & answers about troubleshooting total loss of water pressure in buildings

This article describes how to diagnose the total loss of water pressure and the need for water control, tank, piping, water supply main pipe & valve, or water well repairs. The process of diagnosis and the costs of the repair are explained.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

Consumer advice on saving money on well repair costs is given here and includes a review of the parts and labor costs of a typical well pump and pressure tank replacement case.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

No Water? Diagnosis of Loss of Water Pressure which Does Not Recover on its Own

Here we give basic diagnosis for cases where you lose water pressure and it does not recover. Water flow in the building simply stops dead. By contrast with these "no water at all" causes, if water pressure in the building gets very low or stops but later recovers, you have an intermittent or other water system problem and you should see How to Diagnose Loss of Water Pressure which later Returns or Recovers "on its own".

Guide to Repair of Lost Water Pressure for Homes Supplied by Municipal or Community Water

  1. Is the Main Water Valve on? Has someone shut off the main water valve? Has someone been messing with the water pressure regulator? This is an adjustable water pressure which is often (not always) present on the piping at a municipal water supply pipe entry point ?
  2. Has water been shut off in the neighborhood: is water off in your neighborhood. Sometimes work on the water mains leads to a shut down of all water in an area. Check with your neighbors and your water department.
  3. Is there a burst pipe? A pipe may be burst somewhere you don't see such as in a wall, crawl space, basement, or even outdoors. Listen at your water pipes for the sound of running water.
  4. Is there a frozen pipe? In freezing climates, even in a heated building a pipe might run through a cold location where freezing can stop water supply entirely or in a part of the building.
  5. Is there water pressure but the pressure and/or flow are poor?
    1. See WATER PRESSURE REDUCER / REGULATOR
    2. See Bad water pressure Clogged Pipes & Water pipe clog repair guide
    3. See if a water filter is installed and check to see if it has become clogged. See WATER FILTERS.
  6. See our detailed water pressure diagnostic list at: WATER PRESSURE LOSS DIAGNOSIS & REPAIR

Guide to Repair of Lost Water Pressure for Homes Supplied by a Well

If the building water supply stops and takes minutes to hours to recover, you may have problem with the well flow rate. But the problem of lost water supply and pressure could be more mechanical: a bad well pump. The well pump, in turn, could have been damaged or hastened to the end of its life by a bad water pressure tank which has caused well pump short-cycling. Short cycling of the pump motor can burn up the pump relay control.

Readers of this document should also see Water pressure tanks - how to diagnose the need for air, how to add air, stop water pump short cycling to avoid damage - water storage water pressure tank safety

  1. First Check the Pump and Well Basics:
    1. Is electrical power on at the pump: is power on for the water pump? Is the water pump running at all? Did lightning hit your pump or well?
    2. Is the water main turned off: Has someone shut off the main water valve?
    3. Is there a burst pipe? A pipe may be burst somewhere you don't see such as in a wall, crawl space, basement, or even outdoors. Listen at your water pipes for the sound of running water.
    4. Is there a frozen pipe? In freezing climates, even in a heated building a pipe might run through a cold location where freezing can stop water supply entirely or in a part of the building.
    5. See our detailed diagnostic list at: WATER PRESSURE LOSS DIAGNOSIS & REPAIR
  2. Well or water supply piping leaks: If inside the well there is a leaky or broken water line rising from the well pump, the pump could run but deliver less or no water to the building. If this defect is present, the system will not recover to normal operation on its own. For example, if a well piping connection in the well becomes totally disconnected or the pipe bursts this condition occurs.
  3. Water pump failure or damage: If the well pump keeps running and you have no water it is also possible that the pump itself is defective, such as having broken internal parts so that the motor runs but the pump does not move water. But if the impeller blades in the pump are broken, the system would never recover. You'd have either no water or only very low pump output no matter what conditions in the well.
  4. If the water pump keeps running and you have no water it is also possible that you have a problem with the well or well piping or foot valve in the well -- maybe. See contrasting cases after this list. Turn off the water pump so that you don't burn out the motor. Some water pumps depend on having water inside the pumping mechanism to avoid wear or overheating.

    Lost prime: Your well pump might have lost its prime - if the the well pump is not actually down inside the well, it probably needs water inside the well casing to start things going. See WELL PUMP PRIMING PROCEDURE.

    A shallow well jet pump well line could have a bad foot valve (in the well) and so be losing prime. A leak in the well line can also lead to loss of prime. See Repeated Loss of Pump Prime for a discussion of well piping foot valves.
  5. If the well pump keeps running and won't turn off, but you do have water pressure in the home, possibly reduced water pressure, there could be several causes, but ultimately it means that either the pressure switch is not turning off the pump when it should, or the pump is not able to pump water pressure up to its cut-out setting.

    A well pump pressure switch failure can also cause the water pump to fail to turn off - say if someone has adjusted that control to ask the pump for higher pressure than it can achieve. If no one has adjusted the pressure control switch, it could still be a problem if its pressure sensor is clogged with debris or if another problem is keeping it from turning off. See step 6 below.

    Well flow deteriorated: This symptom may also occur if the well flow rate has deteriorated - that is, water is running from the ground into your well more slowly than your pump pumps it out. You might see this especially if you have just installed a new, more powerful well pump on an older well that previously seemed just fine. Or it may occur in dry weather or for other reasons such as nearby blasting that has changed the ground water level. See WATER PRESSURE LOSS DIAGNOSIS & REPAIR

    Well piping leak: This symptom may also occur if there is a leak in well piping between well and building - the well pump in the well may be working fine but not all of the water is reaching the building because it's leaking into the earth or back into the well. See WATER PRESSURE LOSS DIAGNOSIS & REPAIR and see See Repeated Loss of Pump Prime for a discussion of well piping foot valves.

    Well pump damage: the well pump may be damaged itself, a broken impeller or an air leak - preventing it from reaching full pressure. See WATER PRESSURE LOSS DIAGNOSIS & REPAIR
  6. If the water pump has shut itself off and the pump motor does not restart, the well pump may have tripped an internal or external overload switch, circuit breaker, or fuse.

    Check the fuse or circuit breakers supplying power to the water pump.

    Check the pump motor reset button: If the pump motor is accessible look on the motor for a red or yellow reset button that may have popped "up" indicating that the motor's overload protection circuit has activated.
    When the pump motor cools you may be able to reset this button and the pump may run and deliver water but further diagnosis is needed as this problem will recur.

    Check that the pressure control switch is trying to turn on the pump - see the next step below.

    Check the pump wiring and starter capacitor. See Jet Pump Troubleshooting Guide for more tips for a well pump that won't start.

  7. Problems with the well pump water pressure control switch: such as sticking "on" or "off" or working irregularly may be diagnosed by these articles:
    • How to Adjust Water Pump Pressure: The detailed, step by step procedure for inspecting and adjusting the water pressure control switch is discussed in detail at ADJUST PUMP PRESSURE CONTROL.
    • Diagnosing Water Pump Short Cycling on and off: If your water pump is clicking on and off too often or quite rapidly see SHORT CYCLING.
    • Diagnosing Water Pressure Drops without explanation when the pump stops, see Water Pressure Falls Slowly, Erratic Pumping: bad pressure control switch, building water running or leak, bad pressure gauge, bad check valve, bad foot valve.
    • Diagnosing & Repairing Lost Air in the Water Tank: The problem of lost air in the water pressure tank along with how to correct that condition are discussed beginning at SIGNS OF AIR LOSS.
    • Diagnosing & Repairing a Water Pressure Control or Water Pump Control Switch: We discuss diagnosing and repairing a water pressure control switch that sticks "on" or "off" or simply won't operate, at water pump Pressure Switch Repairs.
  8. If the pump is inside the well you can't see these conditions directly but an electrician or plumber can do some diagnosis from the building by noting the amperage draw on the pump circuit.
  9. Problems with well casing or well flow and recovery - loss of ground water and many other causes of loss of water are discussed at our comprehensive article: WATER PRESSURE LOSS DIAGNOSIS & REPAIR
  10. Problems with water treatment equipment can cause loss of water pressure or no water flow: a completely clogged water filter, or a malfunction in water disinfection or other water treatment equipment can cause a reduction in water pressure or a complete stop in water flow in a building. For example a UV -ULTRAVIOLET LIGHT TREATMENT system may include an automatic shut-off valve (a "normally closed solenoid") that turns off water flow in the building if the UV bulb burns out or falls too low in intensity. Also see WATER FILTERS for details about clogged filters, and see WATER TREATMENT EQUIPMENT CHOICES for our complete list of types of water treatment equipment.
  11. Is there water pressure but the pressure and/or flow are poor?
    1. See WATER PRESSURE REDUCER / REGULATOR
    2. See Bad water pressure Clogged Pipes & Water pipe clog repair guide
    3. See WATER FILTERS if you have a water filter installed
  12. If water pressure is intermittent or varies in flow rate, see Water Pressure Intermittent
  13. See our detailed water pressure diagnostic list at: WATER PRESSURE LOSS DIAGNOSIS & REPAIR

Readers of this document should also see Water pressure tanks - how to diagnose the need for air, how to add air, stop water pump short cycling to avoid damage - water storage water pressure tank safety.

Frequently Asked Questions about fixing complete loss of water pressure at a building

Question: after fixing a plumbing leak water pressure was intermittent, now there is no pressure at all

My tank has a bladder. I had a leak and replaced the pipes with copper on the inside of my house . 2 Weeks ago after the leak was fixed I had an air bubble in the line where water would suddenly stop for a second and then come back on and then there was water underneath the water tank. Now I do get water but no pressure it is reading 20 lbs of pressure. I have no pressure plz help - Peggy

Reply:

Peggy I'm not quite clear on your question nor the relation between your mentioning the bladder tank (water pressure tank with an internal bladder) and air bubble in the line, and water under the water tank. Here are some comments that might help sort this out:

If you have no water pressure in the house but see 20 psi at your pressure gauge - you could have a bad or stuck water pressure gauge. Try tapping gently on the gauge or replace it. Gently GENTLY rock the water tank - if it is empty it will move easily (don't wiggle it around and start a water leak).

If the water pressure tank is empty then your pump or pump control are not sending water to the tank, or a well line is disconnected, or the well was running dry.

Sometimes we get air in water lines when the pump is drawing down the water level in the well so fast (the well recovery rate is so poor) that the pump picks up some air.

Question: our well pump acted up and now quit completely

Hi, our water pump has been acting up recently. And today around 10 o' clock it completely stopped pumping any water into our house. But we don't know what the problem is. - Jimmy

Reply:

Jimmy if our list of things to check first to figure out why you've got no water pressure are not clear, ask me as specific a question as you can and I'll try to help. If none of that information makes sense to you or doesn't help, it looks as if you want to call a plumber promptly. Try reviewing the water pressure loss diagnostic steps summarized in our WATER PRESSURE PROBLEM DIAGNOSIS TABLE. .

Question: water pressure stops completely, then returns six hours later

I have very low pressure in the house and all outside faucets. I checked the pressure gauge and it is at 0. I checked the top of the pressure tank and air came out. I can also hear water running through the pipes. Any ideas? - Adam

strangely enough pressure returned about 6 hours after we lost it. Now the gauge shows shows pressure at 50 and if I run water it slowly drops down to 30 before kicking back on. Seems to take about 5 minutes.

Reply: how to check and then improve well yield

Adam the behavior you describe is often what we see when a well flow rate has fallen to be very poor. It sounds as if the well yield has failed; it is possible to restore yield without drilling a new well if your plumber confirms that this is the problem.

See How Much Water is In the Well? and see How to Get More Water From a Well

Question: what happens if we set the well pump pressure control switch to a level higher than the pump can reach?

"A well pump pressure switch failure can also cause the water pump to fail to turn off - say if someone has adjusted that control to ask the pump for higher pressure than it can achieve." What should you do if someone has been adjusting the control & caused this problem? Is there a way to un-do what they have done? - Jess

Reply:

Certainly, Jess. If the pump cannot reach the pressure setting the problem could be the limits of the pump capacity itself, or the well yield may have deteriorated. See WATER PUMP WONT STOP RUNNING.

Adjust the pump pressure control switch to drop the cut-off pressure down until it is at a pressure the pump can achieve (and thus will turn off). Then set the cut out just a few psi below that point to be safe. See PRESSURE CONTROL SWITCH ADJUSTMENT.

Question: we lost all water pressure after a power outage, even when electricity was restored

Hi,after a power outage that lasted the entire day, I now have no water at all. I'm new to all of this, so please bear with me. Although, thanks to your very informative site I'm learning. I have a single line jet pump and am not sure what the depth of the well is. I tried to reprime with no success, so had a well person check it out. He spent over an hour adding water, turning the pump on and off, gradually bringing the water and pressure back up to the top.

Right as he was ready to give up it worked, and water was flowing strong out of the faucet. It didn't last long though, and he said there must be a crack or hole in the piping of the well, which is letting air in. What I don't understand is I had water before the pwr outage with a supposed cracked or damaged pipe. So since he got the water back up to the top and flowing, why wouldn't it continue and keep the prime since it was before?

He advised that since the well is older (25 years) and the cost to find out what is wrong with it would be $1500 plus the cost of repair, that I would be better off having a new well dug, which is $3800.

I looked into claiming it on my insurance, but was told it had to be caused from a lightning strike, not just a pwr outage. Is it a possibility that whatever is wrong could have been caused by lightning, and if so, how could it be confirmed? - Valora

Reply:

Valora:

if a well has taken a lightning strike that caused damage usually there would be visual evidence such as burning or melted components.

But in your case the one line jet pump is in the house not in the well; a lightning strike at the well casing might still affect the pump IF the piping between well and house is metal. Or if lightning struck the home electrical system or power lines causing a surge.

But in those cases if the pump was damaged I'd expect it not to run.

I suggest that if you haven't done so, see if the well is HOLDING prime after it has cycled off; if water is leaking back down into the well, the piping or a foot valve or other check valve may be what needs replacement - hardly a reason to drill a new well.

Watch out: I would not go for drilling a new well before we have an accurate diagnosis of the problem. It would be maddening to pay thousands of dollars for a new well only to find that the original problem was a bad electrical connection in the original equipment.

Question: lost water pressure; why is the pump relay switch tripping off?

I cam home from work and the water tank appeared to be full. Much to our surprise water suddenly stopped flowing. I hit the reset on the pump relay and also hit the manual override on the pressure switch.
Pump started back up but on its way to filling the tank I heard the pump relay switch trip again.

Any idea on what would be tripping the pump relay switch?

Reply:

Jeff,

Your pump will shut off if the pressure switch is working properly and it senses that pressure has reached the "cut out" pressure (typically 40 or 50 psi). If the water tank is water logged (lost its air charge) then that happens very quickly.

A full water tank means it's lost its air charge. Take a look at WATER TANK AIR, HOW TO ADD.

Question: intermittent loss of water pressure - pump goes off, then comes back on

OK, So I have been having some serious difficulties with my water.....A few days ago the water just went out....maybe a small trickle of water out of all faucets....a couple hours later, everything was fine, without me touching a thing. It lasted for about 10 mins, then went out again. The gauge reads right around 60 PSI non stop, hasn't dropped below 55 PSI that I have seen, but still, no pressure in the house our hose connection that is after the pressure adjustments, and before the tank. I replaced the control box and it worked for another 20 mins, then just died, and I can see the capacitor kickin out a dark goo. I have been all over the net trying to isolate the problem to save myself a few grand, but I keep seeing sooooo many different things people say could be wrong, and I just don't know where to start.....can anyone help?!?! - Larry

Reply:

Larry, your well pump may be turning itself off due to overheating; some pumps, particularly submersible units, include an internal thermal overload switch. If the pump motor overheats the relay turns off the pump to avoid more costly damage. When the motor cools down the relay resets itself on its own .

If this is what's happening, you will want a diagnosis of the cause.

  • A failing pump assembly or motor
  • Loss of water flow into the well itself - pump running dry
  • Something else

Question: After moving the water tank we can't get any water into our cabin

We moved our fresh water tank at the cabin from our driveway above the cabin to under the cabin. The pump has always been located under the cabin. Now the tank sits a few feet below pump level and we cannot get water to the cabin. The tank water level is slightly below the pump. - Pat

Reply:

Pat, I don't have a clear picture of where all of your equipment, controls, and pressure sensing switch are located. But I agree that if a problem shows up after moving equipment, I'd start diagnosing the problem by a review of exactly what was changed. With so little information on your setup I have to suggest you start with a look at our water pressure problem diagnostics at WATER PRESSURE LOSS DIAGNOSIS & REPAIR or at the summary found at WATER PRESSURE PROBLEM DIAGNOSIS TABLE

 

Questions & Answers regarding this article

Questions & answers about troubleshooting total loss of water pressure in buildings.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

These pages are chapters of our comprehensive article: WATER PRESSURE LOSS DIAGNOSIS & REPAIR

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

WATER PRESSURE GAUGES
WATER PRESSURE GAUGE ACCURACY

WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE PROBLEM DIAGNOSIS TABLE
  Making the "right" repair
  MUNICIPAL WATER PRESSURE DIAGNOSIS
  MUNICIPAL WATER PRESSURE IMPROVEMENTS
  WELL WATER PRESSURE DIAGNOSIS
  AIR DISCHARGE at FAUCETS, FIXTURES
  No Water Pressure
  Shaking the Water Tank?
  Water pipe clog diagnosis
  Water pipe clog repair guide
  Water Pressure Bad at Some Fixtures
  Water Pressure Falls Slowly, Erratic Pumping
  Water Pressure Intermittent
  Water Pressure Tank Problems
  Water Pressure Tank Diagnosis
  Water Pressure Later Returns "on its own"
  WATER PRESSURE BOOSTER PUMP
  WATER PRESSURE REDUCER / REGULATOR
  WATER PUMP PRESSURE CONTROL ADJUSTMENT
  Water Tank & Pump Costs
  WELL PIPING LEAK DIAGNOSIS
  Well Tank relation to Water Pressure

WATER PRESSURE REPAIR GUIDE - WELLS

Water Supply & Drain Piping, Wells, Pumps, Water Supply Equipment

  • Access Water Energy, PO Box 2061, Moorabbin, VIC 3189, Australia, Tel: 1300 797 758, email: sales@accesswater.com.au Moorabbin Office: Kingston Trade Centre, 100 Cochranes Rd, Moorabbin, VIC 3189
    Australian supplier of: Greywater systems, Solar power to grid packages, Edwards solar systems, Vulcan compact solar systems, water & solar system pumps & controls, and a wide rage of above ground & under ground water storage tanks: concrete, steel, plastic, modular, and bladder storage tanks.
  • Cheating on water tests: Testing Water for Real Estate Transactions - make sure your water test is valid
  • Diagnosing Clogged Drains: Is it a blocked drain or the septic system? - A First Step for Homeowners
  • Drinking Water Contaminant Levels - Maximum Allowed
  • Drinking Water Supply, Contamination Levels, Water Testing Procedures
  • Drinking Water Testing Advice for home buyers home owners home inspectors
  • Interpreting Drinking Water Test Results and Correcting Unsatisfactory Water
  • Lead Contamination in Drinking Water: Testing & Correction - Advice
  • Lead Testing & Correcting Contamination from Lead Water Supply Lines/Entry Mains - Lead Pipe Problems/Advice
  • Life Expectancy of Water Pumps - Well Pumps: how long should a water pump last? What affects pump life?
  • Life Expectancy of Wells & Water Tanks how long should a water well and its components last?
  • Plumbing Diagnosis & Repair: Water supply, drainage, septic systems, water testing, water contamination, defective plumbing materials & products.
  • Shock or Chlorinate a Well, How to - Procedure for Shocking a Well to (temporarily or maybe longer) "Correct" Bacterial Contamination
  • Smart Tank, Installation Instructions, Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
  • Typical Shallow Well One Line Jet Pump Installation, Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Typical Deep Well Two Line Jet Pump Installation, Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Water Fact Sheet #3, Using Low-Yielding Wells, Penn State College of Agricultural Sciences, Cooperative Extension, School of Forest Resources, web search 07/24/2010, original source: http://pubs.cas.psu.edu/FreePubs/pdfs/XH0002.pdf
  • Water pressure tanks - how to diagnose the need for air, how to add air, stop water pump short cycling to avoid damage - water storage water pressure tank safety.
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water pressure tank failures & water pump short cycling diagnosis and repair
  • Water Supply & Drain Piping, water and drain pipe types, inspection, diagnosis, repairs, problem materials, clogging, etc.
  • Water Tests & Fees this water test fee schedule applies when testing is combined with other onsite building inspection services
  • Water Testing: background comments on classes of water contaminants, & links to home buyer advice about water testing, drinking water, water supply
  • Water Requirements, Home & Outdoor Living

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
    • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop, and from the InspectAPedia bookstore. The 2010 edition of the Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Crystal Clear Supply provides portable ceramic water filter purifiers and portable reverse osmosis water treatment equipment - see http://www.crystalclearsupply.com/category_s/7.htm
  • Handbook of Disinfectants and Antiseptics, Joseph M. Ascenzi (Editor), CRC, 1995, ISBN-10: 0824795245 ISBN-13: 978-0824795245 "The evaluation of chemical germicides predates the golden age of microbiology..." -
    This well-focused, up-to-date reference details the current medical uses of antiseptics and disinfectants -- particularly in the control of hospital-acquired infections -- presenting methods for evaluating products to obtain regulatory approval and examining chemical, physical, and microbiological properties as well as the toxicology of the most widely used commercial chemicals.
  • Potable Aqua® emergency drinking water germicidal tablets are produced by the Wisconsin Pharmacal Co., Jackson WI 53037. 800-558-6614 pharmacalway.com
  • Principles and Practice of Disinfection, Preservation and Sterilization (Hardcover)
    by A. D. Russell (Editor), W. B. Hugo (Editor), G. A. J. Ayliffe (Editor), Blackwell Science, 2004. ISBN-10: 1405101997, ISBN-13: 978-1405101998.
    "This superb book is the best of its kind available and one that will undoubtedly be useful, if not essential, to workers in a variety of industries. Thirty-one distinguished specialists deal comprehensively with the subject matter indicated by the title ... The book is produced with care, is very readable with useful selected references at the end of each chapter and an excellent index. It is an essential source book for everyone interested in this field. For pharmacy undergraduates, it will complement the excellent text on pharmaceutical microbiology by two of the present editors."
    The Pharmaceutical Journal: "This is an excellent book. It deals comprehensively and authoritatively with its subject with contributions from 31 distinguished specialists. There is a great deal to interest all those involved in hospital infection ... This book is exceptionally well laid out. There are well chosen references for each chapter and an excellent index. It is highly recommended." The Journal of Hospital Infection.: "The editors and authors must be congratulated for this excellent treatise on nonantibiotic antimicrobial measures in hospitals and industry ... The publication is highly recommended to hospital and research personnel, especially to clinical microbiologists, infection-control and environmental-safety specialists, pharmacists, and dieticians."
    New England Journal of Medicine: City Hospital, Birmingham, UK. Covers the many methods of the elimination or prevention of microbial growth. Provides an historical overview, descriptions of the types of antimicrobial agents, factors affecting efficacy, evaluation methods, and types of resistance. Features sterilization methods, and more. Previous edition: c1999. DNLM: Sterilization--methods.
  • U.S. Army Field Manual 21-10, Field Hygiene and Sanitation, 1988, web search 07/02/2010, original source: http://www.enlisted.info/field-manuals/fm-21-10-field-hygiene-and-sanitation.shtml
    The purpose of this manual is to assist individual soldiers, unit commanders, leaders and field sanitation teams in preventing disease and environmental injuries. The manual provides information on preventive medicine measures (PMM) to the individual soldier as well as essential information for the unit commander, unit leaders, and the unit field sanitation team on applying unit level PMM.
  • When Technology Fails, Matthew Stein, Chelsea Green Publisher, 2008,493 pages. ISBN-10: 1933392452 ISBN-13: 978-1933392455, "... how to find and sterilize water in the face of utility failure, as well as practical information for dealing with water-quality issues even when the public tap water is still flowing". Mr. Stein's website is www.whentechfails.com/
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com