FAQs about why the heat won't turn off:
These diagnostic questions & answers can explain why you can't successfully turn of heat to all or part of a building: what to dow when there is too much heat or when the heat won't turn off.
This article series explains where and how to turn off the heat if simply turning down the thermostat does not stop un-wanted heat coming from heating radiators or baseboards.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
These questions & answers about trouble getting the heat turn off were posted originally at HEAT WON'T TURN OFF - topic home page. Be sure to see the diagnostic and repair steps given there if you can't get your heat to shut off.
On 2018-10-29 by Anonymous - even if the thermostat is clicked off our heat stays on.
Thank you so much for your response!
On 2018-10-27 by (mod) -
JenniOn 2018-10-27 by Jenni
We have a Thermostat that controls all of the heat upstairs (4BR’s and a bathroom) It controls the heat in all rooms except one just fine.
In our BR, even if the thermostat is clicked off our heat stays on. The baseboards are always hot! (We heat our home with oil if that helps) Please help! Any suggestions would be greatly appreciated!
On 2018-04-14 1 by (mod) - why are the baseboards still hot
Shawnda let's start in the HEAT WON'T TURN OFFarticle in the section titledOn 2018-04-14 by Shawnda
Hi my baseboard heaters will not turn off in my kitchen or livingroom i have two in the livingroom one is not on im guessing not working but the other one os on im able to turn off the analog heat switches in the other room just not thoses two and ot very hot please helpOn 2018-02-18 by (mod) - turning the thermostat down doesn't stop the heat
Anon, please take a look through the suggestions in HEAT WON'T TURN OFFWe're trying to diagnose the reason that we're getting heat when we're not asking for it.
Usually that's a check valve that's not working, a zone valve that's not closing, or occasionally circulator that doesn't turn off when it should. We find and fix the cause.
On 2018-02-18 by Anonymous
How to prevent heat from baseboards in 1 zone of house when turning thermostat all the way down for that zone doesn't stop the heat? Should I just close water valves for that zone?On 2018-01-19 by (mod) - heat not turning off is not liklely to be the low voltage transformer
CoolOn 2018-01-19 by cooldeep - Honeywell RTH6400D 24V thermostat
I had Honeywell RTH6400D 24V thermostat which I was using for heat only on two wires. Before that was old manual with mercury but working well but I changed for cosmetic reasons after consulting Honeywell.After 5 years this Honeywell RTH6400D thermostat was not turning off at set temperature and running continuously sometimes resulting in heating up of fuses in the main electric panel so to stop it we had to pull the fuse box out to cool down and put it back to start the thermostat again.
Before it was working good for one or two days after reset and then keep heat on continuously so we had to reset again by removing fuses.
We talked to Honeywell and they suggested new model RTH 111B but it also started behaving the same way which means the problem is not with the thermostat but somewhere in the thermostat transformer on the electric panel I don't know. Please provide some solution. Thank you.
On 2018-01-05 by (mod) - thermostat doesn't set back the heat at night
Look first fo r an incorrectly-set night time programOn 2018-01-05 17:28:45.572107 by jody
My thermostat heat WONT TURN OFF at night. It runs fine during the daylight hours. We go to bed with the thermostat set at 64. Once the house cools to 64 and the heat turns on ...
It wont turn off. We wake up and the thermometer reads 74 but the thermostat reads a lower inside temp.
So we turn the thermostat down to 60. It turns off for a few minutes and then back on and stays running..
A heating guy came out to look at it and says he cant find anything wrong. He has come out twice during daytime hours when it does work fine. Any ideas on why it wont shut off at night?
On 2018-01-05 by (mod) - heat won't turn ON at night
Sherri please see HEAT WON'T TURN ONOn 2017-12-10 by Sherri Campbell
We keep loosing heat at night. It clicks on but won't come on. And now temperature is reached but won't shut off. HELP PLEASEOn 2017-12-10 by David - my upstairs is cold.
My downstairs heat is fine, but my upstairs is cold. When I turn on the thermostat upstairs (even on Low) it gets very hot. Not regulating. Also 1 room gets no heat at all. Changed the thermostat, still having problems. What could it be?On 2017-11-02 by Steve
It gets complicated...I have 5 pumps and 5 zones...3 on the upper floor (baseboards) and 2 in the concrete basement floor. (designed in 1991...old technology, I assume). I have 1 check valve serving the entire system which is installed after the boiler and all of the pumps.
My current assumption is that the check valve is not being fully opened when the upper pumps are activated, which pushes hot water backwards through the lower floor zones.
Again, my pumps do not have a back-flow check valve. The basement is at 72 degrees, despite the thermostat setting of 68. If I turn the check valve to "manual" I get no back flow, but then I get gravity flow to the upper floor as was the case with my failed check valve from before.
I do have the capability to partially reduce flow through the basement, which should increase the pressure to the upper zones. Would this damage the pumps?
Steve
On 2017-11-01 by (mod) -
Steve,On 2017-11-01 by Steve
The check valve is installed correctly. From what I can see, determining the head press requires an amp measurement on the pump, which I don't how to doOne thing I've discovered is that when one of the pumps engages, there is water being circulated to the zone, but there is also "back flow" into one of the other zones, (my pumps do not have an anti-back flow valve). This tells me that the check valve is not opening completely. Again, when I turn the know to "manual", this back flow stops. Could it be a faulty check valve? Perhaps it's partially stuck?
Steve
On 2017-10-29 by (mod) - When my pump (Taco 007-F5) is engaged, it doesn't open the check valve.
I recall, Steve. Welcome back.And in the REFERENCES section of that article (at the page bottom) you can click to show references to find I&O manuals and instructions for these valves ( such as inspectapedia.com/heat/BandG_Flo-Control_Valves_Manual.pdf )
From B&G's submittal sheet for the HydroTrol Flow COntrol Valve A-444A it looks to me as if the valve should open at 0.5 psi.
FIRST CHECK: you have the valve installed with flow in the right direction, right? Check the flow arrows on the valve body.
SECOND CHECK: what is the head pressure (or feet of head) against which the circulator has to operate? Is it within range of the circulator's specs?
I might contact the company by phone, ask for technical support, and see if they have a different opinion.
Xylem Inc. (B&G)
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
On 2017-10-29 by Steve - a B&G NPT HydroTrol unti and it solved the n"gravity flow" problem
I was in contact with you this spring regarding the check valve problem. I have since installed a B&G NPT HydroTrol unti and it solved the n"gravity flow" problem. Unfortunately a new issue has arisen.When my pump (Taco 007-F5) is engaged, it doesn't open the check valve.
If I turn it "manual" the hot water flows easily. I measured the PSI differential across the pump. When it at rest: (20 PSI), the when the pump is engaged: (20 PSI after the pump and 18 PSI before the pump), so the pressure difference is 2 PSI. What is the activation pressure needed to open the HydroTrol valve? (The valve is located on the "after pump" side of the system)
On 2017-10-29 by (mod) - new flow control valve won't open when it should
I recall, Steve. Welcome back.
The B&G control valve about which you ask as well as the older traditional red B&G FLow Control valve are discussed at CHECK VALVES, HEATING SYSTEM
In that article I also mention your valve and give some links to documents for it.
And in the REFERENCES section of that article (at the page bottom) you can click to show references to find I&O manuals and instructions for these valves ( such as inspectapedia.com/heat/BandG_Flo-Control_Valves_Manual.pdf )
From B&G's submittal sheet for the HydroTrol Flow COntrol Valve A-444A it looks to me as if the valve should open at 0.5 psi.
FIRST CHECK: you have the valve installed with flow in the right direction, right? Check the flow arrows on the valve body.
SECOND CHECK: what is the head pressure (or feet of head) against which the circulator has to operate? Is it within range of the circulator's specs?
I might contact the company by phone, ask for technical support, and see if they have a different opinion.
Xylem Inc. (B&G)
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
On 2017-10-29 by Steve
I was in contact with you this spring regarding the check valve problem. I have since installed a B&G NPT HydroTrol unti and it solved the n"gravity flow" problem. Unfortunately a new issue has arisen. When my pump (Taco 007-F5) is engaged, it doesn't open the check valve.
If I turn it "manual" the hot water flows easily. I measured the PSI differential across the pump. When it at rest: (20 PSI), the when the pump is engaged: (20 PSI after the pump and 18 PSI before the pump), so the pressure difference is 2 PSI. What is the activation pressure needed to open the HydroTrol valve? (The valve is located on the "after pump" side of the system)
If we have radiant floor heating and it is turned off at the thermostat for the summer why is our place so much hotter in the summer. It is a new build.
We keep windows and shades closed to prevent more heat entering but it's 76-80 degree inside with fans and a window A/C on (set at 68).
The upstairs in 70 because that is where the AC is but downstairs is scorching. Help me figure this out...it was much cooler before we moved in. I even bought a new refrigerator to see if that was producing so much heat.
On 2017-07-24 by (mod) -
You need to unplug the heater. If you are physically unable to unplug the heater then you need to turn off the circuit that supplies that heater and have an electrician replace they receptacle end or cord connection.
On 2017-07-23 by Helen Elliott
A bar heater on a wall won't turn off. Cord jammed
On 2017-05-19 by (mod) -
Christopher,
More likely the problem is one of those listed in the article HEAT WON'T TURN OFF, such as a stuck check valve, or a zone valve that is stuck in the open position.
It's not likely to be a thermocouple or thermistor or a component in the thermostat. However you can easily rule out the thermostat as a cause by simply disconnecting it at the heating system.
On 2017-05-18 by christopher webb
I have baseboard heating in my apartment and it will not shut off. I have already put in a brand new thermistat and it is still on. Is the a thermal cuppler or a heating element that may need to be replaced?
On 2017-05-09 by (mod) - shorted wire in the electric heat control
Arthur it sounds as if there's a shorted wire in the electric heat control - try disconnecting the control wires first.
On 2017-05-09 by Arthur
I have a eletrice basebroad with low voltage themostat that the heat won,t shut off . I have replace thermostat. Could in be the step down tranformer or what should be my next step ,Thanks for any help
On 2017-05-01 by Steve
I finally got the lever to loosen and turned it clockwise, and it appears to make no difference. I assume that means the Flo-Control unit has failed.
Is there a newer check valve unit that can be used? (I have a 1+1/4" pipe). I see a brass B+G NPT HydroTrol unit that would be much easier to install and use, or do I need to get another red Flo-Control unit that I currently have?
On 2017-04-28 by (mod) - The valve appears to be stuck
Steve
Yeah I know what you mean; try loosening the locknut.
On 2017-04-27 by Steve
The valve appears to be stuck. I'm hesitant to twist it too hard for fear of breaking it.
There is a small hex nut at the bottom of the larger read valve. Does that need to be loosened? Also, the valve it pointing at the 5:00 position (6:00 being straight towards me), not parallel to the flow of water. Is that any indication? My valve does not have a "winter" stamp on it that I can see.
On 2017-04-27 by (mod) - how to figure out if the check valve is stuck OPEN
Good question, Steve.
Check valves like this one shown in my photo and discussed in this
article HEAT WON'T TURN OFF have a manual lever that can be put into a forced-open position.
At CHECK VALVES, HEATING SYSTEM we give details
about those devices.
Please see that article for details, including this phrase that I excerpt
Manually Open Flo-Control Valve: the valve is turned fully counter-clockwise to put the valve in a manually-opened position. This position may also be used to manually open the valve during filling of the heating system with water or during air-purging operations.
On 2017-04-27 by steve
How do you detect/troubleshoot whether the check valve is stuck in the "forced open" mode vs. a failed check valve?
On 2017-04-16 by (mod) - Why Are the Baseboards or Radiators Hot Even Though the Thermostat is Set Higher than Room Temperature?
Mary
In the article HEAT WON'T TURN OFF please read the section titled
Why Are the Baseboards or Radiators Hot Even Though the Thermostat is Set Higher than Room Temperature? Un-wanted Gravity or Convection Circulation of Hot Water
and let me know what questions remain.
D
On 2017-04-16 by Mary
What can i do when all thernostats are off but some baseboards are still on?
On 2017-04-16 by (mod) re: all thermostats are OFF but some heating baseboards are still ON
Mary
In the article HEAT WON'T TURN OFF please read the section
titled HEAT STUCK ON BY CONVECTION
Why Are the Baseboards or Radiators Hot Even Though the Thermostat is Set Higher than Room Temperature? Un-wanted Gravity or Convection Circulation of Hot Water
and let me know what questions remain.
On 2017-04-16 by Mary
What can i do when all thernostats are off but some baseboards are still on?
On 2017-01-25 by (Mod) re: what to check if the thermostat doesn't turn off heat; what to check if the thermostat doesn't turn heat on or off.
Rod: we provide diagnosis and repair advice for the thermostat-heater communication problem you cite
Zeb: check for a stuck zone valve or circulator relay. Also check for thermostat wires shorted together.
On 2017-01-25 by Rod
My thermostat and my hvac aren't communicating
On 2016-12-15 by Zeb
I am having a issue where heat in one zone will not turn off. The baseboard are staying hot all the time. I have two zones with two taco circulato pumps.
first zone works perfectly fine the second zone is having issues. this is what i did so far
unplugged the thermostate it didnt help ( even when heat is off from theromostate baseboard are still hot). I replaced the theromostate didnt help. Even when theromostate is completely disconnected and circulator pump not runing the pipe still stays hot.
On 2016-12-01 by (mod) re: how to re-set the heat anticipator on old round Honeywell thermostats
Search InspectApedia.com for HEAT ANTICIPATOR to see how the internal heat anticipator control is normally set. But that would not explain the problem you describe.
If heat is never turning off, and it's on in both zones, and if the boiler has adequate heating capacity for the building, then the problem is more likely to be at the boiler controls end.
Check that wiring is correct, then try disconnecting the thermostats entirely at the boiler end - at its aquastat. If the boiler keeps running you know the problem is not shorted thermostat wires nor a bad thermostat.
On 2016-12-01 3 by Hot
New boiler installed. Since new aqua stat installed heat stays on. 2 zone heating. Not thermostats as it is happening in both zones. On the old round thermostats what should the inside round control be set at in case this was tampered with.
On 2016-09-10 by Brian - The thermostat I hooked up ran continually but I did not realize that there are different thermostats
Hello, I figured out the problem but others might have the same problem. The thermostat I hooked up ran continually but I did not realize that there are different thermostats.
With a boiler system you have to use one approved for boiler. I was clueless. Hopefully everyone else is not quite as clueless as me.
Brian
On 2016-09-04 by pflans64
The Thermostat? Or just get management to bring in a heating repair technician ? Fall is coming. Need Help.. Thanks
Moved into older apartment building, Hot Water Baseboard heaters run along outer wall, Thermostat is turned all the way down. But Heat stays at 80° in apt:
Had building caretaker look at it.( No Luck) it comes in from heater threw two bedrooms in to living room where it ends with value.(Handle like a garden spicket) So I just shut it off. No more Heat, So What would you Start with?
On 2016-09-04 by Brian
Hello, I have a boiler system in my house with multiple zones. I have very old thermostats with Mercury.
Every tiem I install a new thermostat the heat continues to run no matter the temperature it is set at. As soon as I put the old one on the temperature is regulated properly. I am not buying fancy thermostats, they are simple honeywell ones with two wires. Any thoughts? Thanks so much, Brian
On 2016-06-21 by (mod) re: why is one radiator still hot
Anon, chances are the problem is one of those listed in the
article HEAT WON'T TURN OFF.
or a circulator that won't stop because of shorted thermostat wires or a bad control relay
or a zone valve stuck open
On 2016-06-21 by Anonymous
Turned off central heating 5 radiators off 1 still throwing out the heatOn 2016-04-29 by richard
i recently became a maintenance assistant at a assisted living facility. i was in a apartment that has an old round honeywell thermostat to control a forced hot water hydronix heating system. the room stays very warm and the thermostat reads 74-76 degrees even though i turned the thermostat all the way down.
Is this a problem with the thermostat or something else i should look into. thanks for any help on this problem.
On 2016-04-07 by (mod) re: why would removing a radiator make another radiator not turn off?
Cynthia:
It'd be odd for the removal of a radiator on another floor to make your unit run hotter, unless there was some strange plumbing in your place. You need someone onsite to follow the pipes, find the controls and then see how your heating system works.
Meanwhile try closing the input valve on that hot radiator.
On 2016-04-07 by Cynthia Traugott
I live in a 40 yr old apartment with hot water heat.
My upstairs neighbor removed at least one radiator during a renovation. Meanwhile, one of my radiators has continued to run hot, even though the thermostat is turned off. I think the problem is due to his renovation.
The strata ordered and paid for a new zone regulator in my suite, which didn't help. So, is this just a coincidence and I suddenly need to replace that radiator, or will that even help?
I'm thinking it has something to do with my neighbor's renovation-----gravity----water flows down, etc. I'm not a plumber and I don't understand how all this works. Can you help me out with some info or advice?
On 2016-03-03 by (mod) re: tracing a York problem to a bad control board or shorted control wires
Basically this problem will almost always be traced to a control or control board problem, thermostat failure, shorted thermostat wires, or an open check valve; occasionally of course heat runs continuously because of low outdoor temperatures, indoor thermostat setting, and a high rate of heat loss from the building.On 2016-03-02 by Anonymous
Having same problem. ..did u get any resolutions to York problem?On 2016-02-01 by Too hot
Hi we're having an issue with the heat randomly rising, first thought problem was thermostat so changed that, then replaced again because I thought first replacement might be a dud. I have thermostat set at 70, wake up hot and it's reading 82.
Switch from heat to ac, and ac doesn't kick on, keeps blowing hot. Flipping breaker has been helping,after flipping ac will start to kick on, but this last time, it took an hour for it to finally kick on.
Flipped breaker, (thermostat set to cool) heat turned on, attempted couple more times, same thing, then left breaker flipped off for an hour, came back and flipped back on,cool air is now blowing on. This has been a repeated issue for two weeks now.
On 2015-12-12 by ray
Changed thermostat but heat stays on in radiator(Jan 4, 2013) Nick said:
I have a Honeywell round thermostat and the space temperature sensor does not respond to the actual space temperature. in order to turn the heat on or off one must adjust the set-point above or below 65 deg. Are there any tricks to breathing some life back into the sensor or is it time to replace the assembly?
Thanks,
-Nick
(Jan 16, 2013) Larry Morris said:
I have base board heaters. 2 in my living room, one in each room and its two room apartment. The heaters are heating up on their own even when I am not turning on the thermostat. I am now receiving $200 monthly bills from the electricity company and a shut off notice because its so high.
I dont understand why they are doing this. Can someone provide some clarification on this situation as I do not want to be without power with my wife and kid. Thanks.
(Feb 18, 2013) Jay said:
My thermostat is working for AC. But for my heating system, it didn't turn off the heat at desired temp. What might be the problem? Any help?
I have baseboard-radiator heat, 3 different zone circulator pump so only the upstair is having the problem. I used GRUNDFOS UPS15-58FRCV 59896343 pump. After reading all these, looks like "check valve" is the problem, but is that my check valve in built with my pump?
If yes, the can I just fix the problem by replacing the circulator pump... Any help is appreciated.
(Jan 24, 2014) Chike said:
My heater won't turn off despite trying all the advice given. What do i do? the heat is becoming unbearable.
If heat continues when a thermostat is set to a temperature below room temperature, or when the thermostat is disconnected entirely then I suspect one of the problems discussed at HEAT WON'T TURN OFF and also HEAT STUCK ON BY CONVECTION
(Apr 3, 2014) John said:
I have a Peerless MI-05. The unit will run periodically when the room temperature is above the thermostat setting. The unit will also run when the thermostat is set to "off." It will turn on and fin every twenty minutes, for about three minutes.
The contractor that installed the unit blamed the problem on federal regulations and, eventually, the President of the United States. Could it be a fault other than the President's?
John,
I'd start by disconnecting the thermostat wires at the boiler end. That will rule out a wire short that an cause the problem you describe. I've also seen this problem as an artifact of the primary aquastat. It's a potential for a fist-fight that's to be avoided IMO.
If you read the installation instructions for a Honeywell aquastat (like the R818x series) you'll see that the mfg wants you to use a heat conducting paste on the sensor when it's mounted in the sensor well on the boiler = thus assuring good thermal contact between the aquastat's temperature sensor and actual boiler temperature.
The fellows like to skip this extra work and worse, will be very reluctant to go back and correct it as you'd have to R&R the whole assembly from the boiler in most cases. But that too could be at fault.
John also check the Aquastat settings.
(Apr 3, 2014) John said:
Dan,
Thank you for your reply. This unit was installed in February of this year. I have no experience with this type of equipment. It is safe to say that the unit is not working properly and we can rule out new federal regulations that require it to run as it does? The contractor is begging for a political debate when I just want the boiler to work properly. Thank you very much for your help!
Reply:
If you are not already speaking with the company's service manager, give that person a polite call and ask for help from someone more experienced. If there is no higher authority you're stuck with the guy you have or bailing and hiring someone else. Sorry.
(June 9, 2014) xenaon said:
i rent from a bad guy. He shut off the wall switch - which shut off the fan. Before, if I turned on the wall switch - the AC went on. Now, it doesn't. Inside my apt the AC and Furnace breakers are fine. 3 hours later, the bully shut off the gas water tank downstairs - turning the switch horizontal, then setting it to off and vacation, so the pilot light is out.
I cannot relight the pilot - turn on the gas line, hold down the pilot valve - won't light.
I cannot find a way to turn on the Rheem Criterian II gas/AC unit. What else needs to be turned on? Thermostat (Honeywell) does not ignite the AC or fan or heat - but it could not possibly be the thermostat as the person who shut off the fan switch - also turned off the water heater.
(Sept 17, 2014) Edgar Cruz Sr said:
The burners are lit & staying on,even though we are not calling for heat from a 2 wire thermostat,please advise.
Check for shorted thermostat wires
(Oct 4, 2014) Anonymous said:
I am very grateful for my landlord its very hot in here we have radiator s they should all have a leavle to shut off
(Dec 14, 2014) Anonymous said:
I have a tenant who is complaining that the heat will not go down even though the thermostat has been at its lowest setting. I have gone there twice and both times, the pipes after the zone valve feel room temperature, but the thermostat is still showing the room is at 75.
I took off the baseboard covers and showed her how the pipes are room temp and immediately get boiling hot when the thermostat calls for heat.
My question is, could there be a tiny amount of hot water sneaking past the zone valve that almost doesn't register as hot when you touch the pipes, but still warm enough to keep heating the room? It's probably been averaging 20s-30s here in Minnesota lately.
She's on a third floor with units above below and on either side, but I can't imagine the residual heat from those units would heat hers to 75. I used to live there, but don't recall this problem.
Any help is appreciated.
If the room temp is high, say 75F, indeed I'd expect the baseboard to be close to that temp even if there is no call for heat.
You might be seeing some convection circulation if a flow control valve at the boiler is not fully closing when the circulator is off, or if a zone valve is not fully closing.
But I'd look for
- improper thermostat settings
- a bad thermostat location - in a draft for example
- a dust or debris clogged thermostat sensor
(Dec 17, 2014) Anonymous said:
I've set my thermostat the the factory settings but it will not stop heating up. At the moment the reading is locked at 62 but it's already hit 75! What am I doing wrong??
Mick.
Anon have you tried the diagnostic suggestions in the article HEAT WON'T TURN OFF? You may not be doing anything wrong yourself.
8 Jan 2015 liz the landlord said:
The temp in my apartment is over 80 degrees. There is a sensor in the unit. The main thermostat is located in the basement. It has been set to 65 and below. I just turned it down to 62 and closed all the valves on each radiator. I think that my sensor is not working and since it is so cold in the basement, THAT unit is registering the temp, and firing the boiler. It is constantly going. I would love to hear what you might suggest.
Liz
First we need to get clear what thermostat is controlling just what. I can't know the wiring of controls at your building from just your e-note.
When the thermostat in your apartment is set well below the actual present temperature, feel the radiators, convectors, baseboards - whatever is your heat source. If they are hot and thus are the heat source (as opposed to heat coming from a neighbour or other source) then I suspect a control or thermostat is mis-wired or the thermostat wires are shorted together somewhere, thus always calling for heat.
(Feb 25, 2015) Mary said:
I have a two zone baseboard heating system. I've turned by downstairs thermostat off but heat is still coming thru the baseboards. Upstairs is fine.
Mary, in HEAT WON'T TURN OFF see the section titled
"Why Are the Baseboards or Radiators Hot Even Though the Thermostat is Set Higher than Room Temperature? Un-wanted Gravity or Convection Circulation of Hot Water"
There we address this situation and suggest that there may be a check valve that's not working.
A less likely explanation is that the circulator controls and thermostats are not wired correctly. If this is a new problem and the system wiring has not been changed, then this less likely explanation is still less so.
(Apr 8, 2015) lkmoore2009@live.com said:
why does fan come on even though the thermostat is in the off position, no heat comes out just air, even took batteries out still fan comes on and off
LK
Forced warm air furnace fans are controlled by a limit-switch on the blower assembly. The fan might turn back on at the end of a heat cycle if the heat exchanger is still hot enough to re-warm the supply air plenum and thus the fan limit switch sensor even if the burner is off.
If the problem seems recurrent and random and not related to the end of a heating cycle I'd look for loose wires, fan-on wires from the thermostat shorted anywhere en route, or a bad control board (depending on your equipment).
You can rule out the thermostat wiring by disconnecting it entirely not at the thermostat end but at the furnace end.
Details are at FURNACE FAN CYCLES AFTER HEAT
...
Continue reading at HEAT WON'T TURN OFF - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see
Or see these
HEAT WON'T TURN OFF - FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about troubleshooting too much heat or heat that won't turnoff in a building.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.