Air conditioner compressor unit diagnosis & repair Questions & Answers:
These FAQs about the diagnosis or repair of the compressor/condenser unit assist in understanding what's wrong with the equipment and what to try next.
This article series discusses the outdoor components of air conditioners and heat pumps: how the air conditioning compressor-condenser unit works; the detection of defects in air conditioning compressor and condensing units, including evaluation of air conditioner compressor noises, hard starting, lost cooling capacity, and detection of a burned out compressor or A/C compressors at or near end of their life.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions & answers about repairing an air conditioner or heat pump compressor/condenser unit were posted originally at COMPRESSOR / CONDENSER REPAIR - you will want to review that page.
Our sketch of the condenser unit shown here was provided courtesy of Carson Dunlop Associates , a Toronto home inspection, education & report writing company. [Click to enlarge any image]
On 2018-10-19 by (mod) - signs of over-pressure in an A/C or heat pump compressor system
Jozef
regarding your question:
Air conditioning 12 LG outdoor unit, replaceable capacitor, inflammation starts and falls, shakes on swaps for two min.
What could i be t.j. is it still to be done?
...
say the mehanical it's comresor is die, not me posible starting compresor end stop, two min work end shake...,why is this?
Reply:
If the compressor started and ran normally for two minutes, then stopped after shaking, I would suspect an over-pressure condition on the "high-pressure" side of the system. That can be caused by a blockage in the high pressure refrigerant piping or a stuck or frozen TEV - thermostatic expansion valve.
If I am correct that we are speaking Croatian:
Ako je kompresor započeo i trčao normalno dvije minute, a zatim je zaustavljen nakon tresenja, pretpostavljam da postoji pretjerani pritisak na "visokotlačnoj" strani sustava. To može biti uzrokovano začepljenjem u visokotlačnom cjevovodu rashladnog sredstva ili zaporenim ili zamrznutim TEV - termostatskim ekspanzionim ventilom.
On 2018-10-19 by jozef - sta bih moglo biti t.j. sta dalje da se radi?
say the mehanical it|s comresor is die,not me posible starting compresor end stop ,two min work end shake...,w is this?
...sta bih moglo biti t.j. sta dalje da se radi?
klima 12 LG spoljna jedinica ,zamenjen kondenzator,upali krene sa radom i stane,protrese se na swakih two min.
On 2017-07-30 by joemarie
Is it ok when a condenser capacitor value is 15uf and i put 17uf
On 2017-06-06 by (mod) - Compressor is going on and off
As
At OPERATING DEFECTS, AIR CONDITIONING we list the common operating problems and suggest sequences of diagnosis and repair steps for them.
But cycling on and off at the compressor is not well-addressed there.
Diagnosis depends in part on the "on and off" frequency and regularity, and also on whether the problem is a recent one or one that has been present since the system was installed.
if the unit has always cycled as you describe we could be looking at an oversized thermostatic expansion valve - that causes a "seeking" behaviour that will cycle the system with some regularity
If the problem is new and the compressor cycling is frequent but irregular I'd look fist for a loose wire or loose or corroded connector, then for a failed control relay or control board.
On 2017-06-06 by asif
Compressor is going on and off
On 2017-06-06 by (mod) re: A/C compressor cycling on and off
Asif
At OPERATING DEFECTS, AIR CONDITIONING we list the common operating problems and suggest sequences of diagnosis and repair steps for them.
But cycling on and off at the A/C or heat pump compressor is not addressed.
Diagnosis depends in part on the "on and off" frequency and regularity, and also on whether the problem is a recent one or one that has been present since the system was installed.
if the unit has always cycled as you describe we could be looking at an oversized thermostatic expansion valve - that causes a "seeking" behaviour that will cycle the system with some regularity
If the problem is new and the compressor cycling is frequent but irregular I'd look fist for a loose wire or loose or corroded connector, then for a failed control relay or control board.
On 2017-06-06 by asif
Compressor is going on and off
Mark:
The concerns about running an A/C unit with the cover on would be around problems with overheating. Details are
On 2017-05-06 by Mark
my air conditioner was run accidently with the cover on. What kind of problem will that create? and how best to diagnose?
On 2017-04-29 by Anonymous
RLA for compressor is 13.44 i checked while running and it shows only 4.4 amp , is it compressor broke ?
On 2016-12-13 05:28:59.001907 by J
I have a Heil heat pump (8 years old) and the fan turns on for thirty seconds then off for five and continues to repeat this process over and over.
On 2016-09-21 00:04:25.372076 by karen
even when i turn off inside unit with remote outside unit continues to run?
On 2016-09-14 by (mod) re: icing on the suction line
Typically you see icing on the compressor itself and on the suction line remote from the cooling coil when there is low refrigerant in the system or when the refrigerant metering device, cap tube, or TEV or EEV is not working properly.
On 2016-09-14 06:42:50.001212 by bebesotek
why compressor and suction piping became icing ? LP = 55psi HP = 250psi
On 2016-07-04 03:42:24.384565 by (mod) re: compressor can't start: bad capacitor?
Possibly a bad capacitor;
Try turning off the system for 45 minutes or longer;
Then see if it can re-start.
On 2016-07-04 by Barry
Our heat pump stopped producing cold air. The outside evaporator fan runs and I hear the compressor trying to start. Would a capacitor be bad?
On 2016-06-22 by Anonymous
What is to check, its 50hz not 50/60hz. Somebody told me it will not give me as much cool as it suppose to be. Is it correct? I thought 60hz will make compressor to work faster, not slower?
On 2016-06-22 by (mod) will a mini split work on both 60Hz and 50 Hz power?
Check the manual and data tag. Often yes.
On 2016-06-22 01:28:35.297625 by Anonymous
Would 220/50hz mini split unit work with US 220/60hz apartment?
On 2016-06-04 by (mod) bad contactor or loose wire & other causes of a cycling A/C compressor
It could be the contactor relay or a loose wire or a bad sensor, or a sticking TEV or something else.
On 2016-06-03 by jason
when a condenser fan and compressor keep going off and on,Is it the contactor that is bad?
On 2016-06-04 by (mod) fan motor turns on but doesn't spin
The AC fan motor could be seized - is it humming? If so turn it off.
Or the motor may run but the fan is loose on the motor drive shaft
On 2016-05-27 by joseph re: fan motor won't rotate
what could be the problem of our carrier window airconditioner, the fan motor turns on but it does not rotate?
On 2016-05-26 by roberto zarate
how look a 24v coil in split system air condition
On 2016-05-18 09:51:23.911808 by Anonymous
Does the water from compressor base comes when AC in use..?
On 2016-05-08 by (mod) re: I was told a chipped reed valve cannot br repaired or replaced
Peg,
What you were told is correct. A/C or heat pump compressor motors are a hermetically sealed unit: the motor and components are in a "can". It is not possible to repair parts inside the unit. The repair is to replace the compressor motor; there are perhaps other reasons why your repair person wants to replace the entire compressor/condenser unit instead.
On 2016-05-08 by Peg
I was told a chipped reed valve cannot br repaired or replaced, so I require a whole new condenser. I've been unable to find information here about repair or replacement of reed valves. Please help me find the answer. Thanks!
On 2016-04-28 18:29:33.992824 by Anonymous
How to maintain level cooling tower
Y did codenser tube in used
On 2016-04-17 by (mod)
Sorry, I don't understand the question
On 2016-04-17 by heat falling air in blower inside the room
heat falling air in blower inside the room
On 2016-02-12 by (mod)
Rick, Sorry I don't understand the question. Compare the fusing size to the recommended fuse amperage on the data tag of your unit. Check for power on the circuit. Check for burned aluminum wiring on the circuit. Leave power off.
On 2016-02-12 by rick
Exchange air handerler fuse to a 20.amp an unit stopet after 2 days
On 2016-01-09 by (mod) re: how much ice on the cooling piping is OK
A small amount of ice on a refrigerant piping close to the unit is common and OK - (insulate the line); if the coil is icing then the unit won't keep working properly - that is in heat pump mode it won't provide heat to the home. A cause could be low refrigerant or a refrigerant metering valve that is not working properly. IN that case call your sevice company for repair.
On 2016-01-09 by Anonymous
I can't seem to find my questions in the Inspectapedia. I have ice build up on my outside compressor unit. It is working fine and the temp. outside is about 28 degrees. Should ice be forming around the unit?
On 2015-11-13 by (mod) re: loud noise when compressor condenser starts up
Not sure, Brandy. Perhaps a damaged compressor motor or a blowing fuse.
On 2015-11-13 by Brandy
What would make you outside unit make a loud noise when you first turn your heat on in the winter
On 2015-09-17 by chris
I tested the heat on my unit the other day worked fine the aux. Heat worked fine. Turned on the air today and the air wasn't cool I checke the outside unit and the coils were hot like the aux Heat was stuck on. What would cause this the thermostat inside didn't say it was on
On 2015-08-18 by (mod)
Terri I can't diagnose the vibration from just your email - it could be serious, such as a failing compressor, or something simpler like a loose fan or even just loose hardware. I'd ask for help from a local service tech as by making a repair you may avoid more costly damage.
On 2015-08-18 by Terri
We rarely need to run our air conditioner but recently had a heatwave. On the third day of running it a fairly loud vibration noise started. It was coming from the outside unit. We turned the air off at the thermostat then turned it back on after about one half hour. It would run fine then after a period of time the vibration would start again. I'm hoping it's an easy fix.thank you
On 2015-08-17 by (mod)
Princely
You can read our content copy and use policy in the comment just below.
You are welcome to make PRINTED copies of any web page at InspectApedia. Not electronic copies.
Regarding your request that we provide a PDF of the thousands of A/C articles at our entire website, No.
INSPECTAPEDIA.COM POLICY on use of our website content
We would be pleased for you to pass on to others links to articles or to use PRINTED (only) copies of articles or photos quoted from our InspectApedia.com website or if appropriate, to make and give away printed copies of our web page material in a class or professional presentation, printed text, printed article, or printed book, or in a classroom presentation, (such as power point slides that are not elsewhere reproduced electronically), provided you agree to respect these simple provisions:
1. Our website content is not going to be reproduced electronically nor, for example, copied or mirrorred online at a website or sent by email. Printed or “hard copy” versions of our web pages can be made and distributed without cost or restriction provided you leave the content un-changed and its source is identified.
2. You tell us specifically what content, article, or photo(s) you want to use in printed form or in a classroom. If you can describe other items or topics of interest, we almost always can provide higher resolution versions. In addition, with a library of nearly 100,000 photos, we can often provide additional examples of things you need to illustrate.Also, we can usually provide higher-resolution copies of our images on request.
3. Printed or class room photographs, text, content of (or online web page links to) our articles must clearly cite either our website home page InspectAPedia.com or alternatively, the specific URL address of the specific website page and article from which the material was copied.
4. Changes or corrections: If you find that you want to make changes or corrections to our material let me know. It is important that corrections are also made to the original – an action for which we are happy to give full credit, citation, links, etc. to our critics and contributors.
On 2015-08-17 by princely
hi,
your page has been helpful with hint on how to fix it yourself. i intend starting a diploma program in Refrigeration and Air conditioning. please I would like to have a pdf copy of the entire air conditioning section for educational/personal improvement purpose; my email is peppyetas@gmail.com thanks alot
On 2015-06-10 by (mod)
Donna I can't diagnose this from just your e-text; no one would, however, be able to patch a refrigerant leak with an external black gummy substance that I know of. More likely that's something else, perhaps sealing an opening where tubing passes or replacing damaged refrigerant tubing insulation.
IF your unit has lost refrigerant, indeed there is a leak to find and fix. Do not waste money by repeated re-charges of refrigerant (nor do we want to keep dumping refrigerant into the environment).
Surely the new work was warranted, right?
On 2015-06-10 by Donna
We had our air handler replaced just about 1 month ago but not the out side unit! I was surprised because the unit out side and in were put in when the house was bui!t in 1997. There was a freon leak in the unit inside. I was told there was no leak outside but there is a blue gummy substance where it looks as if the tried to patch a leak!
So why would someone not deem the whole system shot and replace the whole unit! Cause I seat here now with a non working unit again after dumping more than 800.00 into the unit on the inside and no freon in the unit yet again!
On 2015-05-29 13:45:14.084950 by Anonymous
I have a UPG Coleman 14.5 SEER 3 ton split unit. Unit is less than 3 years old. It runs almost all the time and the temp coming out of the registers is about 68 to 70 degrees. Return air is about 75 degrees. Coils are not iced up. TXV and reversing valves have been replaced. If set on 72 degrees, the temp goes up during the day to almot 79 degrees when 90+ outside. Unit is not producing cold air to keep a constantly cool temp inside. What is wrong with my unit?
On 2015-04-13 21:30:57.716140 by (mod)
Thank you Anil. We also welcome questions, critique, or content suggestions. Working together makes us smarter.
On 2015-04-13 20:32:50.878590 by ANIL KUMAR
Working of referent components is easily understandable . It is really good for beginners . Excellent.
On 2015-03-01 17:45:04.793430 by (mod)
Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies,
I've a Lennox outside a/c unit. The fan/motor and compressor are part of the unit. The fan was not spinning and the A/c is not running. I've isolated the problem down to the fan/motor or the compressor, but don't know how to check or find out which it is. Any idea on how to check if the fan/motor is 'bad' or the compressor is 'bad'? - Fan or ... 7/23/11
Fan or compressor: you could also have a bad control board, or relay switch in the compressor/condenser unit. If the fan is bad and the compressor is OK you'll hear the compressor turn on at the start of a cooling cycle, though a bad fan and system overheating could later cause some compressors to turn themselves back off. Similarly, if the compressor is bad your fan motor would still run. So I'm suspecting a control or switch problem./
the outside unit of the heat pump is icing up on the compressor - Steve 8/7/11
Hi my fan in my house goes on but my compressor unit does not all the electric seems to be fine . could it be my thermostat? - Sam 8/7/11
the accu very heat,although it is new gen. clean,2Tr LS-60psi & HS-100psi, - Anon 8/6/11
Steve: icing at the compressor/condenser sounds like a refrigerant charger or refrigerant metering problem.
Sam: if your thermostat turns on the air handler but the compressor/condenser does not run, the problem is not the thermostat. Check out the diagnostic suggestiosn beginning at LOST COOLING CAPACITY (link at the ARTICLE INDEX the bottom of this article )
Anon: those pressures look kind of low, no? What does your HVAC tech say about normal for that system?
I recently noticed my AC condenser unit still running when the system inside shutoff by itself. and also, does the condenser unit have to be leveled. I notice the slap which holding the unit is slopping. Any suggestions? Thank you. - Rick 8/16/11
A/C compressor/condenser won't stop running:
Rick usually when an A/C condenser unit won't stop running even though the inside equipment has shut off by itself my thinking divides into two investigations:
- is there a problem with the INDOOR unit such as a blower fan that won't start, an access door switch open, a condensate drain switch turning off the blower unit - these can leave the system calling for heat and the compressor running (though that's not good for the compressor)
- is there a problem with the outdoor equipment such as a bad control relay or control board
outside unit making loud cricket sounding noise when running. Takes long time to come on when temp set low. - JT 7/276/12
JT our link at the ARTICLE INDEX the bottom of this article NOISE AIR CONDITIONER / HEAT PUMP provides noise diagnostics.
About taking a long time for the A/C to "come on" when the temperature is set low: the thermostat is operating like an "on-off" switch that turns the air conditioner system on and off in response to room temperature. It's not an accelerator. So if there is an operating problem related to the system controls, the number of degrees below the room temperature to which the thermostat is set should make no difference in how long it takes the A/C system to start. As long as the SET temperature is lower than the room temperature the cooling system will turn on.
Anon said
when you turn on the AC for the first day of summer or heat how long would the unit circulate air then when does it stop
The length of time that the A/C will run depends on many factors including
- the thermostat set temperature
- the building temperature at time the A/C is tuned on
- the efficiency of and cooling power (BTUS) of the system
- where the air is delivered
- thermostat location
- the thermal mass of the building: what materials have been heated up and need to be cooled down
- the heat gain rate of the building
- outdoor temperature, wind, and sun exposure
The air will circulate and the A/C will run until the thermostat is satisified. If the system cannot satisfy the thermostat for any reason the system will keep running.
(June 30, 2014) Anonymous said:
Is it normal for there to be water coming out of the base of my compressor
Anon
Water at the outdoor compressor condenser is probably coming from melting ice or frost. If you see cycles of significant ice or frost build-up the refrigerant charge or metering may be incorrect and I'd ask for a check by an HVAC tech.
(July 13, 2014) Anonymous said:
i have a Carrier heat pump that i cant get the blower to come on. I have replaced the board and thermostat and not sure what to do next. Any suggestions?
(Aug 2, 2014) Lou said:
I have a carrier condensing unit that the compressor wont start.I have voltage at the contactor and have replaced the start cap and run cap.odd to say,im drawing 11 amps on start and run wires coming from the contactor but i hear nothing from the compressor! any suggestions?
Lou
Check for a bad start relay
(Aug 14, 2014) Andre Matthew said:
my AC is not cooling well don't know the problem with that.
(Aug 21, 2014) Wayne said:
When unit is cold it will start and run. After an hour the cooling fan stops but the compressor continues for a short time then quits. It will continue to start but will not start and run until it cools down.
Any ideas?
Look for an overheating fan motor, relay or control board or possibly a refrigerant metering valve that is sticking
On 2013-01-18 11:35:53.062599 by JR
DEAR SIR
I am an architect with limited technical knowledge of the mechanics of A/Cs but based on past experience I have noted that compressors are normally located externally to provide air circulation around them or else they'll pack up.
On one of the projects one of my colleague is currently involved with is where the building owner has specifically stated that he does not want anything including compressors or satellite dishes installed externally where they are visible. the mechanical engineer has instructed the sub-contractor to install these in a stair well.
My opinion is that this is not the correct location as the stair-well will heat up due to discharge from the compressors - which means we'd need to provide mechanical extract! but more importantly due to lack of fresh air the compressors will within a short time pack up and the A/Cs will not function.
The mech. engineer who disagrees with these observations! Please advise if I am incorrect in my observations and what are the remedies.
Please also note contractually we've done the paperwork in informing the mech. engineer that the instructions are incorrect and any malfunction of the system as a result will be his responsibility - so that has been taken care of but what I'd like to know is whether we can go around this problem by introducing ducts or substituting outdoor compressors with indoor units which are more cost effective
On 2012-11-28 18:44:41.274447 by Bryan
Do all condensers work with air handlers as long as they are of the same refrigerant oil?
On 2012-11-28 12:05:08.524329 by (mod) -
Compressor won't start,
Did anyone check the electrical circuit itself, including the wire size, run length, voltage levels, and current draw. .??
On 2012-11-28 12:02:35.868436 by (mod) -
David,
That sounds like a bad defrost cycle relay switch or a bad control board.
On 2012-11-28 03:59:10.229528 by David
My outside condensing unit has been missing the defrost cycle recently. Now, it will go into defrost cycle but will not return back to normal operation.
On 2012-10-30 11:11:13.079338 by Compressor won't start and the e
Sir i had installed a package type air condition (two fans at the outdoor), First time we start it running the circuit breaker will trip because where using a 15A circuit braker, that's why i change it to 30A circuit breaker. After replaced, the air condition will run but the compressor hard to start, and then the contactor will trip or it will trip directly when it will switch to cool mode..,The capacitor i used is 450V/60 micro farad, is this not enough to start this 220V,1 phase compressor?? and i already call an air condition technician, he conducted an inspection and testing, but still the same, that's why he ordered me to change a new compressor to replace it,,After the installation of new compressor still the same problem we face..He conducted again a testing,(change the capacitor,clean the contactor, bypass the overload relay, check the control board and wirings but still can't run the compressor it will always trip when it will switch to COOL mode...What will be the solution with this problem..?Please help me,,thank you...
On 2012-10-30 10:25:35.688660 by Giovani (10/2
SIr my package air condition type , the Compressor wont start and the contactor will trip,,What might be the cause with this problem???
On 2012-10-08 00:31:14.659949 by (mod) -
Jim
Not every unit uses a defrost cycle. If we had the model and serial number we might be able to looknup the unit specs.
On 2012-10-07 22:53:44.440038 by Jim
I have a very old Lenox heat pump system. The "contractor" said it is 40 years old. He mentions it needs a new Defrost Control Board (problem is the condenser fan always runs). I went snooping around the unit and could not find a board. It appears to be a direct 220V connection too condenser unit; capacitors and simple contactor. I found the contactor to be stuck. I freed it up and all seems fine. I will replace contactor. Is it possible that this old lennox heat pump does not have a defrost control board or should I keep looking? Can it be in the air handler?? Thanks.
On 2012-10-05 18:59:27.024237 by Anonymous
compresor sometimes comes onevaporater tub is dry
On 2012-09-21 21:12:53.990614 by Ken
The Heat Pump/Air Conditioner quit. It seems like an electrical issue. The reset button in not popped out. The fan is good/recently replaced-it turns in a breeze. The condenser was recently replaced. I let it sit but it is totally dead-no sounds, like an electrical interruption.
On 2012-08-29 16:56:50.453919 by Anonymous
Air comes on inside the house but not cooling. Found the condensor/compressor was not running outside. Called repair guy. Found a "circuit" type switch has tripped. When this was reset, the outside "compressor/condensor" came back on.
Before guy left, I noticed the fan was not turning. He turned system off, manually turned fan blades a bit by sticking screw driver in between grate, then powered back up and it worked.
Next day, (after turning air off), fan did not turn yet again. Did the fact that the fan was not turning indicate another issue that should have been explored?
WD-40, hosing/cleaning blades at a minimum? Possible start/run capacitor, relay switch or control board, (ideas from reading this site). they are supposed to come back out this afternoon. Want to be informed. Thanks.
On 2012-08-14 17:47:30.601477 by michigan
I need to cool a very warm room year round. Can I leave the compressor outside and running in cold winter temps?
On 2012-08-06 01:15:41.929869 by Pete Moreno
condensor will come on, but fan motor will make a hissing noise and will not turn.
On 2012-07-03 15:12:24.059405 by good
it's very useful to me,thank you.
On 2012-06-21 16:44:22.670475 by sibte, shah
Thanks so much for bringing this excellent , comprehensive and easy to understand article. God bless you
On 2012-02-24 01:44:27.008535 by rick
Need an narrow 13 or better seer outside unit Where to buy? Thanks Rick
On 2011-07-12 02:57:53.925164 by matt
Seems like it is a dead technology, can anyone share any new air conditioning technologies?
...
Continue reading at COMPRESSOR / CONDENSER REPAIR or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
COMPRESSOR / CONDENSER REPAIR FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.