After the pump stops the water pressure falls a few psi, then stabilizes:
Questions & answers on the causes of a brief water pressure drop each time the water pump cycles off.
This article series describes how to diagnose slow water pressure loss and erratic well pump behavior.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions about diagnosing the cause of a slow but brief or "fixed quantity" fall-off in building water pressure when no water is being run (we think) were posted originally at WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP
If when the water pump shuts off the water pressure falls quickly to a lower level then stops falling, this article explains the possible causes of that aggravation.
Chun and Mac
Diagnostic question: How much does pressure fall? Could there be a toilet tank filling? Could there be a debris clogged, slow-to-respond pressure gauge?
0. Rule out water leaks or running toilets. I've seen this pressure drop at the end of a pump-on cycle too. When pressure remains steady afterwards we know it's not an actual water leak - no running toilet, no leaky foot valve. Or we think so
So what might be causing this brief pressure drop that occurs at every pump on-off cycle?
1. Air cushion in the system? I previously thought this was an artifact of the particular pump, piping arrangement, controls - and not something that I think needs fixing. It's probably nothing to do with the switch - more likely the tank and piping and an air cushion somewhere.
2. Pressure cushion in the system? A less-likely possible explanation is that pressure during pumping is, after the pump stops, converted to an expansion of plastic parts or a tank bladder component that absorbs a bit more of the system pressure.
3. Pinhole leak in water tank bladder? There is another possibility: a very small pinhole leak in the flexible rubber bladder in the pressure tank may open enough to pass a few psi worth of water at your cutoff pressure - say 50 psi - then as pressure drops even a little - to say 45 psi - the hole closes enough that any remaining leakage is so slow that you don't notice it.
You'll eventually find this problem - if a pinhole tank bladder leak is what's happening in your case - when over time the water pressure tank becomes waterlogged even though with an internal bladder that should not occur. It will show up as
4. Leaky check valve or foot valve? usually a leaky check valve or foot valve will cause pressure to fall continuously even if slowly after the pump turns off. But on occasion debris on a valve seat might leak water mostly at higher pressure, falling off to very slight or even zero leakage after pressure in the system has dropped.
See WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP and also see CHECK VALVE
A bad internal pump seal might water leak-back into the well piping system and into the well itself (depending on check valve locations) and it will almost always cause a reduced ability of the pump to reach cut-off pressure.
Favorite - 5. Debris-clogged pressure gauge or pump pressure switch? I think the most-common cause of this phenomenon is simply a lack of precision in the pump pressure control switch (or an effect of its location on the plumbing system) combined with the location of a pressure gauge (perhaps right on the pump housing).
Both pump pressure control switches and pressure gauges accept water pressure through a small opening in the body or base of those instruments.
I've found that when a switch or pressure gauge is partly-clogged with debris but before it fails entirely it will begin to respond slowly, or to show a delayed response to pressure changes. That's because it takes extra time for pressurized water to enter OR to leave the body of the gauge or switch.
That can cause a switch or gauge to be "behind" the actual pressure in the system
See our pressure control switch repair discussion wherein we discuss
Also see more discussion of this question at WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP
6. Pressure control or jet pump too distant from water pressure tank: water pressure control manufacturers and water pressure tank manufacturers generally instruct that the pressure control switch and pressure tank should be as close to one another as possible.
Gould Pumps suggests that the jet pump should be no more than 5 ft. from the pressure tank.
Here is what Amtrol™ says about tank & pressure control switch location:
The Well-X-Trol should be installed as close as possible to the pressure switch. This will reduce the adverse effects of added friction loss and pressure switch bouncing, and the difference in elevation between WELL-X-TROL and switch.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2021-05-24 - by (mod) -
@Anonymous,On 2021-05-19 by Frank Taylor
Sorry i sent a picture of my set up but forgot to but my name on it it is below under anonymous!!
On 2021-05-18 by Anonymous
I have this tank attached to a Rain catchment tank[s]. is being gravity fed by 2" hose. So do you think I need a foot valve on it?? I am a bit of a rookie in this science.
On 2021-05-18 - by (mod) -
@frank Taylor,On 2021-05-17 by frank Taylor
I have a jet pump with attached tank, if I start it up it goes to pressure shuts off then i can hear either water or air as it bleeds down fairly quickly, to bottom pressure setting and restarts about 20-30 seconds. pressure tank is aired to correct pressure and holds. Have changed the pressure switch, have took apart and cleaned everything, is it possible a shaft seal or something is leaking? i can't understand what is happening all my limited experience tells me it should be working.
On 2020-05-25 - by (mod) -
That could be a debris clogging problem. Try changing out the pressure control switch and be sure that the tube conducting pressure to the switch is not clogged.On 2020-05-25 by Jeff
Holding tank drops to 30psi and calls for water.. usually works fine but lately more often when it calls for water at 30psi .. hear a gurgle like it’s not getting water then psi drops to 0.. but I can flip the switch to auto to fill tank and it shuts off at its 50psi like normal. Any ideas what’s wrong? Is it the pump going?
On 2020-02-09 - by (mod) -
Sounds like a leaky check valve or foot valveOn 2020-02-09 by Chris
Pressure goes to 60, well turns off as it should, pressure drops immediately to 42, stays there even with faucet running for almost 4 minutes, then well kicks on goes to 60 happes all over again.. pressure in tank top 38, new pressure switch, new check valve, new gauge.
On 2019-03-28 - by (mod) -
Louise the cause and cure are probably one of those listed in the article above. Please go through those as that's our best information, then let me know what you found and we'll take it from there.On 2019-03-28 by Louise
My water (county water in a mobile home park) pressure drops off by about 50% after a few seconds, then remains low. What is the cause and cure?
On 2017-08-01 by Chun
this time is even more strange, last night when the pump stopped the pressure was dropping continuously (psi wasn't holding). I tried the cycle again and same thing happened. However, it got better the next morning (dropping slower) and eventually it was holding. What can cause the psi to drop one day and not the next? It's a new well and it's been showing up with sand and dirt. Can well sentiment be the cause? Or can it be the bladder tank. Can I add a check valve by the pressure tank to prevent this back flow?
On 2017-07-08 by Chun - pressure drops 5psi then it stays there everytime pump reaches cut off
Mac, same exact thing is happening to me, it drops about 5psi then it stays there everytime it reaches cut off, let me know if you have figured it out
On 2017-04-28 1 by Mac
The water pressure drops 5 psi every time it stops either at 50 or 60. If I set to 30/50, it stops at 50, then comes down to 45..at 40/60, it stops at 60, but comes down to 55... every time.
At first I thought there was a leak somewhere, but then I noticed the pressure will not keep going down.. i've left it for over 2 hrs and it will not continue to drop once it drops the 5 psi..so maybe there is no leak.
I have replaced the pressure switch and the gauge a couple of times with new ones and different models - same thing.
This have driven me crazy for a very long time and I can't figure it out.
Question: why does water tank pressure slowly fall down from 40 psi when the pump stops to a stable 35-36 psi?
(Oct 9, 2015) Bill said:
I have a question. My tank pumps up to 40 psi, but then it slowly "relaxes" to 35 or 36 psi and then stabilizes there. Why could this be?
There is little or no air or water leaking. I know this because the cycle time of the pump is very stable. This happens even when I have the output of the tank closed off, so it's not an effect of anything inside the house.
My first tank arrangement had the input at the top of the tank, pumping the water through the air and splashing into the water and creating bubbles in the water (I'm fairly sure) which might cause a slow air loss into the pipes in the house. I didn't see this relaxing effect then. The output was a few inches above the bottom of the tank.
I had to change the tank and since I was concerned about the air loss, I did it differently. Now the output is still a few inches above the bottom but the input is from the side about six inches above the output. This should be under water all the time I think so there should be no more bubbles to cause air loss.
What could be causing this pressure relaxing? Could the check valve be leaking backwards until the pressure reduces a bit?
Could there be cavitation causing water vapor bubbles that slowly reabsorb into the water and give the air room to expand? Any other ideas?
This question and reply were posted originally at BOYLE's LAW where we explain water tank pressures and volumes controlled by this law: P1V1 = P2V2 at constant temperature
Thanks for the interesting question. I've seen this discussed before without an authoritative scientific explanation.
At WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP I commented that I've originally figured this problem was an artifact of the particular pump, piping arrangement, controls - and not something that I think needs fixing. It's probably nothing to do with the switch - more likely the tank and piping and an air cushion somewhere.
There I give other possible explanations for the phenomenon you describe.
If there were a bad check valve or a running toilet, water pressure measured at the tank would
For cases in which the water pump pressure falls after the pump stops, but on every pump cycle the pressure drop stops at about the same point and after the same time interval, something else is going on.
More explanations of possible causes of this pressure drop are given in the top of this article.
(Nov 14, 2014) Tim2014 said:
Drilled Well 16yrs old. Previous owner said 400+ ft. I had a short cycle issue that was resolved by re-pressurizing the tank. Pump now works 40-60 as expected and tank is holding the expected air pressure.
I then noticed a slow leak of water pressure while I was correcting the short cycle. Symptom: Gauge at well shows about 62 when pump stops.
Then settles down to 59. I assume that much play in gauge is ok given it is a $6 part.
Water pressure then slowly drops at a slightly variable rate over hours. 15 lbs-9 hrs, 5 lbs-6 hrs, 7 lbs-6.5 hrs, etc... I can turn off the flow to the house at the well and the well and tank holds water pressure constant at 59 lbs for 6 hours.
That leaves me to believe that the drilled well itself (foot valve, piping, etc..) is ok. I don't see any signs of leakage in my home (no visible water, no toilet leak,etc..), but to make sure, I turn off the water as it enters the house and have similar drop rates in pressure as listed above.
That leaves me to believe I have a slow leak in the yard line between the well and the home. Does that sound right? Of course there is no visible evidence of a leak, and that line crosses the sewage, power, phone/internet and propane gas line before it enters the home as the builder was apparently not a good planner.
Question: My tank at the well is supposed to produce a 5 gal draw down at 40/60. So, if I let the well pump 60lbs then open the faucet at the well and let it run in a bucket until the pump kicks back on, I should expect to fill up a 5 gal bucket? So I did that after 6 hours and had about 2 gals in the bucket
So, I'm leaking 3 gals in 6 hours correct? I don't know much about this, but I assume if the water pressure drops that the water had to go somewhere even I can't find the leak.
I don't understand how air could leak into the system, but I've had several people and couple of articles on this site indicate that air might be leaking into the system. Any comments or suggestions?
Tim
At the start of WATER PRESSURE FALLS BRIEFLY THEN STOPS we list possible explanations for why a water pump keeps losing pressure at the end of the pump-on cycle, for the case in which the pressure loss seems to stop after just a few psi.
At WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP we describe a similar problem except that water pressure sometimes continues to drop until the pump turns on even though no water is being run in the building.
A slow leak of water out of the piping anywhere between well bottom and building water equipment can leak both water out and in some circumstances air in to the system. Usually we look first for a bad foot valve or check valve
At AIR DISCHARGE at FAUCETS, FIXTURES gives sources of air leaks into a water system: well piping leaks, snifter valves, etc. are discussed. One of those could cause the formation of unexpected "air cushions" or air bubbles in the water supply system.
On 2017-01-26 by Susan - Opened house water valve and lost 10 pounds of pressure.
Had a new well pump installed, now my pressure tank will lose pressure right after the pump turns off. I shut the water to the whole house off and kept the pump to tank valve open, Pressure maintained in tank.
Opened house water valve and lost 10 pounds of pressure. No house water running. Toilets are not running. Does this indicate we have some kind of leak in the house or could there be other reasons why we are losing pressure?
On 2017-01-26 by (mod) Reply: pressure tank will lose pressure right after the pump turns off.
If pressure continues to fall then look for a leaky check valve or foot valve in the well - see WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP
and see
If pressure falls a fairly consistent few psi and then stops, see our speculations at WATER PRESSURE FALLS BRIEFLY THEN STOPS
(Mar 28, 2013) janet said:
I have a double line jet pump system. The cut in is 30 and off is 50 on pressure switch.
The problem is as soon it shuts off, the pressure drops, takes about 20 minutes then cycles again. We installed a check flow valve at the pump, thinking water was flowing back down to well. That didn't solve it. What could be the problem?
(Apr 15, 2015) Anonymous said:
the pump pumps water but when shut off the pressure falls
Janet & Anonymous
It should be pretty easy to determine if the leak is in the building, at the pump and water tank, or in the well piping. If you shut off all water entering the building and pressure drops, the problem is not a leak in the building.
If your check valve is absolutely pefect, or if you use a temporary shutoff valve between the pressure tank and pump and the well itself, and pressure drops, there is a leak on the pump and tank side of that valve.
See WATER PUMP INTERMITTENT CYCLING
...
Continue reading at WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these common sources of slow dropping in water pressure and loss of well prime:
Or see these
WATER PRESSURE FALLS BRIEFLY THEN STOPS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers on intermittent loss of building water pressure: troubleshooting, causes, repairs. .
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.