Bath vent fan installation, troubleshooting, repair FAQs:
Questions & Answers on how to design, size, install, wire, or fix bathroom vent fans, ducts, switches & controls.
This article series describes how to install bathroom ventilation systems, fans, ducts, terminations. We include bathroom venting code citations and the text also explains why bathroom vent fans are needed and describes good bath vent fan choices, necessary fan capacity, and good bath vent fan and vent-duct installation details.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Questions & answers about bathroom ventilation codes, ducting, termination, posted originally at BATHROOM VENTILATION CODES SPECS - be sure to review that article.
FAQs on How to install, specify or improve bathroom venting, reduce indoor condensation, avoid bathroom mold. Bathroom vent fans, required bath vent fan capacity, fan noise and sones.
Bathroom vent fan ducts, where to route vent air, duct condensation, ceiling leaks; Photographs of bad or ineffective bath fan installations.
On 2016-10-18 by (mod) - move the bath exhaust fan & light to gain wiring access
VV:
Perhaps you could install the new fan/light in a new location, moving it just 6" or so in a suitable direction, so that you can use the existing gang box for wiring connections and so that you can make the existing box accessible by a cover plate.
On 2016-10-18 by (mod) -
joon said:
good information, thank you so much admin, i come back again this blog,
On 2016-10-14 by vvicci@aol.com
have a problem where there is a 2 gang box in the ceiling of a bathroom on the first floor that is hidden above and connected to a fan/light combo. the box feeds other lights and switches. access, because it is embedded in the ceiling, is not available and therefore not code.
i would like to install a new fan/light if possible with a larger 2 gang wiring box built in (most only have enough room for the switch/power connection just for the unit). do they exist or is there a work around?
thanks
bill
On 2016-09-12 by (mod) - New YorkCity Bathroom Ventilation Code Excerpts
A very detailed building code guideline beyond the IRC I cited below is the New York City housing code from which I excerpt this Bathroom Ventilation Code:
§[C26-1207.3] 27-759 Bathrooms and toilet rooms.-Bathrooms and toilet rooms shall be ventilated as follows:
(a) When ventilated by natural means, the natural
ventilation sources shall comply with section 27-749 of
article six of this subchapter and shall have an
unobstructed free area of at least five percent of the
floor area. In no case shall the net free area of the
ventilation sources be less than one and one-half square
feet except that in occupancy groups H-1 and H-2,
provided the ventilation opening conforming with
section 27-749 of article six of this subchapter may be
in a vent shaft provided that the net free area of the
opening is not less than three square feet. The vent shaft
cross-sectional area shall be increased by one-fifth of a
square foot for every foot of height, but shall not be less
than nine square feet in area and open to the outer air at
the top; or, the vent shaft may be open at the sides
above the roof with louvres providing an equivalent net
free area at the top, equal to the area of the shaft.
(b) By individual vent shafts or ducts constructed of
noncombustible materials with a minimum cross-sectional
area of one square foot and one-third additional square
foot for each additional water closet or urinal above two
in number. The upper termination of such ducts shall be
equipped with a wind-blown ventilator cap.
(c) When a bathroom or toilet room is not ventilated by
natural ventilation as required by this section, it shall be
mechanically ventilated as follows:
(1) Rooms containing only one water closet or urinal
shall be mechanically ventilated by an exhaust system
capable of exhausting at least fifty cubic feet of air per
minute. Means shall be provided for air ingress by
louvres in the door, by undercutting the door, or by
transfer ducts, grilles, or other openings.
(2) Rooms containing more than one water closet or
urinal, and any auxiliary spaces such as those used in
hand basins, slop sinks, and locker rooms, shall be
mechanically ventilated by an independent exhaust
system capable of exhausting at least forty cubic feet of
air per minute per water closet or urinal. The outdoor
air supply shall conform to the requirements of article
seven of this subchapter.
(3) Toilet exhaust systems shall be arranged to expel air
directly to the outdoors.
On 2016-09-12 by (mod) - down-vented bath exhaust
Todd:
I don't have a clear understanding of the situation. In general, you can try venting a bath vent fan "down" but the combination of down-direction, elbows, and total run length may mean that it's ineffective.
Take a look at the installation manual for your fan brand and model. The manufacturer will give guidance on the total duct length permitted. Adding elbows and bends increases the "effective" duct length (shortening what's allowed) as would blowing "down".
I've seen OPINION by some builders and web page authors that venting a bath vent "down" is "best" and that it "respects the laws of physics". I'm not sure what physics class those authors attended.
Warm air wants to rise, so pushing that air "down" and out is harder for a bath fan than blowing it upwards and out. The authors are, I think mixing up the importance of avoiding backdrafts with the importance of providing a vent duct size, routing, length that make the fan work effectively.
Perhaps some confusion about up or down venting also arises because it IS good practice for an overhead fan duct to slope down 1/8 to 1/4" per foot so that any condensation in the fan drips out of the wall vent or soffit vent rather than back into the bath ceiling.
I also prefer using solid metal duct or solid PVC piping as a bath vent fan duct rather than thin mylar or plastic flex duct - you'll get better and safer airflow.
At the wall termination you'll need to install a vent termination cover that
1. closes to prevent back-drafting when the fan is not running. Typically the cover closes by gravity and works fine.
(Unlike a clothes dryer vent (where lint clogging is a fire safety issue) you can screen a bath vent outdoor termination with 1/4" or 1/2" mesh (2006 IRC [305.5]) but that won't prevent a cold backdraft if wind is blowing towards the opening. )
2. prevents critters from entering or nesting in the duct system
It's smart to insulate the vent ducting too, reducing condensation in the duct from exposing the warm moist bath air to cooler crawl space (or attic) air.
Locate the bath vent fan high in the bathroom - high on an exterior wall when you can, or on the ceiling where it can pick up steamy air from a bath shower.
Watch out: as we warn elsewhere, if a bath fan or light is close to or can be touched by someone in a tub or shower it must be on a ground fault circuit interrupter (GFCI) protected circuit lest your installation kill someone who's naked and wet.
Bath venting codes: see the 2006 (or later) International Residential Code IRC R303.3 Bathroom Ventilation - requires that when natural ventilation requirements (3 sq ft of windows 50% operable) can't be met, the bath should be vented by either a 20 cfm continuous vent fan or a 50 cfm vent fan that is intermittent (or switched). Exhausting of the bath vent fan must indeed be to the building exterior.
"Exhaust Air from toilet rooms and bathrooms shall not discharge into attic, crawl space or other areas inside building."
On 2016-09-12 by (mod) -
Jane:
You can vent two fans through a common duct provided the duct size, length, number of bends meets the manufacturer's specs. Watch out for back-drafting out through the fan opening that is not running when the other one is. If that problem occurs your installer will need to either vent the fans separately or add a one-way backdraft preventer in the ductwork .
Fans vary in noise - measured in sones. A problem is that noisy fans tend to be left OFF so a bath may not be vented when it should be.
On 2016-09-12 by Todd
We have built an addition to our house. The bathroom fan vent was run to the outside of the house but was removed as the addition surrounded vent. The contract nicely wrapped the exhaust hose around the fan and installed the roofing with out re plumbing it.
All the floor joists have some kind of wiring or vents running through them. Would it be alright to exhaust the bathroom fan air under the addition as there is to vents on either side of the addition. I would have to cut a hole through the wall to get to the next room to install the vent outside. This is a down stairs bath.
On 2016-09-12 by Jane
Hi Guys
Can someone tell me whether you can run 2 fans (in the same bathroom) through one lot of ducting? One appears to be quieter and less powerful than the other.
Many thanks for any advice offered.
On 2016-06-03 by Mark
Agreed.
(Sept 26, 2014) James said:
I have come across your site 3 times, as I continue to get our recently purchased 1950's home up to snuff. Excellent resource, great photos, and very detailed explanations. Just wanted to say thanks for your effort!
(May 16, 2014) Kevin said:
Are there any restrictions on how close an exhausting bath vent may be placed to an exhausting vent for a gas water heater? Both exhaust vents will terminate outside through a side wall. Thanks.
Kevin,
Clearances for gas fired appliance sidewall vent terminations are given in detail at
inspectapedia.com/chimneys/Direct_Vent_Chimneys.php - side wall & direct vent clearances
You will see that the required distances range from 1 foot to 7 feet depending on what's being cleared-from.
If the bath vent respects the gas fired exhaust (chimney / flue) vent clearances you should be ok.
(May 21, 2014) Mary. Question said:
My builder has installed a small 4" extractor fan in a newly created utility room with a door to outside, but no windows. The fan has been installed on the outside wall which is 30 cms thick. It will blow out through the old metal ventilation grille.
My worry is that he has not lined the 'duct' with anything other than plaster. I cannot see any plastic or metal material lining the hole. Is this acceptable? Won't I be getting damp air in my brickwork?
Mary I'm not sure I've got the whole picture, but I'd agree that a metal or plastic duct liner would have made cleaning easier and would have reduced the chances of damage should moisture accumulate in or condense on the sides of the air path.
If it's easy to paint and thus seal that surface that'd help. Sounds a bit odd.
(Aug 20, 2014) rob said:
we had rough in electrical inspection and it passed and went back and seen our electrician vented ours to the attic and there it lay i live in pa how did that pass? other than their all close friends with each other?
Rob:
about the mistake of incomplete routing of a bath vent fan I can't *know* but I can offer speculation based on experience:
1. The electrician is not someone who is going to want to cut a hole in a roof, gable end nor soffit - nor might s/he know how to properly flash and seal that opening against leaks.
2. The electrician wants to finish the job quickly and get paid and go home for a beer and to watch the World Cup on TV.
3. The building inspector doesn't want to crawl into a hot attic, and furthermore, cannot possibly inspect every detail of every job - so over time the inspectors tend to get to know individual contractors and to trust (or not trust) their work, making just spot checks on it. It's not a matter of being close friends or of bribes.
You need to vent the fan properly to avoid a moisture problem down the road.
(Sept 7, 2014) Anonymous said:
Can I vent a bathroom into the attic space that has soffit vents and a ridge vent?
Anon:
Physically you "can" but it's a bad idea, sending moisture into a building cavity rather than outdoors invites mold, insect damage, rot.
Vent bath exhaust to the outdoors not into an attic.
(Sept 15, 2014) Anonymous said:
Thanks, will look to vent to the outside but was hoping that the air flow from the soffit to the ridge vent would carry out the moisture
Reply:
Anon
Well air flow may carry moisture but enroute, flowing across attic surfaces it will also deposit it on cooler surfaces - leading to mold-sorrows later.
(Sept 17, 2014) Redpoint said:
I want to install a four port remote bathroom fan in my house. I have a conditioned attic where the 4" thin walled PVC pipes will run. I have two concerns; first when I have this running for one bathroom i don't want it sucking all the heat out of my house (in winter) from the other 3 bathrooms.
How would I prevent this from happening? Second I have some long runs in my conditioned attic (60-70ft) is this too long and should I pitch the pipes or worry about condensation ? Thanks
You might want to use an air to air heat exchange ventilation system instead.
(Nov 5, 2014) Peter said:
Can you vent a bathroom fan into the chimney?
No. Don't do that.
Nov 13, 2014) Gene said:
We get a sewer smell in two of our four bathrooms in the fall when it turns cold and also in the spring. It's usually short lived but is lasting longer this time. The same smell is also in a few spots outside our home. Toilets are not loose and bathrooms are well vented. Any suggestions ? Any help would be appreciated. We live on an acreage but have city plumbing...no septic.
Gene,
Even if a toilet is not loose it could have a failed wax ring seal.
You might also be facing odors exacerbated by partly clogged drains or defective vent piping.
(Dec 8, 2014) Anonymous said:
What's the best way to vent a 1st floor guest bath that has a half story above it? Should I just go straight to the outside wall of the bathroom, through the brick? Or should I try to go around the upstairs rooms to get to the gable attic, and to a vent there? The second just seems like a long distance, but I can't find much info about venting out the side of the house.
Anon the best answer is site specific - depending on framing and construction details such as which way ceiling joists run I might go into the ceiling and then out through the wall, or I might place a vent right into the exterior wall.
Shorter distances are of course better.
(Dec 24, 2014) joyce said:
how might I stop the blown in attic insulation from entering the bathroom thru the ceiling vent when the wind blows thru the attic window vent?
Joyce
Your installers needed to adequately seal or baffle around ceiling vents, ducts, HVAC air intakes, etc. to keep insulation in its place.
There is a more serious worry here if your bath vent is for a ceiling exhaust fan: loose fill insulation that enters a power-operated bath vent can clog it leading to overheating and a fire.
(Dec 24, 2014) Anonymous said:
Dan, thanks so much for this reply. Yes, the bath fan is for exhaust of moisture during shower, etc. I live in a home well above a lake, when the wind blows hard (often) I then note fine particles of insulation on the bathroom floor and other surfaces.
I have an attic vent on a gable style roof line and hear the wind blowing thru.....at this time, I have in place plastic over the vent until I can figure out what to do. Not using the fan. Yes! conerned re: fire..thanks so much.
Reply:
Joyce
take a look at our notes about wind-washing - blowing attic insulation from air entering at soffits
inspectapedia.com/Energy/Cathedral_Ceiling_Ventilation.php#WindWash
(Dec 29, 2014) Katrine said:
We moved into a house built in 1999 in north Florida and learned that the bath exhaust fans are connected to the HVAC ductwork and not to the outside. Is this acceptable? We have had problems with high indoor humidity even when the air conditioning is running.
Katrine
I can't be as smart as an on-site expert who will see important details we can't, but what you describe sounds wierd to me. Exhaust fans should exhaust to outdoors, not blow moisture or odors into the HVAC system. It sounds to me as if someone took an improper shortcut.
(Dec 30, 2014) Katrine said:
Thanks for your reply. I am following up on this with the buildings inspection office and getting everything rerouted properly.
(Apr 23, 2015) Jim said:
Why is the air from my bathroom exhaust fan blowing down into the bathroom instead of blowing up and out?
Jim
Some bathroom fixtures combine a light, exhaust fan and heater. If your ceiling fixture includes a heater it may be on and blowing air down.
If your fan is ONLY an exhaust fan then it's running backwards OR there is no exhaust vent.
(Aug 3, 2015) Carole said:
I have a combination light/exhaust/heater in bathroom ceiling. It looks like blown insulation in the vent blades. Hate to think I am breathing this. What do I do?
As the bath is normally going to blow air out rather than into the bathroom, it ought not be blowing anything onto you. However if the fan is not properly-installed or if its ducting is damaged, attic insulation could be falling into the room below.
Start by identifying the suspect material; most-often you'll see gray dust accumulating on the intake louvers of a vent fan as house dust, principally fabric fibers and skin cvells, is deposited to the surface of the fan while air passes into it.
(June 26, 2016) Rgrigsby said:
Question, several years ago we had 2 bathrooms redone! The venting was redone at the time. The vent material was light weight foil. Run through the ceiling and the second floor.
Bird move's in to the cheesy duct and in the process of the bird evacuation the line is damaged and is not accessible without removing the drywall in the ceilings. What are the odds of those lines meeting code.
I can't guess at the code compliance issues, though you could ask your local code inspector for an opinion; the installation is largely hidden by reality (the ceiling) and remoteness (e-text). However there should have been an appropriate vent guard on the exterior wall = that usually is what keeps the birds out.
Since you've got who-knows-what bird pathogens in the ceiling it might make sense to do enough demolition to remove the nasty old birded-duct and install new material.
See BATHROOM VENT CODES for details about the allowable screen size on bath exhaust vent terminations.
(Aug 18, 2016) Toni said:
I recently had a contractor come in and replace a 20 yr old bath exhaust fan in my condo. I did not watch the process, however due to the "accessibility" of the existing ducting, he was forced to use flexible ducting to connect the new fan. I intentionally requested a 1 sone fan for obvious reasons, however the fan noise level is inaudible due to the now very low "wind tunnel" noise.
The contractor advised that because he was forced to install flexible ducting, this is what I was hearing. In order to repair with rigid ducting, he would have to open the ceiling up further. Is it likely that the flexible ducting is what is causing this flapping wind tunnel noise? Thanks
sorry my last comment should have stated " very LOUD "wind tunnel" noise...not LOW.
Tony I can't know quite what's going on from an inspection by e-text, but a key word in your note is "flapping" - something is loose. I'd want to inspect and find what that is before spending a lot on a new approach to the exhaust duct.
Flex duct, properly installed in a bath fan, would be stretched out with no extra material and ought not be flopping nor flapping around.
Also check for a loose flapper door on the vent duct termination outdoors.
Noisy bath vent fans can also be traced to use of a reduced exhaust vent duct size. The duct size must be at least the same as the diameter of the fan's discharge port. Here is a typical manufacture's warning:
Duct work size must be a minimum of the discharge and should not be reduced. Reducing the duct size can increase fan noise.
To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc., off power unit. - Ventilation Fan with light and Heater, Model RAD80L, Delta Breez Ventilation System, [PDF]
2016/09/12 Jane said:
Hi Guys
Can someone tell me whether you can run 2 fans (in the same bathroom) through one lot of ducting? One appears to be quieter and less powerful than the other.
Many thanks for any advice offered.
Jane:
You can vent two fans through a common duct provided the duct size, length, number of bends meets the manufacturer's specs. Watch out for back-drafting out through the fan opening that is not running when the other one is. If that problem occurs your installer will need to either vent the fans separately or add a one-way backdraft preventer in the ductwork .
Fans vary in noise - measured in sones. A problem is that noisy fans tend to be left OFF so a bath may not be vented when it should be.
Also seeFAN NOISES in BUILDINGS
Also see AIR LEAK NOISES in BUILDINGS as duct leaks can also be noisy.
2016/09/12 Todd said:
We have built an addition to our house. The bathroom fan vent was run to the outside of the house but was removed as the addition surrounded vent.
The contract nicely wrapped the exhaust hose around the fan and installed the roofing with out re plumbing it. All the floor joists have some kind of wiring or vents running through them.
Would it be alright to exhaust the bathroom fan air under the addition as there is to vents on either side of the addition. I would have to cut a hole through the wall to get to the next room to install the vent outside. This is a down stairs bath.
In general, you can try venting a bath vent fan "down" but the combination of down-direction, elbows, and total run length may mean that it's ineffective. Take a look at the installation manual for your fan brand and model. The manufacturer will give guidance on the total duct length permitted. Adding elbows and bends increases the "effective" duct length (shortening what's allowed) as would blowing "down".
Please see BATHROOM VENT DOWN THROUGH FLOOR / CRAWL AREA for a detailed reply to your question.
...
Continue reading at BATHROOM VENTILATION - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see BATHROOM VENTILATION FAQs-2 - more-recent Q&A about proper exhaust ventilation for bathrooms
Or see these
BATHROOM VENTILATION FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.