FREE Encyclopedia of Building & Environmental Construction, Diagnosis, Maintenance & Repair The accuracy & trustworthiness of every article or Q&A is researched by human experts. See WHO ARE WE?
Swamp Coolers & Evaporative Coolers for Air Cooling: Design & Usage Guide
POST a QUESTION or COMMENT about using a swamp cooler to cool a building interior - when do swamp coolers work better than an air conditioner?
Swamp coolers:
This article explains the use of an evaporative cooling system or "swamp cooler" including cool air delivery design considerations when using under-floor ducts for cool air delivery in buildings.
Swamp coolers or evaporative cooling systems work well in dry climates - usually, as we explain here.
The discussion of cool air duct location and routing includes general air conditioning duct design concepts that also apply to all air conditioning and cooling designs.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Evaporative Cooling Systems or "Swamp Coolers" - How They Work
Evaporative coolers, also called "swamp coolers" rely on the evaporation of water to cool building air, rather than the movement of a refrigerant through cooling coils.
Cooling towers, swamp coolers, and even a simple window fan blowing air across a pan of water and into a room are types of evaporative cooling systems.
[Click to enlarge any image]
Swamp coolers systems may use less energy than a refrigerant-gas and compressor type air conditioner but they'll only work where the ambient humidity is low enough to make it easy to evaporate water, such as in Arizona and other areas of the Southwest and Mexico.
Our sketch (left), courtesy of Carson Dunlop, shows three types of evaporative cooling systems or "swamp coolers".
All three evaporative cooling system approaches are similar: dry outdoor air is blown across an evaporative cooling device that uses water evaporation to cool the incoming air.
The differences among these swamp cooler designs are principally how the water to be evaporated is delivered to the evaporative cooling device (drum or pad bottom is immersed in a water reservoir pan, or a pump delivers water to the top of the evaporative pad), and the type of evaporative device itself: a rotating drum or an evaporative pad.
Delivery of Cool Air Using an Evaporative Cooling System
The question-and-answer article below paraphrases, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.
Topic: Under-floor ducts for cool air delivery with (for example) an evaporative cooling system
Question: We plan to build a pilot energy-efficient home in our city.
We have a long and somewhat severe cooling season, with a humidity level that is relatively low (10-15 % RH). An evaporative cooling system or swamp cooler should suffice, but there are several drawbacks: dust, open windows, safety, noise, and the like.
I would like to duct the cool air delivery system under a wood-framed floor, supplying cool air through floor registers, and exhausting it out through a roof cupola. (See sketch above, courtesy of Solar Age Magazine). I am sure that an attic fan will be necessary to drive the warm air exhaust out of the building.
Do you see any obvious problems with the scheme I have described? -- Jimmy Moore, Odessa, TX
Answer:
Single-stage direct evaporative coolers, also called "swamp coolers" do provide a cost-effective means of cooling houses during hot, dry periods. Their main drawback is moister indoor air - the cost for a lower dry-bulb temperature.
Due to low energy use (for a small fan and water pump), swamp coolers are popular in the U.S. in parts of the West and Southwest. For example, our photograph at page top shows a swamp cooler system whose operating components are mounted on a Tucson Arizona rooftop.
Watch out: a swamp cooler, like other water-eavaporation cooling devices can become a reservoir of dangerous Legionella bacteria. See details
Delivering cooled air through the floor and exhausting it through the roof runs counter to the tendency of warm air to rise and cool air to fall in a building. But an exhaust fan in the roof should pull air upwards through the entire house.
Watch out: Two warnings:
Make sure that the exhaust fan capacity in cubic feet per minute (CFM) is matched to the volume of air that is being supplied from the cooling system upwards from the floor ducts and air registers.
Carson Dunlop Associates' sketch (left) shows a different approach for a closed air duct system that changes its duct operation depending on whether warm air or cool air is being delivered into the building.
You would probably not use this duct design in an evaporative cooling system because the evaporative cooling approach depends on continuous introduction of dry outside air into and through the building during the cooling system, but the sketch makes clear a duct system intended to deliver cool air in a building needs to operate differently than ducts intended to deliver warm air during the heating system if airflow is to be optimized.
Using a Rooftop Cupola to Exhaust Swamp Cooler-Delivered Cool Air?
Provide an air duct between the top floor ceiling grille and the roof exhaust cupola. This will keep moist (and possibly cooler) air out of the attic, where it might condense at night and cause moisture problems in the structure and in the attic insulation.
Carson Dunlop's sketch (left) warns of another safety consideration: a whole house fan or an attic exhaust fan (such as we describe above), can cause back-drafting at fireplaces and atmospheric-vented gas heating appliances - backdrafting can in turn cause dangerous, potentially fatal carbon monoxide hazards in buildings.
Finally, remember to provide a means of closing off the rooftop exhaust during the heating season. Otherwise your warm house air will simply escape by natural convection currents carrying it up and outdoors through your rooftop-mounted exhaust system even if the fan is not running.
See Solar Age Magazine "Notebook" 2/84, for the conditions where evaporative cooling is effective.
In that issue, author Jerry Germer reviews use of the psychrometric chart that relates moisture, temperature, and indoor relative humidity to discuss the conditions that make people comfortable indoors, and how to relate indoor comfort to the outdoor climate, particularly to temperature and humidity in those two environments.
Our photo (left) shows an evaporative cooler or "swamp cooler" in use blowing cool air into an outdoor mechanic's work area at Canyon Auto Sales in Tucson, AZ. Photo by the author and Andy Gieseke, Canyon Auto.
Swamp coolers or other evaporative cooling systems can cool a building interior using less energy than a conventional air conditioner or heat pump system except during times of very wet or humid weather such as the "monsoon" season in southern Arizona.
During wet and very humid weather evaporative cooling simply cannot evaporate enough water to produce good cooling. Some building owners install both evaporative cooling or swamp coolers and a conventional refrigerant-based air conditioner or heat pump, running the latter only when necessary due to humid conditions.
Watch out: leaky swamp coolers or just about any mechanical equipment that regularly spills or overflows water onto a roof surface is likely to cause stains on the roof surface and might lead to roof wear as well.
Mr. Germer mapped eight heating and cooling "design zones" onto areas of the psychrometric chart and then described eight indoor air conditioning approaches and related them to the outdoor climate. For areas or times of the year when temperature and humidity outdoors, and thus also relative humidity, fall within multiple zones on the Germer chart, multiple of the 8 zones and 8 indoor air conditioning strategies below might be usable.
Active solar or mechanical heating: this zone has outdoor temperatures too low for passive building environment conditioning strategies.
Passive solar heating: direct solar gain, indirect solar heat gain, hybrid systems, combined with air infiltration and temperature conduction control - we describe passive solar heating
Dehumidification: high outdoor (or indoor) humidity requires using some method to remove the excess humidity in order for building occupants to be comfortable. In the 1984 article Germer pointed out that passive dehumidification had not been well developed.
Mechanical air conditioning: temperature & humidity combinations in this climate zone cannot be managed by passive means and so mechanical air conditioning
Ventilation: although temperatures and humidifies may be high, occupants may be made comfortable by direct evaporation of sweat from the skin if enough air velocity is available - in other words, fans can do the trick.
Thermal mass: these air conditioning systems are usually found in hot-dry climates with dry cool nights, such as southwestern United States and parts of Mexico, particularly at higher elevations
and THERMAL MASS in UPSTAIRS Radiant cooling and night-flushing of internal mass with cool outside air stores coolness (the ability to later absorb heat) for the next day, and similarly, during the warmer day, the same thermal mass can store warmth to even out cooler nighttime temperatures indoors.
Evaporative cooling: low energy "swamp coolers" (discussed in this article) can be used under conditions of low humidity such as in Arizona and higher elevations of Mexico.
Humidification: moisture needs to be added to very dry air for indoor comfort.
See HUMIDITY LEVEL TARGET. We prefer local or room humidifiers after seeing duct, mold, concerns with some centralized humidifier add-ons to heating and air conditioning systems.
The link to the original Q&A article in PDF form immediately below was preceded above by an expanded/updated online version of this article.
The articles at this website describe the basic components of an air conditioning system
and then we discuss how to estimate the rated cooling capacity of an air conditioning system by examining various data tags and components.
The limitations of visual inspection of A/C systems are described.
Evaporative Cooling Resources for Products, Manuals, Installation Guides
Bonaire Evaporative Coolers, distributes heating & cooling products in Australia and New Zealand, including Bonaire whole-house rooftop-mounted evaporative cooling systems and window coolers (Durango)
New South Wales
Unit B2 7 Hepher Road
Campbelltown NSW 2560
Australia
Phone: +61 2 4602 4242
Victoria
26 Jellico Drive
Scoresby VIC 3179
Australia
Phone: +61 3 8588 4900
Fax: +61 3 8588 4990
Queensland
Unit 5 / 5 Currumbin Court
Capalaba QLD 4157
Australia
+61 7 3114 0005
Western Australia
6/91 Leach Highway
Kewdale WA 6105
Australia
Phone: +61 8 9353 551
Breezair Corporation, Seeley International Americas
1202 North 54th Avenue
Building 2 Suite 117
Phoenix Arizona 85043
United States of America
Phone: 602-353-8066, Website: www.breezair.com
Breezair provides owners manuals, installation guides, and technical support for evaporative cooling systems
Quoting from the Braemar website (see links below), Seeley International
now exports to well over 120 countries. Not bad for a
company that started out in 1972 in the garage of its
founder and Executive Chairman, Frank Seeley
Brivis Australia
61 Malcolm Road
Braeside Victoria 3195
Australia
1300 BRIVIS
(1300 274 847)
Fax: +61 (03) 9264 9400
www.brivis.com.au
email: sales@brivis.com.au Website: www.brivis.com.au
Brivis New Zealand
Distributor: Warm Air Ltd
69 Marsden Street
Lower Hutt 5010 New Zealand
PO Box 38523
Wellington Mail Centre
Wellington 5043 New Zealand
0800 WARMAIR
(0800 9276 247)
Ph: +64 (04) 920 1670
Fax: +64 (04) 920 1681
www.warmair.co.nz
email: sales@warmair.co.nz
Brivis South Africa
Distributor: Lorenz and Associates
Northlands Deco Park
Cnr Witkoppen and Newmarket Roads
North Riding, Johannesburg South Africa 2194
0861 BRIVIS
(0861 274 847)
Ph: +27 (011) 704 6112
Fax: +27 (011) 704 0022
www.brivis.co.za
email: info@brivis.co.za
Home Depot, EVAPORATIVE COOLER INSTALLATION INSTRUCTIONS [PDF] no brand nor model given, Home Depot stores, retrieved 2021/06/16 original source: https://images.homedepot-static.com /catalog/pdfImages/65 655e827f-6383-4559-8d21-0542d513a486.pdf
Seeley, Australia, SEELY EA EVAPORATIVE COOLER INSTALLATION MANUAL [PDF] Seely International, Website: seeleyinternational.com retrieved 2021/06/16 original source: https://www.seeleyinternational.com/artefact/braemar-ea-evaporative-coolers-manual/
For Australia Only Seeley International Technical Support 1300 650 399 Seeley Spare Parts Distributors 1300 367 437 Authorised Service Agents 1300 650 644 Service -
All Regions Other Than Australia: Please Contact Your Local Distributor.
Manufactured By: Seeley International Pty Ltd 112 O’sullivan Beach Rd, Lonsdale Sa, 5160. Australia
Imported By: Seeley International (Europe) Ltd Unit 11 Byron Business Centre Duke Street Hucknall, Nottingham, Ng15 7hp
United Kingdom Seeley International (Americas) Ltd 1002 S 56th Avenue, Suite # 101 Phoenix, Arizona 85043, USA
Seeley International (Africa) Pty Ltd 6 Witton Road, Foundersview South, Modderfontein 1609, Gauteng, South Africa
Moderator reply: Exhaust-Vent opening distance to Evaporative Coolers: 10 ft horizontal distance or exhaust 3 ft. above Cooler & ? horizontal distance
I took a look at the IO manuals for several evaporative coolers;
none of the IO manuals for evaporative coolers (cited above on this page) addressed your question of clearance distance to kitchen exhausts or grease exhaust vents,
and an evaporative cooler education website purporting to answer this rooftop evaporative cooler clearance distance question confuses building system mechanical air intakes (such as a fresh air intake vent or combustion air intake vent) clearance codes with rooftop-mounted evaporative cooler clearance distances and safety.
But for safety, and considering that smoke and grease may clog and foul the evaportive cooler's air flow, fan, evaporator surfaces, in our OPINION
acceptable clearance from a kitchen exhaust (a potential source of grease, smokee and noxious debris) as
10 ft. (3.3m) horizontal distance from kitchen exhaust or similar outlet to the evaporative cooler
When the exhaust opening height is less than three feet above the evaporative cooler's air intake openings.
The model codes will allow noxious exhaust to be closer to a mechanical system air inlet (or in our opinion to an evaporative cooler) IFthe exhaust vent is at least 3 ft. above the air intake of the evaporative cooler assembly. How much closer? It's not specified. Let's consider the object: avoiding grease clogging or contamination of the evaporative cooler components.
The clearance to a mechanical air intake (such as might be part of an evaporative cooler intake) is required for any source of "noxious flumes, smokes, vapors" including for example, bathroom or kitchen exhaust vents, plumbing vents, and chimneys.
Your kitchen exhaust is 9 feet away (IF you measured that as a level horizontal distance) which is almost enough, but is three feet below rather than above the evaporative cooler inlet - which is no surprise given how these units are usually placed on a roof.
Really? note that some experts assert that a kitchen should not be considered a source of "noxious exhaust" and I agree from an aesthetic point of view but NOT from a functional or safety view: kitchen exhaust vent contains FOGs (Fats, Oils, Grease) that can foul and even clog-up a nearby rooftop HVAC or Evaporative Cooler system.
Watch out: the local building code official is the final legal authority for this question
See details and IO manuals for Evaporative Coolers above on this page.
Or give us the brand and model of your evaporative cooler so that we can take a look at its installation instructions.
Thanks for asking
Question:
why is my evaporator freezing up?
(May 30, 2012) ramon said:
all exits are open fully-living room,3 rooms,dining room, yet the evaporator freezes- the evaporator is fully clean. Why it freezes?
Reply:
Improper refrigerant charge, inadequate airflow across the cooling coil, are examples of cause for frosting of the evaporator/cooling coil. - yours is not a swamp cooler.
Search InspectApedia.com for COOLING COIL ICING to read details.
Question: oily substance coming from swamp cooler
(July 21, 2014) Barry said: oily substance coming from swamp cooler
Reply:
Check for a leak at an electric motor or for a unit suffering from algae or settled dirt and debris.
Evaporative coolers are either roof-mounted (whole house cooling systems) or mounted in a window (smaller units) so are positioned differently than refrigerant-based cooling systems using an indoor air handler and outdoor compressor/condenser unit. An important consideration in mounting the rooftop unit is the proper selection of and strength of the supporting roof jacks.
But a look through the installation and owners manuals for six evaporative coolers (listed in the article above) I did not find any references to side clearances or top clearances for the units, perhaps because of their anticipated location. Certainly it would make sense to avoid installing a rooftop unit where you'd expect trouble such as
- Don't install any fan operated or air cooled device where its air intake or outlet are obstructed by a nearby vertical wall, chimney, or other exhaust system
- Don't install any fan-operated or air-cooled component where its intake air or outlet air compete with another such unit installed close-by - lest hot exhaust from one unit increase the temperature of the incoming air in another unit.
OPINION: if you don't see other specific clearance distances in the installation guide for your particular system, check with the manufacturer for advice. A general safe rule is probably to keep at least 2 meters of separation between nearby air operated devices and at least one meter from a vertical or enclosed overhead surface.
...
Continue reading at ROOFTOP A/C / HEAT PUMP - the air conditioning system seems to be "running" but not enough cool air, or no cool air at all is being delivered to the occupied space, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted. Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.
[1] "Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]
[2] Thanks to Mark Cramer, Tampa Florida, for assistance in technical review of the "Critical Defects" section and for the photograph of the deteriorating gray Owens Corning flex duct in a hot attic. Mr. Cramer is a Florida home inspector and home inspection educator.
[3] Thanks to Jon Bolton, an ASHI, FABI, and otherwise certified Florida home inspector who provided photos of failing Goodman gray flex duct in a hot attic.
[4] Thanks to Scott at SJM Inspect for suggesting this EPA document and for technical editing remarks regarding our air conditioning website,
SJM Inspection Service LLC, serves the entire state of CT, sjminspect.com 203-543-0447 or 203-877-4774
5/16/07
[5] Thanks to Joe Panimondo for technical editing, April 2011
[14] Ratib Bakera is member of Refrigeration Service Engineers Society (RSES), an International
training organization for the HVACR industry provides educational and certification programs to HVACR professionals of all experience levels. www.rses.org provides information on the organization and its training materials. Independent testing and certification of HVAC technicians is provided by North American Technician Excellence - NATE - see www.natex.org.
NATE is supported by ASHRAE, the US EPA, and a host of other trade and professional associations.
[15] Singer brand HVAC equipment brand history: Singer was bought by & became the climate control unit of Dallas-based Snyder General Corp. (founded by a former Singer HVAC manager) in 1982. The name Singer was dropped in 1984. In 1984 Snyder General operations included Arcoaire, Comfortmaker, and McQuay. In 1991 Snyder General sold Arcoaire & Comfortmaker to Inter-City Products. In 1994 Snyder General was acquired by Hong Leong Group Malaysia. Snyder General is at 2001 Ross Avenue Dallas, TX 75201
[16] Lennox air conditioning and heat pump owners manuals for air conditioners, air handlers, furnaces, heat pumps, indoor air quality systems, packaged units, water heaters, zone controls and other controls such as thermostats, are provided by Lennox at http://www.lennox.com/support/manuals.asp
[23] Air Diffusion Council, 1901 N. Roselle Road, Suite 800, Schaumburg, Illinois 60195, Tel: (847) 706-6750, Fax: (847) 706-6751 - info@flexibleduct.org - www.flexibleduct.org/ - "The ADC has produced the 4th Edition of the Flexible Duct Performance & Installation Standards (a 28-page manual) for use and reference by designers, architects, engineers, contractors, installers and users for evaluating, selecting, specifying and properly installing flexible duct in heating and air conditioning systems. Features covered in depth include: descriptions of typical styles, characteristics and requirements, testing, listing, reporting, certifying, packaging and product marking. Guidelines for proper installation are treated and illustrated in depth, featuring connections, splices and proper support methods for flexible duct. A single and uniform method of making end connections and splices is graphically presented for both non-metallic and metallic with plain ends." The printed manual is available in English only. Downloadable PDF is available in English and Spanish.
[24] Engineering toolbox properties of water - http://www.engineeringtoolbox.com/water-thermal-properties-d_162.html and email: editor.engineeringtoolbox@gmail.com web search 09/16/2010
[25] Owens Corning Duct Solutions - www.owenscorning.com/ductsolutions/ - provides current HVAC ductwork and duct insulating product descriptions and a dealer locator. Owens Corning Insulating Systems, LLC, One Owens Corning Parkway, Toledo, OH 43659 1-800-GET-PINK™
[26] "Flexible Duct Media Fiberglas™ Insulation, Product Data Sheet", Owens Corning - see owenscorning.com/quietzone/pdfs/QZFlexible_DataSheet.pdf "Owens Corning Flexible Duct Media Insulation is a lightweight, flexible, resilient thermal and acoustical insulation made of
inorganic glass fibers bonded with a thermosetting resin."
"Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]
[29] Refrigeration and Air Conditioning Technology, 5th Ed., William C. Whitman, William M. Johnson, John Tomczyk, Cengage Learning, 2005, ISBN 1401837654, 9781401837655 1324 pages
[30] Carson Dunlop, Associates, Toronto, have provided us with (and we recommend)
Carson Dunlop Weldon & Associates'Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.).
[32] FlowKinetics LLC, 528 Helena Street
Bryan, Texas 77801 USA, Tel: (979) 680-0659, Email: inform@flowkinetics.com, Website: www.flowkinetics.com, "FKS 1DP-PBM Multi-Function Meter
Pressure, Velocity & Flow
User’s Manual", web search 07/16/2012, original source: http://www.flowkinetics.com/FKS_1DP_PBM_Manual.pdf [copy on file] and "FKT Series Flow Measurement And
Pressure Acquisition System
User's Manual" http://www.flowkinetics.com/FKTSeriesManual.pdf [copy on file]
[33] Histoire de l'Académie royale des sciences avec les mémoires de mathématique et de physique tirés des registres de cette Académie: 363–376. Retrieved 2009-06-19.- Pitot Tubes, Henri Pitot (1732)
[34] Wikipedia Web: https://www.wikipedia.org/ provided background information about some topics discussed at this website provided this citation is also found in the same article along with a " retrieved on" date. NOTE: because Wikipedia entries are fluid and can be amended in real time, we cite the retrieval date of Wikipedia citations and we do not assert that the information found there is necessarily authoritative. "Pressure sensor", retrieved 7/16/2012
[35] "GE Zoneline® Owners Manual and Installation Instructions, Heat/Cool Model 2900, Heat Pump Model 3900", General Electric Corporation, [copy on file].
[36] "GE Zoneline® Owners Manual and Installation Instructions, Heat Pump Model 5800", General Electric Corporation, [copy on file].
[38] N Lu, YL Xie, Z Huang, "Air Conditioner Compressor Performance Model", U.S. Department of Energy, August 2008, [copy on file as PNNL-17796.pdf] Available to the public from the National Technical Information Service,
U.S. Department of Commerce, 5285 Port Royal Rd., Springfield, VA 22161
ph: (800) 553-6847, fax: (703) 605-6900
email: orders@ntis.fedworld.gov
online ordering: http://www.ntis.gov/ordering.htm
[39] Yinger R, R Bravo, and D Martinez. 2006 Air Conditioner Stalling Effects Study/Air Conditioner Testing
Procedures. Southern California Edison, Rosemead, California
[40] Bravo, R, R Yinger, and L Gaillac. 2006. Conditioner Stalling Unit Level Solutions Test Report. Southern
California Edison, Rosemead, California.
[41] Lu N, B Yang and Z Huang. 2008a. Evaluation of Southern California Edison Air-Conditioner Stalling
Solutions. PNNL-17686, Pacific Northwest National Laboratory, Richland, Washington.
[42] Danny S. Parker, John R. Sherwin, Bart Hibbs, "Development of High Efficiency Air Conditioner Condenser Fans", ASHRAE Transactions June 2005, [copy on file as FSEC-CR-1674-05.pdf]
Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Carson Dunlop Associates provides extensive home inspection education and report writing material. In gratitude we provide links to tsome Carson Dunlop Associates products and services.