InspectAPedia.com InspectAPedia®
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US


Mobile Phone/PDA website viewMobile View
WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS

AIR DISCHARGE at FAUCETS, FIXTURES
AIR INLET VALVE, WATER TANK
AIR VOLUME CONTROLS, WATER TANK

BIOLOGICAL POLLUTANTS
Bisphenol-A, BPA

CHEMICAL CONTAMINANTS in WATER
CHECK VALVES
CHLORAMINE / CHLORINE Tests
CHLORINE IN DRINKING WATER
CHLORINE in WATER, HOW TO TEST FOR

CISTERNS

DEBRIS in WATER SUPPLY, Water Heater
DRINKING WATER TESTING

DRINKING WATER - EMERGENCY PURIFICATION
DRINKING WATER - EMERGENCY SOURCES

EPA GUIDE to WATER QUALITY

FHA WATER TESTS REQUIRED

FILTERS, WATER
FLOW CONTROL VALVES
FOOT VALVES, WELL PIPING

GALVANIC SCALE & METAL CORROSION
GREYWATER SYSTEMS

HARD WATER - SOFTENERS
HEAT TAPE USAGE GUIDE

LEAD POISONING HAZARDS GUIDE
Legionella Legionnaires' Disease

METHANE GAS SOURCES
MVOCs & MOLDY MUSTY ODORS
MSDS Material Safety Data Sheets
MUNICIPAL WATER PRESSURE IMPROVEMENTS

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS IN WATER
OZONE HAZARDS

Pesticide Exposure Hazards

PIPING IN BUILDINGS, Clogs Leaks Types
PLASTIC CONTAINERS, TANKS, TYPES
PLUMBING SYSTEM ODORS
PRESSURE CONTROL SWITCH ADJUSTMENT

RADON HAZARD TESTS & MITIGATION

RELIEF VALVES - Water Tanks

REVERSE OSMOSIS CONCENTRATE DISPOSAL

SEWAGE PATHOGENS in SEPTIC SLUDGE
SEWER GAS ODORS

TANK TYPES: WATER, OIL, EXPANSION, ALL

VALVES, PLUMBING

WATER CONTAMINANT LEVELS
WATER FILTERS
WATER HAMMER NOISE DIAGNOSE & CURE

WATER HEATERS

WATER ODORS, CAUSE CURE

WATER PRESSURE & FLOW MEASUREMENT
WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE REPAIR GUIDE - WELLS

WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS
WATER PUMPS, TANKS, WELLS - BASICS

WATER PUMP CAPACITIES TYPES RATES GPM
WATER PUMP CONTROLS & SWITCHES
WATER PUMP PRESSURE CONTROL SWITCH
WATER PUMP TYPES & LIFE EXPECTANCY
WATER PUMP PRIMING PROCEDURE
WATER PUMP PROBLEM DIAGNOSTIC TABLE

WATER PUMP REPAIR GUIDE
WATER PUMP SHORT CYCLING
WATER PUMP WONT STOP RUNNING

WATER PURIFIERS

WATER QUALITY TESTS, CONTAMINANTS, TREATMENT
WATER QUANTITY IMPROVEMENT

WATER SHUTOFF VALVE LOCATION, USE
WATER SHUTOFF VALVE, WELL PUMP

WATER SOFTENERS & CONDITIONERS
WATER SOURCE ALTERNATIVES

WATER TANK: USES, TROUBLESHOOTING
WATER TANK AIR, HOW TO ADD
WATER TANK AIR INLET VALVE
WATER TANK AIR LOSS SIGNS
WATER TANK AIR VALVE REPAIRS
WATER TANK AIR VOLUME CONTROLS
WATER TANK BLADDERS & CAPTIVE AIR
WATER TANK CAPTIVE AIR vs TRADITIONAL WellMate

WATER TANK CONTROLS & SWITCHES
WATER TANK LIFE EXPECTANCY

WATER TANK PRESSURE CALCULATIONS
WATER TANK PRESSURE GAUGE
WATER TANK PRESSURE RELIEF VALVE

WATER TANK REPAIRS
WATER TANK REPLACEMENT

WATER TANK SAFETY
WATER TANK SIZE & VOLUME

WATER TANK TYPES: WATER, OIL, EXPANSION, ALL

WATER TESTS, CONTAMINANTS, TREATMENT
WATER TEST CHOICES & WATER TEST FEES
WATER TESTING GUIDE
WATER TEST INTERPRETATION

WATER TREATMENT EQUIPMENT CHOICES

WELL PUMP PRIMING PROCEDURE

WELLS CISTERNS & SPRINGS

WINTERIZE A BUILDING

More Information

Schematic of a shallow well single line jet pump water system (C) Carson Dunlop

How Does a One Line Jet Pump Well Water Pump Work?
InspectAPedia®  -    

  • Sequence of operation of a well and pump system using a one line jet pump
  • Installation and troubleshooting for one line jet pumps used for private well water supply
InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This article describes the sequence of operating steps in a one-line jet pump water system. The process of diagnosis and the costs of the repair are explained. Consumer advice on saving money on water supply repair costs includes a review of the parts and labor costs of a typical well pump and pressure tank replacement case. Carson Dunlop's sketch (at page top) shows the main parts of a one-line jet pump well installation. Readers of this document should also see our other diagnostic guides for water pumps, wells, motors, in table form:

  • ELECTRIC MOTOR DIAGNOSTIC GUIDE - table format and text.
  • SHORT CYCLING DIAGNOSIS TABLE - table format. Also see SHORT CYCLING WATER PUMP - text.
  • WATER PRESSURE PROBLEM DIAGNOSIS TABLE - table format. Also see WATER PRESSURE LOSS DIAGNOSIS & REPAIR - text.
  • WATER PUMP PROBLEM DIAGNOSTIC TABLE - table format. Also see WATER PUMP PROBLEM DIAGNOSTIC TABLE - text

See WATER PUMP, ONE LINE JET for a description of the function of each component of a one-line jet pump system. Readers should also see IDENTIFY WELL PUMP TANK COMPONENTS. Nearly all well pumping systems, one line jet pump, two line jet pump, or submersible well pump, require a foot valve installed at the bottom of the well piping. If your building has water pressure problems, see WELL WATER PRESSURE DIAGNOSIS. Readers whose wells simply run out of water should also see How to Test Well Water Quantity and see How to Get More Water From a Well.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

How a One-Line Jet Pump Well Water System Works - Sequence of Operating Steps

Photograph of a water system check valveWhat happens when you turn on the water at a faucet in a building whose water is supplied by a one-line jet pump? (See the sketch at the top of this page for the basic components of a one-line jet pump system.) Our photograph (left) shows a one-line jet pump installed in a home.

Notice that there is a horizontal pipe with a check valve? That's the pipe leading to the water source. (We explain this check valve at WELL PIPING CHECK VALVES.)

The vertical pipe rising from the pump is the jet pump outlet connection that sends pressurized water to the water pressure tank and onwards to the rest of the building.

The following steps describe normal operating of a building well pump and water supply system. Other cases in which the well pump controls are not working properly, there is a problem with the controls, pressure tank, pump, or well itself are discussed at WATER PRESSURE REPAIR GUIDE & COSTS and at WELL WATER PRESSURE DIAGNOSIS.

  1. Turn on building water at a plumbing fixture: open a sink valve, tub valve, or flush a toilet.
  2. Water runs out of the supply faucet, into the fixture, down the drain
  3. Water pressure and flow are being supplied to the building from a water pressure tank. If we didn't use a pressure tank, because water is not very compressible, the second water was turned on, water pressure in the system would drop below the pump cut-on pressure, the pump would turn on, and probably bring water pressure up to the cut-off pressure quickly, causing short cycling and burning up pump controls or a pump motor. See WATER TANKS HOW THEY WORK.
  4. Pressure in the water pressure tank and in the building piping system drops down to the well pump cut-in pressure. Typically this is 20 or 30 psi on a residential water system.
  5. The well pump pressure control switch senses the pressure drop, closes an internal electrical relay switch to turn on the well pump. See WATER PUMP PRESSURE CONTROL.
  6. The well pump motor runs, drawing water back into the building from the well by "sucking" water up from a shallow depth (a one-line jet pump can't draw water from much below 25 feet)
  7. Water is forced into the building water pressure tank and simultaneously into the building piping and on to the plumbing fixtures.
  8. If the pump sends water into the building faster than water is flowing out of the open faucet or plumbing fixture, the pump will "get ahead" of the water flow, successfully pressurizing the water tank, causing the pressure switch to turn off the pump (see step 10 below).

    OR

  9. If the pump cannot send water into the building faster than water is flowing out of the open faucet or plumbing fixture, the well pump will run continuously and water will flow out of the open faucet or plumbing fixture at a rate limited basically by the pump's water delivery flow rate in gallons per minute. You'll also find this condition if a building water supply pipe bursts. We say "basically" because the well piping and building piping and faucets themselves offer some back-pressure against the pump's flow rate. In this case, the well pump will continue to run until the building faucets or plumbing fixtures are turned off. At that point ...
  10. The well pump pressure control switch senses that water pressure has increased to the cut-out point, opening its switch and turning off electrical power to the well pump. The well pump has re-pressurized the building water tank and piping up to the cut-out or cut-off water pressure.
  11. The foot valve closes (at the bottom of the well piping) and/or a check valve located in the building on or close to the well pump closes, preventing water and pressure from flowing backwards down into the well, losing building water pressure and possibly losing pump prime. See WELL PIPING FOOT VALVES and see WELL PIPING CHECK VALVES and if necessary, WELL PUMP PRIMING PROCEDURE.

How to Diagnose Poor Well Water or Pump Water Pressure

For our complete water pressure and pump, well, and piping problems diagnostic article list, see WATER PRESSURE REPAIR GUIDE & COSTS and WATER PRESSURE LOSS DIAGNOSIS & REPAIR. Separately we also provide a WATER PRESSURE PROBLEM DIAGNOSIS TABLE. The following articles pertain if you have a private well, pump, and tank system for your building or if your incoming community water supply pressure and flow are just too low to start with:

  1. Water Tank Problems? See Water Pressure Tank Problems. Examples of water tank problems include poor water pressure or the well pump rapidly turning on and off (short cycling).
  2. Water pump problems? Examples of water pump problems include poor water pressure or no water pressure at all. See
    • WATER PUMP PRESSURE CONTROL ADJUSTMENT - poor building water pressure or flow
    • PUMP PRESSURE CONTROL REPAIR - pump is not delivering water at all or water pressure is poor
    • WATER PUMP RELAY SWITCH - submersible pump has stopped working
    • WATER PUMP PRIMING PROCEDURE - well pump keeps losing prime - pump runs but gives no water
    • WATER PUMPS & TANKS & WELLS - complete list of articles
    • WATER PUMP CONTROLS & SWITCHES - complete list of well pump controls and switches, identification, diagnosis, repair
    • WATER PRESSURE GAUGE ACCURACY - maybe water pressure is fine and it's the gauge that's bad?
  3. Water piping or well piping problems? If your water pump keeps losing prime, a shallow well jet pump well line could have a bad foot valve (in the well WELL PIPING FOOT VALVES) or there may be a bad check valve on well piping at or near the water tank or near the above-ground water pump (CHECK VALVES) and so be losing prime. A leak in the well line piping itself can also lead to loss of prime.
  4. Well Problems? Do you run out of water or after running water for some interval water pressure and flow are poor? Well problem diagnosis starts at  WELLS CISTERNS & SPRINGS. Before assuming that there is no water in the well, check to see if the water pump is working properly, including loss of pump prime (WATER PUMP PRIMING PROCEDURE) and a bad or leaky well piping foot valve (WELL PIPING FOOT VALVES).
  5. Bad water pump or water tank pressure regulator control? See WATER PRESSURE REDUCER / REGULATOR (not usually installed on private well and pump systems, often present on municipal water supply systems that use an in-building local water pump and pressure tank to boost pressure). Water pump pressure regulator switch diagnosis and repair steps include these:
    • How to Adjust Water Pump Pressure: The detailed, step by step procedure for inspecting and adjusting the water pressure control switch is discussed in detail at ADJUST PUMP PRESSURE CONTROL.
    • Diagnosing Water Pump Short Cycling on and off: If your water pump is clicking on and off too often or quite rapidly see SHORT CYCLING.
    • Diagnosing Water Pressure Drops without explanation when the pump stops, see Water Pressure Falls Slowly, Erratic Pumping: bad pressure control switch, building water running or leak, bad pressure gauge, bad check valve, bad foot valve.
    • Diagnosing & Repairing Lost Air in the Water Tank: The problem of lost air in the water pressure tank along with how to correct that condition are discussed beginning at SIGNS OF AIR LOSS.
    • Diagnosing & Repairing a Water Pressure Control or Water Pump Control Switch: We discuss diagnosing and repairing a water pressure control switch that sticks "on" or "off" or simply won't operate, at water pump Pressure Switch Repairs.
  6. Bad Hot Water Pressure? See HOT WATER IMPROVEMENT especially if the building cold water pressure is acceptable but hot water pressure and flow are poor. Accumulated debris in a water heater, and debris from a corroded or disintegrating hot water tank dip tube or hot water tank sacrificial anode can also block the hot water outlet opening, resulting in low hot water pressure in a building.
  7. Bad cold or hot water pressure and flow just at certain plumbing fixtures? See our discussion of Poor water pressure just at certain plumbing fixtures just above.
  8. Problems with water treatment equipment can cause loss of water pressure or no water flow: a clogged water filter, or a malfunction in water disinfection or other water treatment equipment can cause a reduction in water pressure or even a complete stop in water flow in a building. See WATER FILTERS for details about clogged filters, and see WATER TREATMENT EQUIPMENT CHOICES for our complete list of types of water treatment equipment.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

PLUMBING SYSTEM INSPECT DIAGNOSE REPAIR

AGE of PLUMBING MATERIALS & FIXTURES
AIR DISCHARGE at FAUCETS, FIXTURES
AIR VOLUME CONTROLS, WATER TANK

FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP

PIPING IN BUILDINGS, Clogs Leaks Types

WATER FILTERS
WATER HEATERS

WATER ODORS, CAUSE CURE

WATER PRESSURE REPAIR GUIDE - WELLS

WATER PRESSURE & FLOW MEASUREMENT
  WATER PRESSURE VARIATION CAUSES
  WATER PRESSURE TOO HIGH: DANGERS
  Definition of Static Water Pressure
  Definition of Dynamic Water Pressure
  Measure Municipal Water Pressure
  Measure Pump & Well Water Pressure
  WATER FLOW RATE MEASUREMENT
  HOT WATER PRESSURE EXPANSION RATE

WATER PRESSURE GAUGES
WATER PRESSURE GAUGE ACCURACY
WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE PROBLEM DIAGNOSIS TABLE
  AIR DISCHARGE at FAUCETS, FIXTURES
  MUNICIPAL WATER PRESSURE DIAGNOSIS
  WELL WATER PRESSURE DIAGNOSIS
  WATER FILTERS
  Water Pressure Intermittent
  No Water Pressure
  Well Tank relation to Water Pressure
  Shaking the Water Tank?
  Water Pressure Bad at Some Fixtures
  Water Pressure Falls Slowly, Erratic Pumping
  Water Pressure Intermittent
  Water Pressure Tank Problems
  Water Pressure Tank Diagnosis
  Water pressure Later Returns "on its own"
  Water pipe clog diagnosis
  Water pipe clog repair guide
  WELL PIPING LEAK DIAGNOSIS
  Making the "right" repair
  WATER PRESSURE BOOSTER PUMP
  Typical Water Tank & Pump Prices

WATER PRESSURE REDUCER / REGULATOR

WATER PRESSURE & FLOW MEASUREMENT

WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS
WATER PUMPS, TANKS, WELLS - BASICS
A HREF="/water/Well_Pump_Capacities.htm">WATER PUMP CAPACITIES TYPES RATES GPM
WATER PUMP CONTROLS & SWITCHES
  CHECK VALVES
  FLOW CONTROL VALVES
  FOOT VALVES, WELL PIPING
  RELIEF VALVES - Water Tanks
  MAIN WATER SHUTOFF VALVE
  WATER PUMP ELECTRICAL SWITCHES
  WATER PUMP PRESSURE CONTROL SWITCH
  WATER PUMP RELAY SWITCH

WATER PUMP PRESSURE CONTROL SWITCH
  WATER PUMP PRESSURE CONTROL ADJUSTMENT
  WATER PUMP PRESSURE CONTROL REPAIR
  WATER PUMP PRESSURE CONTROL REPLACE
WATER PUMP PROBLEM DIAGNOSTIC TABLE

WATER PUMP REPAIR GUIDE
  AIR DISCHARGE at FAUCETS, FIXTURES
  CONTROLS & SWITCHES
  INTERMITTENT CYCLING WATER PUMPS
  WATER PRESSURE BOOSTER PUMP
  PUMP & TANK REPAIRS & COSTS
  SHORT CYCLING WATER PUMP
  SHORT CYCLING CAUSES
  SHORT CYCLING CAUSE: WELL PIPE LEAKS
  SHORT CYCLING DIAGNOSIS TABLE
  WATER PUMP ELECTRICAL SWITCHES
  WATER PUMP PRESSURE BOOSTER
  WATER PUMP PRESSURE CONTROL SWITCH
  WATER PUMP PRESSURE CONTROL ADJUSTMENT
  WATER PUMP PRESSURE CONTROL REPAIR
  WATER PUMP PRESSURE CONTROL REPLACE
  WATER PUMP PRIMING PROCEDURE
  WATER PUMP RELAY SWITCH
  WATER PUMP WONT STOP RUNNING
  Water Tank & Pump Costs
  WATER TANK AIR, HOW TO ADD
  WATER TANK PRESSURE GAUGE
WATER PUMP SAFETY
WATER PUMP SHORT CYCLING

WATER PUMP TYPES & LIFE EXPECTANCY
  WATER PUMP, ONE LINE JET
  WATER PUMP, ONE LINE JET OPERATION
  PUMP, TWO LINE JET
  PUMP, TWO LINE JET OPERATION
  PUMP, SUBMERSIBLE
  PUMP, SUBMERSIBLE OPERATION
  PUMPS, OTHER Kinetic Water Ram, Manual, Artesian
  WATER PRESSURE BOOSTER PUMP
  PUMP & TANK REPAIRS & COSTS
WATER PUMP PRIMING PROCEDURE
WATER PUMP WONT STOP RUNNING

WATER PURIFIERS

WATER QUALITY TESTS, CONTAMINANTS, TREATMENT
WATER QUANTITY IMPROVEMENT
WATER QUANTITY USAGE GUIDE

WATER SHUTOFF VALVE LOCATION, USE
WATER SHUTOFF VALVE, WELL PUMP

WATER SOFTENERS & CONDITIONERS
WATER SOURCE ALTERNATIVES
WATER SUPPLY & DRAIN PIPING

WATER TANK: USES, TROUBLESHOOTING
WATER TANK AIR, HOW TO ADD
WATER TANK AIR INLET VALVE
WATER TANK AIR LOSS SIGNS
WATER TANK AIR VALVE REPAIRS
WATER TANK AIR VOLUME CONTROLS
WATER TANK BLADDERS & CAPTIVE AIR
WATER TANK CAPTIVE AIR vs TRADITIONAL WellMate

WATER TANK CONTROLS & SWITCHES
  WATER PUMP RELAY SWITCH
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK AIR INLET VALVE
  WATER TANK AIR VALVE REPAIRS
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK DRAIN VALVE
  WATER TANK PRESSURE GAUGE
  WATER PRESSURE GAUGE ACCURACY
  WATER TANK RELIEF VALVE
WATER TANK LIFE EXPECTANCY

WATER TANK PRESSURE CALCULATIONS
WATER TANK PRESSURE GAUGE

WATER TANK REPLACEMENT
WATER TANK REPLACEMENT
WATER TANK REPAIRS
  AIR DISCHARGE at FAUCETS, FIXTURES
  CONTROLS & SWITCHES on WATER TANKS
  INTERMITTENT CYCLING WATER PUMPS
  SHORT CYCLING WATER PUMP
  SHORT CYCLING CAUSES
  SHORT CYCLING CAUSE: WELL PIPE LEAKS
  SHORT CYCLING DIAGNOSIS TABLE
  WATER TANK AIR, HOW TO ADD
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK AIR ADD AT AIR VALVE
  WATER TANK AIR ADD BY DRAINING
  WATER TANK AIR HOW MUCH TO ADD
  WATER TANK AIR HOW OFTEN TO ADD
  WATER TANK AIR INLET VALVE
  WATER TANK AIR LOSS SIGNS
  WATER TANK AIR VALVE REPAIRS
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK BLADDERS & CAPTIVE AIR
  WATER TANK BLADDER PRESSURE ADJUSTMENT
  WATER TANK DRAIN VALVE

WATER TANK REPLACEMENT
WATER TANK SAFETY
WATER TANK SIZE & VOLUME
WATER TANK TYPES: WATER, OIL, EXPANSION, ALL

WATER TESTS, CONTAMINANTS, TREATMENT
WATER TREATMENT EQUIPMENT CHOICES
WATER USAGE TABLE

WELLS CISTERNS & SPRINGS
  AIR DISCHARGE at FAUCETS, FIXTURES
  Basement Wells
  CHECK VALVES
  CISTERNS
  DEPTH of a WELL, HOW TO MEASURE
  Drilled Wells - steel casings
    Drilled Well with Submersible Pump
    Shallow Well with One Line Jet Pump
    OLD WELL - RETURN TO SERVICE
    Well with Two Line Jet Pump
  Driven Point Wells
  How Much Water is In the Well?
    Static Head of Water in the Well
    Well Yield: Well Flow Rate
      Define Well Yield, Recovery Rate, Flow Rate
      Calculating the Flow Rate of a Well
      Well Flow Rate in GPM or 24-Hours
      Well's Flow Rate Change Over Time
      Define Safe Yield for a Well
    Total Quantity of Water Available
  How to Test Well Water Quantity
  How to Get More Water From a Well
  Hand Dug Wells
  Hand Dug Well Procedure
  Jetted Wells
  OLD WELL - RETURN TO SERVICE
  Springs as Water Supply
  Wash Wells
  Well Pits
  WATER HAMMER NOISE DIAGNOSE & CURE
  WATER PRESSURE LOSS
  WELL CHLORINATION SHOCKING PROCEDURE
  WELL CLEARANCE DISTANCES
  WELL DEPTH, HOW TO MEASURE
  WELL FLOW RATE
  WELL LIFE EXPECTANCY
  WELL PIPING CHECK VALVES
  WELL PIPING FOOT VALVES
  WELL PIPING LEAK DIAGNOSIS
  WELL PIPING TAIL PIECE
  WELL PUMP PRIMING PROCEDURE
  WELL PUMP TYPES & LIFE EXPECTANCY

WINTERIZE A BUILDING

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Thanks to our reader, Carole Cimitile, 2/17/2009, for reminding us that small problems like faucet o-rings, clogged faucet strainers and similar local plumbing fixture defects can have a big impact on hot water flow, cold water flow, or both hot and cold water flow and pressure problems.
  • Water Fact Sheet #3, Using Low-Yielding Wells [ copy on file as /water/Low_Yield_Wells_Penn_State.pdf ] - , Penn State College of Agricultural Sciences, Cooperative Extension, School of Forest Resources, web search 07/24/2010, original source: http://pubs.cas.psu.edu/FreePubs/pdfs/XH0002.pdf
  • Smart Tank, Installation Instructions [ copy on file as /water/Smart_Tank_Flexcon.pdf ] - , Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
  • Typical Shallow Well One Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect_Jet_Pumps_1.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Typical Deep Well Two Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Water Ace Jet Pump Installation Manual, instructions from Water Ace Pump Co., web search 08/28/2010, original source: http://www.waterace.com/pdf/R510%20R520%20and%20R100%20Jet%20Pumps%20Manual.pdf
    Consumer hotline: 800-942-3343 - instructions for the installation and maintenance of
    Water Ace shallow well pump Model R510 1/2 HP
    Water Ace deep well pump Model R100 convertible 1HP and
    Water Ace deep well jet pump Model R250 convertible 1/2 hp.

Water Supply & Drain Piping, Wells, Pumps, Water Supply Equipment

  • Access Water Energy, PO Box 2061, Moorabbin, VIC 3189, Australia, Tel: 1300 797 758, email: sales@accesswater.com.au Moorabbin Office: Kingston Trade Centre, 100 Cochranes Rd, Moorabbin, VIC 3189
    Australian supplier of: Greywater systems, Solar power to grid packages, Edwards solar systems, Vulcan compact solar systems, water & solar system pumps & controls, and a wide rage of above ground & under ground water storage tanks: concrete, steel, plastic, modular, and bladder storage tanks.
  • Cheating on water tests: Testing Water for Real Estate Transactions - make sure your water test is valid
  • Diagnosing Clogged Drains: Is it a blocked drain or the septic system? - A First Step for Homeowners
  • Drinking Water Contaminant Levels - Maximum Allowed
  • Drinking Water Supply, Contamination Levels, Water Testing Procedures
  • Drinking Water Testing Advice for home buyers home owners home inspectors
  • Interpreting Drinking Water Test Results and Correcting Unsatisfactory Water
  • Lead Contamination in Drinking Water: Testing & Correction - Advice (This Article)
  • Lead Testing & Correcting Contamination from Lead Water Supply Lines/Entry Mains - Lead Pipe Problems/Advice
  • Life Expectancy of Water Pumps - Well Pumps: how long should a water pump last? What affects pump life?
  • Life Expectancy of Wells & Water Tanks how long should a water well and its components last?
  • Plumbing Diagnosis & Repair: Water supply, drainage, septic systems, water testing, water contamination, defective plumbing materials & products.
  • Shock or Chlorinate a Well, How to - Procedure for Shocking a Well to (temporarily or maybe longer) "Correct" Bacterial Contamination
  • Smart Tank, Installation Instructions [ copy on file as /water/Smart_Tank_Flexcon.pdf ] - , Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
  • Typical Shallow Well One Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect_Jet_Pumps_1.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Typical Deep Well Two Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Water Fact Sheet #3, Using Low-Yielding Wells [ copy on file as /water/Low_Yield_Wells_Penn_State.pdf ] - , Penn State College of Agricultural Sciences, Cooperative Extension, School of Forest Resources, web search 07/24/2010, original source: http://pubs.cas.psu.edu/FreePubs/pdfs/XH0002.pdf
  • Water pressure tanks - how to diagnose the need for air, how to add air, stop water pump short cycling to avoid damage - water storage water pressure tank safety.
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water pressure tank failures & water pump short cycling diagnosis and repair
  • Water Supply & Drain Piping, water and drain pipe types, inspection, diagnosis, repairs, problem materials, clogging, etc.
  • Water Tests & Fees this water test fee schedule applies when testing is combined with other onsite building inspection services
  • Water Testing: background comments on classes of water contaminants, & links to home buyer advice about water testing, drinking water, water supply
  • Water Requirements, Home & Outdoor Living

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
    • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop, and from the InspectAPedia bookstore. The 2010 edition of the Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Crystal Clear Supply provides portable ceramic water filter purifiers and portable reverse osmosis water treatment equipment - see http://www.crystalclearsupply.com/category_s/7.htm
  • Handbook of Disinfectants and Antiseptics, Joseph M. Ascenzi (Editor), CRC, 1995, ISBN-10: 0824795245 ISBN-13: 978-0824795245 "The evaluation of chemical germicides predates the golden age of microbiology..." -
    This well-focused, up-to-date reference details the current medical uses of antiseptics and disinfectants -- particularly in the control of hospital-acquired infections -- presenting methods for evaluating products to obtain regulatory approval and examining chemical, physical, and microbiological properties as well as the toxicology of the most widely used commercial chemicals.
  • Potable Aqua® emergency drinking water germicidal tablets are produced by the Wisconsin Pharmacal Co., Jackson WI 53037. 800-558-6614 pharmacalway.com
  • Principles and Practice of Disinfection, Preservation and Sterilization (Hardcover)
    by A. D. Russell (Editor), W. B. Hugo (Editor), G. A. J. Ayliffe (Editor), Blackwell Science, 2004. ISBN-10: 1405101997, ISBN-13: 978-1405101998.
    "This superb book is the best of its kind available and one that will undoubtedly be useful, if not essential, to workers in a variety of industries. Thirty-one distinguished specialists deal comprehensively with the subject matter indicated by the title ... The book is produced with care, is very readable with useful selected references at the end of each chapter and an excellent index. It is an essential source book for everyone interested in this field. For pharmacy undergraduates, it will complement the excellent text on pharmaceutical microbiology by two of the present editors."
    The Pharmaceutical Journal: "This is an excellent book. It deals comprehensively and authoritatively with its subject with contributions from 31 distinguished specialists. There is a great deal to interest all those involved in hospital infection ... This book is exceptionally well laid out. There are well chosen references for each chapter and an excellent index. It is highly recommended." The Journal of Hospital Infection.: "The editors and authors must be congratulated for this excellent treatise on nonantibiotic antimicrobial measures in hospitals and industry ... The publication is highly recommended to hospital and research personnel, especially to clinical microbiologists, infection-control and environmental-safety specialists, pharmacists, and dieticians."
    New England Journal of Medicine: City Hospital, Birmingham, UK. Covers the many methods of the elimination or prevention of microbial growth. Provides an historical overview, descriptions of the types of antimicrobial agents, factors affecting efficacy, evaluation methods, and types of resistance. Features sterilization methods, and more. Previous edition: c1999. DNLM: Sterilization--methods.
  • U.S. Army Field Manual 21-10, Field Hygiene and Sanitation, 1988, web search 07/02/2010, original source: http://www.enlisted.info/field-manuals/fm-21-10-field-hygiene-and-sanitation.shtml
    The purpose of this manual is to assist individual soldiers, unit commanders, leaders and field sanitation teams in preventing disease and environmental injuries. The manual provides information on preventive medicine measures (PMM) to the individual soldier as well as essential information for the unit commander, unit leaders, and the unit field sanitation team on applying unit level PMM.
  • When Technology Fails, Matthew Stein, Chelsea Green Publisher, 2008,493 pages. ISBN-10: 1933392452 ISBN-13: 978-1933392455, "... how to find and sterilize water in the face of utility failure, as well as practical information for dealing with water-quality issues even when the public tap water is still flowing". Mr. Stein's website is www.whentechfails.com/
  • ...
Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com