Types & definitions of HVAC duct & flue dampers, vibration dampeners, and fire dampers found in buildings.
This article defines and describes barometric dampers, draft regulators, automatic flue dampers, draft inducers, zone dampers, HVAC supply register controls, fire dampers, automatic fire and smoke dampers, fireplace dampers, and fresh air inlet dampers and controls.
We include photographs of each type of damper or dampener used in buildings or in building mechanical systems and we provide links to in-depth articles describing the choices, installation, inspection, troubleshooting and repair of all types of building and HVAC system air controls, dampers and dampeners such as automatic and barometric flue dampers used on heating equipment, coal stove, pellet stove, woodstove draft controls, draft inducer fans, HVAC duct air flow controls (manual register controls, duct dampers, zone dampers, automatic fire dampers, vibration dampeners), fireplace dampers, and fresh air supply dampers and controls.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This article catalogs and describes all types of air and draft regulation devices used in buildings where control of heating appliances is needed.
Direct-vented heating appliances that vent flue gases outside without using a chimney are typically operated by a power vent fan in or at the heating appliance. These vents don't use a barometric damper for draft regulation.
See DIRECT VENTS / SIDE WALL VENTS
An automatic flue damper is a device (shown below) that closes the heating flue when the furnace or boiler is "off" so that we won't continue to lose building heat up the chimney - it's a device to reduce heating costs and save on heating oil consumption.
When the heating system has turned off at the end of an "on" cycle of burning fuel, the automatic flue damper electric (see sketch above and photo at left) motor turns a baffle inside of the flue vent connector pipe to a position "across" the pipe so that the airflow inside the pipe is blocked or stopped.
Don't confuse an automatic flue vent damper with other "damper" devices: a heating system automatic duct damper or a duct fire damper or a heating zone damper.
A barometric draft control, also called a "damper" or barometric damper, is a hinged, weighted door on an opening at a heating flue. The key difference between a barometric draft control or flue damper and an automatic flue damper is that the barometric damper operates by barometric pressure or natural draft while an automatic flue damper is operated by an electric motor.
The door opens or closes to let extra air into the flue to assure that the draft in the flue remains constant at the proper setting needed for proper heating system operation.
Coal fueled heaters use manual dampers in the coal stove flue or for larger and automatically-fed coal fired boilers or furnaces the system may incorporate a thermostatically-operated automatic flue damper to control both draft and thus the system's heat output.
The coal stove shown at above left was installed by the author (DF) in the 1970's. A slider along the stove bottom permitted the user to adjust the air intake rate - a necessary combustion and heat control since the installation of this stove in front of a small fireplace gave no access room for a flue damper control.
The second fireplace-inserted heater at above right is a coal stove that was designed to also burn wood. This wood/coal heater, installed by Paul Galow in New York in the 1970's, also had a sliding air intake control and no accessible flue damper.
The vertical lines you see in the glass front of each of these coal burners allowed the installation of glass that would not fracture due to thermal expansion, allowing the occupants to enjoy watching the fire. Yes ultimately these get broken by a careless occupant or user, putting the stove out of use until the glass could be replaced.
Watch out: if the incoming combustion air cannot be shut down because of leaky coal stove gaskets or other damage like the broken glass in the coalstove door, the coal stove is unsafe as its burn-rate cannot be regulated.
See CHIMNEY FIRE ACTION / PREVENTION
Also see FIRE CLEARANCES WOOD & COAL STOVES
I have a Alaska channing 111. My barometric damper is 6 in then [the flue vent connector goes to 8 in to connect ] to massonary chimney.
It seems I need two dampers. I installed a manual damper to help
My question is can I put 2 baro dampers in the same flue to control proper draft
Thanks, Bill
Bill
Watch out: I infer that you are getting too much heat or having trouble controlling your coal stove. This condition can be unsafe and in fact in extreme cases can cause a house fire.
See COAL STOVE OPERATION & SAFETY for detailed suggestions on solving this problem with your coal stove. There we repeat your question and answer it in detail.
A draft inducer is a booster fan that increases the flow of combustion gases up a chimney. In our photo at above left you can see the black motor and bronze-coloured fan cage of a draft inducer fan mounted underneath the flue vent connector between the oil fired boiler and the concrete block wall that affords entry into a chimney (not visible).
Draft inducers are used when there is a problem with the chimney or heating equipment installation that prevents natural draft from working adequately.
We discuss draft inducer or "draft boosting" fans for heating systems (and maybe for some fireplaces) in detail
at DRAFT INDUCER FANS.
Zone dampers are manual or electrical (thermostatically controlled) baffles that open or close in heating or cooling air ducts to control heating or cooling zones in buildings.
Details about zone dampers are
at ZONE DAMPER CONTROLS
An automatic duct damper is a mechanical device (shown above), usually controlled by a room thermostat, which opens or closes a metal baffle inside of a warm air (or cool air) heating (or cooling) duct in order to provide multiple heating zone control in a building.
You can see photographs of and read about manual and automatic heating and air conditioning zone dampersA manual duct damper, also referred to as a manual HVAC zone damper, is a hand-operated baffle that can be turned to open or close a heating or air conditioning supply duct to thus control the flow of conditioned air into a building area.
Our photo below shows a manual duct damper control handle on an older (asbestos-paper-covered) heating duct. When the handle long axis is parallel to the ductwork (our blue line) the air flow is fully open (the red arrow).
Details about manual HVAC duct dampers are
at MANUAL HVAC ZONE DAMPERS.
The most-common means of controlling heating or cooling air delivery out of an individual duct or zone is the opening or closing of individual supply air registers. A lever on the supply register grille permits opening or closing a baffle that controls air flow out of the duct system just at this individual register.
Details about individual supply air register controls are
at AIR REGISTER for ZONE CONTROL
Control of the entire duct zone is possible using a
manual (DUCT DAMPERS, MANUAL) or
automatic (DUCT DAMPERS, AUTOMATIC) duct zone control damper.
A fire damper is required to prevent the spread of a building fire or smoke through air conditioning and heating ducts in some commercial installations and possibly by local residential building codes in some jurisdictions. Fire and smoke dampers are typically required in office buildings, health care facilities, and other commercial structures.
The automatic fire/smoke damper operates (usually) by automatically closing a door or doors within the damper on the detection of a temperature increase or by operation of a separate smoke detector.
Our photo at below left shows a pair of open fire damper doors in the ceiling of a commercial building in New York City. In event of a fire these doors are intended to be automatically closed. Similar dampers may be installed right in HVAC ducts where the ducts pass between different building areas.
More about the photo of ceiling return air plenum fire dampers shown at above left is
at RETURN AIR REGISTERS & DUCTS
A fire damper might work similarly to an automatic duct damper, but its purpose is quite different: in the event that a fire is detected in a building or in its mechanical systems, (by heat or smoke or other means of fire sensing), the fire damper closes off the air duct to avoid spreading smoke or fire rapidly through the building. The fire damper is otherwise normally "open".
See photographs of and read details about automatic fire dampers and automatic fire/smoke dampers
Duct vibration dampers or properly called vibration dampeners are fabric joints placed in HVAC ductwork to prevent the transmission of vibration and noise from the air handler of a heating or air conditioning system into the ductwork and through the ductwork into the occupied spaces of a building.
Details about duct vibration dampeners are found
A fireplace damper is a metal door installed in the fireplace chimney throat. To avoid wasting building heat by sending it up the chimney when a fireplace is not in use, the fireplace damper door is closed when the fireplace is not in use.
Our sketch below, provided by Carson Dunlop Associates and used with permission, shows the location of a fireplace damper in the chimney flue where a woodstove or fireplace insert has also been installed.
Details about fireplace dampers, their installation, inspection, repair, replacement, and defects are
at FIREPLACE DAMPER DEFECTS, REPAIRS
Definition of Fresh Air or Outdoor Air Supply Dampers & Controls
Outdoor air or fresh air is supplied (or can be or often should be) supplied to combustion equipment such as gas or oil or other fuel fired heaters as well as to fireplaces or woodstoves. Outdoor or fresh air is also supplied to the HVAC duct or air delivery system to improve indoor air quality. Below we list articles describing these various outdoor air or fresh air supply controls.
You can see photographs of and read about fire dampers in ductwork or read about strategies for managing building fresh air intake at
Our photo below shows a kerosene heater installed in an older New York Home. There is no visible draft control on this heater's flue. Instead the user regulates heat by controlling the fuel flow level.
[Text and illustrations are in process, text, comments, photo, contributions are invited. CONTACT US]
Pellet stoves usually make use of a draft fan for proper burning, though in event of a power failure some models permit limited operation using natural draft.
Illlustration: The AGP Pellet Stove from Lopi, Travis Industries, excerpted from the company's instruction manual cited below.
Travis Industries recommends a minimum vertical vent of 5’ to ensure adequate draft
during a power outage.
Other pellet stove installation manuals, for example the Harman Pellet Stove cited below, specifically describe using a manometer to check the appliance draft and may provide a mechanical adjustment of the combustion motor speed.
Harman specifies a normal pellet stove "high" draft (for their model) of -0.50 to -0.60 inches of W.C. (Water Column) and normal pellet stove "low draft) of -0.35 to -0.45 in. W.C.
Details are
The combination wood-oil fueled heater shown above regulates draft by a combination of Input air and oil burner adjustments at the oil burner and a barometric damper regulated draft when the heater is being fired using heating oil (indicated in yellow)
A themostatically operated combustion air inlet regulates the wood fire when the heater is being fired using wood. In this mode a barometric damper may be replaced with a manual draft control or an automatic draft control in the exhaust flue between the heater and its chimney (green arrow 1, 2, 3, 4)
Details of wood-oil combination heaters and the difficulty of attempting to control draft on these devices are now found
at WOOD-OIL COMBINATION DRAFT CONTROL
I'm not so sure the wood burning stove shown above is a fire-safe installation, but you can plainly see the manual flue damper handle (pointed-to by our blue arrow) in the rusty flue section about 30 inches above the top of the woodstove.
When the damper handle's long axis is parallel to the flue the damper is in its fully open position.
Details of how this control is used are at
Also see
...
Continue reading at DRAFT REGULATOR, DAMPER, BOOSTER or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
DAMPERS & DRAFT REGULATOR TYPES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.