This article describes the discovery, inspection, and significance of abandoned chimneys in buildings.
By "abandoned chimney" we do not mean simply a chimney that is not in use.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
A greater concern are chimneys that have been only partially removed, may not be adequately supported, and risk collapse, fire spread, heat loss, and other building concerns.
Our photo (at page top) shows the abandoned chimney in the attic below the corrugated metal roof in the photo shown in our
separate ABANDONED CHIMNEYS, OUTDOORS article.
[Click to enlarge any image]
Happily this chimney was not in use at the time of our inspection. Do you suppose someone might some day try to use this flue without checking it out first?
Carson Dunlop Associates [at REVIEWERS] sketch (left) demonstrates the need to repair the roof and add support where a through-roof chimney is removed above the roof line.
Abandoned chimneys may be discovered in an attic, basement, or even in the middle of a structure, and can be a big surprise. We often wonder what's holding up all this weight.
Someone may have eliminated a fireplace or an entire chimney on the lower floors, but neglected to remove the chimney from the attic out through the roof, perhaps because they didn't want to repair the ensuing hole in the roof left if the chimney were removed.
Point loads from unanticipated weight or even a sudden collapse can be a real hazard
if chimney bricks suddenly come through an upper floor bedroom ceiling.
Our photo (above) shows an unsupported chimney in the top floor of a pre-1900 home.
This chimney has it all (bad): the masonry chimney rests on floorboards between floor joists - it does not support its own weight. The chimney is cracked, damaged, and has evidence of a fire.
There is also danger of chimney collapse, damaging the structure and injuring building occupants should masonry chimney parts fall through floors or ceilings below.
The hole in the floor at the base of the chimney was a passage for a woodstove flue vent connector (with no fire protection or clearance) that connected into the upper opening in the chimney.
and
at FLUE VENT CONNECTORS, HEATING EQUIPMENT we show a closeup of the lower cleanout opening - which was blocked by falling debris.
Look for unsupported or inadequately supported masonry left in the building, sagging floors, or worse, on occasion you may find that the chimney was only "abandoned" above the roof, and that it continues to vent into the building attic. We found just that condition in a chimney trying to vent a gas fired furnace.
Our photo (above left) shows fiberglass stuffed into a round hole in a building surface. [Click to enlarge any image]
Regardless of whether you see this clue in a floor, ceiling, or wall, some investigation for the presence of a chimney behind the opening is an important safety check. Older homes were sometimes constructed with a single flue chimney that served appliances on multiple floors - an unsafe practice that is prohibited by modern building and fire codes.
Carson Dunlop Associates [at REVIEWERS] sketch (above right) shows a common "pie plate" cover over an un-used chimney opening. For safety the opening should be filled in with masonry. Be sure the repair leaves masonry flush with the chimney interior, not just the chimney's exterior side. Otherwise the repair may interfere with draft and it may make cleaning the flue difficult or impossible.
When an upstairs woodstove is removed the hole left in the chimney is best sealed with masonry material, not a metal cover plate, not insulation, not wood or drywall. Closing a chimney opening with those less durable materials leave a fire and flue gas leakage risk in the building.
Some of the hazards associated with incomplete removal of a masonry or even a metal chimney in a building include the items listed below.
Photo: a collapsed unreinforced stone fell on and smashed the family car. (In this case it was an earthquake, not a chimney abandonment).
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
@charlie cocca,
Thank you for a helpful question.
Sometimes chimneys are not removed on purpose. Our photo shows masonry chimney remains lined up in the street after the 1994 Northridge Earthquake in California.
[Click to enlarge any image]
In most countries and jurisdictions you will need a building permit and approvals from local authorities (such as building council in the U.K.) to remove an existing masonry (and some other) chimmey.
I have not found building codes that explicitly discuss
There are regulations concerning
I include examples of these below.
Where part of a fireplace or chimney is to be removed there are serious conerns for
Partially-abandoned and removed chimneys and the possible dangerous effects on structures and building code requirements (in the U.K.) are discussed in detail
at BRACKET CHIMNEYS & GALLOWS BRACKETS
In adopted and model building codes such as the IFGC International Fuel Gas Code (Chapter 5), and in model mechanical codes such as the two adopted mechancal code examples given below.
2015 CHAPTER 5, CHIMNEYS AND VENTS, SECTION 501 (IFGC), [PDF] (2015) Seattle building code, Retrieved 2017/07/22, original source: http://www.seattle.gov/dpd/cs/groups/pan/@pan/documents/web_informational/p2622099.pdf
we have:
This same requirement appears under other code numbers in other model or adopted fireplace and chimney codes such as the New York City Mechanical Code (2014) Chapter 8, Chimneys and Vents
From the British standard as well as from building regulations throughout the U.K. we have more details like the following:
If the chimney pot is removed and it is intended to slab over the chimney and continue to use the chimney,
by providing side outlets, then an area of at least 12 000 mm2 !per flue" on each of the opposite sides
should be provided in accordance with the dimensional requirements for non-proprietary terminals in 5.1.5. The outlets should be suitably protected to prevent bird entry.
A typical label that should be attached to an appliance should state “This appliance is fitted to a shared flue system and must not be removed or replaced without reference to the person responsible for the building, phone or contact details are ................. Further advice is given in BS 5440-1:2000.”
Let me see what else I can find in addition to what's listed above.
On 2021-05-21 by charlie cocca - what building code number or section deals with the regulations of abandoning a residential chimney ? t
what building code number or section deals with the regulations of abandoning a residential chimney ? thank you
On 2019-02-08 by (mod)
For the air movement issue I'd try packing the open chimney top with fiberglass - that ought to slow down the air.
But really we want to get the water out of the house, and I worry that there's a larger problem here with a wet crawl area that as I suggested can cause a range of troubles.
The spray foam, IF it was closed cell foam, would form a water and moisture barrier that would indeed stop a lot of air and moisture movement upwards through the floor.
On 2019-02-08 by Paul
Definitely no other sources of moisture or leaks possible in that area of the house. It can only be coming in from the ground/air in the crawl space.
I'll look to see if it is actually capped off rather than just cut off, and if not I'll see about stopping any air movement. Do you think adding a little insulation inside the chimney in the attic and capping it is sufficient, or do you think I should try to insert insulation further down into the chimney before capping?
I don't believe that the air is condensing on the chimney as the latex paint on is not wet on the surface and near the baseboard it is bubbling up, but I suppose it is possible.
The brick is covered with the original 1920s plaster which looks to have been steadily deteriorating over the course of the last 100 years. In another room I'm renovating, the brown coat of the plaster where it meets the chimney near the baseboard is turning to dust but higher up in the room the plaster is firm and dry.
Not sure if it matters one way or another, but in that part of the house the underside of the floor has been covered with spray foam insulation at some point.
I'll read through the crawl space dryout pages. Thanks for the tips so far!
On 2019-02-08 by (mod)
Paul
Is the moisture really "wicking up" ?
That may make a lot of sense if your outdoor drainage problems are sending water into the base of the chimney. If that's the root cause you really need to start at the problem source.
If you have a wet crawl space that's a moisture source that will continue to affect the building even when the chimney moisture transport issue is solved.
Search InspectApedia.com for WET CRAWL SPACE DRYOUT to see a sickeningly long list of suggestions.
Back to "wicking up moisture" to be sure we're on the same page:
In my lexicon "wicking up moisture" would be coming from a water source such as wet soil - at ground level.
If you are seeing moisture signs higher in the building and on or around and attributed to the chimney I would be looking for
1. air drafts up through the chimney, bringing moisture from some lower source such as a damp basement or crawl area
2. un-wanted moisture sources, leaks, water somewhere in the building
3. less likely - plumbing leaks in the same areas.
You can of course stop updrafts in an un-used flue by sealing its top - even fiberglass may do the job.
But you want to also look for the moisture and draft sources and address those.
I would not add a power fan and exhaust to stop updrafts and moisture as you describe - you'd actually be increasing the air movement up through the chimney, and if we are indeed bringing up moisture from some lower level, perhaps seeing it condense in the masonry, you'd be making that worse.
The other direction of thinking is to look at temperature differences.
Moisture in building air will condense out on cooler masonry surfaces.
On 2019-02-07 by Paul
I have a single story circa 1925 house with a chimney in the center of the 4 front rooms (each room houses one face of the chimney diagonally in the central corner). It is no longer used for any exhaust purposes and has been taken down about 5 feet below the roof line, so there is no danger of it leaking rainwater into the house.
I am experiencing moisture wicking up the chimney though. I added battens and sheetrock over one face of the chimney in one room as I remodeled and have noticed that this has caused efflorescence at the base plaster wall directly adjacent to the chimney. Also, I'm not certain but it is possible that this chimney provides structural support to the center of these four rooms.
Knowing that removing the chimney completely would be both costly and difficult (logistically speaking) and that crawl space access is nearly non-existent in that area, what can be done to mitigate the moisture wicking issue?
I am addressing some of the lot drainage issues which should help dry out the crawlspace, but what else can be done to dry out this chimney? Would placing some sort of ventilation fan at the top (exhausted through the roof) help? Any other suggestions?
On 2016-04-08 by (mod)
Len: I'm not quite clear on your comment. If a chimney was removed above the rooftop
1. the roof itself must be repaired to avoid leaks
2. the chimney below can usually be left in place unless it's a bracket chimney - see https://inspectapedia.com/chimneys/Bracket_Chimneys.php
or if the interior or even exterior chimney is severely cracked, bulged, leaning, (See "Severe Cracking" at https://inspectapedia.com/chimneys/Chimney_Crack_Diagnosis.php) or otherwise in danger of collapse (see https://inspectapedia.com/chimneys/Chimney_Collapse_Hazards.php ) , I'd agree that safest is to completely remove it.
On 2016-04-08 by Len
Existing chimney was taking down to the roof peak and appears to be unsealed. The heating system is direct vent and inlet combustion air. Water heater is electric.
I recommend that the chimney be inspected for structual integrity.
(Aug 2, 2014) ElaineS926@aol.com said:
I have a problem with an odor in one room, second floor, on the wall of the chimney, however we had a direct vent boiler installed to bypass chimney thinking the chimney was the problem of this odor like a burnt out match or moldy.
Can an unused chimney be the cause?
I also had all vents cleaned and air cond cleaned. Keep the room closed and unused.
Yes Elaine, creosote and other materials such as animals, dead animals, nests, can still be an odor source in an otherwise un-used chimney.
Try hiring a chimney sweep to inspect and clean the chimney interior. Then be sure there is a weather and invader-proof cap atop the flue.
...
Continue reading at ABANDONED CHIMNEYS, OUTDOORS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
ABANDONED CHIMNEYS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.